Product
Program controller PCA1Handling Company
Shinko Technos Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Cold junction compensation accuracy | Control output DC current | Control output non-contact voltage (for SSR drive) | Control output relay contact 1a1b | Event output EV1 to EV4 relay contact 1a | H (mm) | Input DC current | Input DC voltage | Input resistance thermometer | Input sampling period | Input thermocouple | Number of patterns | Number of steps | Program time range | Repeat count | Setting resolution Setting temperature | Setting resolution time | Standard accuracy measurement DC current DC voltage | Standard accuracy resistance thermometer | Standard accuracy thermocouple | Time indication accuracy | W (mm) | Weight value |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
PCA1 |
Available upon quote | Within ±1℃ from 0 to 50℃ | 4-20mADC resolution 12,000 load resistance up to 600Ω | 12VDC±15% max. 40mA (with short circuit protection) | Control capacity 3A250VAC (resistive load) 1A250VAC (inductive load cosΦ=0.4) Electrical life 100,000 times | Control capacity 3A250VAC (resistive load) 1A250VAC (inductive load cosΦ=0.4) Electrical life 100,000 times Event output One side of EV3 and EV4 is a common terminal | 96 | 0~20mADC, 4~20mADC input impedance 50Ω Allowable input current 100mA or less | 0 to 10mVDC, -10 to 10mVDC, 0 to 50mVDC, 0 to 100mVDC, 0 to 1VDC Input impedance 1ΩM or more Allowable input voltage 5VDC or less Allowable signal source resistance 2kΩ or less (0 to 1VDC) | Pt100, JPt1003 conductor type allowable input conductor resistance resistance per wire 10Ω or less However, PT100-100.0 to 100.0 is 5Ω or less | 125ms | K, J, R, S, B, E, T, N, PL-Ⅱ, C (W/Re5-26) External resistance 100Ω or less However, for B input, external resistance 40Ω or less | 16 patterns (can be connected) | 256 (16 steps/pattern) | 0 to 99 hours 59 minutes/step or 0 to 99 minutes 59 seconds/step (If you set -----, fixed value control is performed with step SV) | 0 to 9,999 times (If set to 0, repeat operation will not occur) |
Thermocouple, RTD input without decimal point: 1°C (F) Thermocouple, RTD input with decimal point: 0.1℃ (F) For DC voltage and DC current input: 1 |
1 minute or 1 second | Within ±0.2% ±1 digit of each input span | Within ±0.1% ±1 digit of each input span | Within ±0.2% ±1 digit of each input span However, R and S inputs 0 to 200°C (32 to 392F) are within 6°C (12F) B inputs 0 to 300°C (0 to 572F) are outside the guaranteed accuracy range | ±0.1% of setting time | 96 | Thermocouple, RTD input without decimal point: ± (0 to 100) °C (F) Thermocouple, RTD input with decimal point: ± (0.0 to 100.0) °C (F) |