Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-THV-10PZ020-5*NNN-N
Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-RKC INSTRUMENT

Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)
RKC INSTRUMENT

RKC INSTRUMENT's Response Status

Response Rate

100.0%

Response Time

14.3hours

Relatively Fast Response


About This Product

■All models have CE marking, UL and cUL certified

All models are CE marked and certified to overseas safety standards (UL, cUL). *For CE marking, use of the specified noise filter complies with the CE marking.

■Data monitoring and settings are possible via host communication (optional)

- You can monitor and configure settings using external devices using RS-485 communication. You can monitor current and power values, and manage parameter switching based on the control target from the outside. ・Monitor items: current value, power value, power supply frequency, external slope setting monitor, alarm monitor, input signal monitor, phase angle ratio monitor, etc. ・Setting items: Internal manual setting, internal gradient setting, soft up/down time, various alarm setting values, current limiter value, output mode selection, RUN/STOP, etc.

■Transmission output allows easy connection to measuring instruments (optional)

- Equipped with loader communication function as standard. ・Can be connected to a computer via USB using the converter COM-KG. You can easily save various settings and setting values ​​to your computer, and upload various setting values ​​from your computer to the THV-10. *Loader communication is for setup only. Do not use it for control or operation.

■Equipped with a wide range of functions as standard

It comes standard with a wide range of functions such as automatic/manual switching, slope setting function, soft up/soft down function, external contact input, two-position control, and loader communication.

■About 50% lighter*

The 20A/30A type has achieved significant weight reduction. The weight of the control panel and control box can be reduced. *Comparison with our THV-1 (20A, 30A)

■Reducing the size of the transformer without limiting the magnetic flux density of the transformer (optional)

The transformer primary side control function can suppress excessive currents caused by momentary power outages on the load side (transformer). When controlling the primary side of a transformer, use a transformer with primary side control function. There are no restrictions on the magnetic flux density of the transformer.

■Heater disconnection with non-linear load can be detected.

- Up to 3 inflection points can be set according to the characteristics of the heater. It can also be used with loads (such as lamp heaters) that have large resistance changes due to temperature. - Automatic setting of inflection point is possible. *Other product numbers are available.

  • Product

    Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)

Share this product


270+ people viewing

Last viewed: 45 minutes ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

10 Models of Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Power frequency Applicable load phase control Output limiter time at startup Startup output limiter (upper limit) Load power supply voltage Alarm output Permissible ambient humidity Permissible ambient temperature Insulation voltage Insulation resistance Absolute humidity Power consumption Minimum load current Rated current Gradient setting Control method Control power supply voltage Output voltage range Output limiter (lower limit) Output limiter (upper limit) Leakage current when output is OFF Cooling method Input signal Input/output plug side connector included Transmission output or communication function Base up setting (output bias) Heater burnout alarm, current limiter function, etc. Zero cross control Manual settings Input sampling period
Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-Part Number-THV-10PZ020-5*NNN-N

THV-10PZ020-5*NNN-N

Available upon quote

50/60Hz shared (automatic detection)
Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz

Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less)

0~600 seconds (front key)

0.0~100.0% (front key)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

No alarm output

5~95%RH (no condensation)

-15~+55℃ (guaranteed operation range)

Between main circuit terminal and heatsink: AC2,500V, 1 minute
Between power terminal and heatsink: AC2,500V, 1 minute
Between main circuit terminal and input terminal: AC2,500V, 1 minute
Between power terminal and input terminal: AC2,300V, 1 minute

Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V
Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V
Between power terminal and input terminal: 20MΩ or more, DC500V

MAX.W.C 29g/m3 dry air at 101.3kPa

6VA or less (at AC100V) Inrush current 5.6A or less
8VA or less (at AC240V) Inrush current 13.3A or less

0.6A (at 98% output of rated voltage)

AC20A

0.00~2.00 (front key)
0.0~100.0% [External setting device (volume)]

Phase control/zero cross control method (Factory: Phase control)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

0~98% of load power supply voltage
(Excluding voltage drop due to fuse)

0.0~100.0% (front key)

0.0~100.0% (front key)

Approximately AC27mA rms or less
(Load voltage 200V rms 60Hz Ta=25℃)

Natural cooling

DC0~10V

None

No function

-9.9~100.0% (front key)

No function

Resistive load

0.0~100.0% (front key)
0.0~100.0% [External setting device (volume)]

10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz

Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-Part Number-THV-10PZ020-5*NNA-N

THV-10PZ020-5*NNA-N

Available upon quote

50/60Hz shared (automatic detection)
Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz

Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less)

0~600 seconds (front key)

0.0~100.0% (front key)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

No alarm output

5~95%RH (no condensation)

-15~+55℃ (guaranteed operation range)

Between main circuit terminal and heatsink: AC2,500V, 1 minute
Between power terminal and heatsink: AC2,500V, 1 minute
Between main circuit terminal and input terminal: AC2,500V, 1 minute
Between power terminal and input terminal: AC2,300V, 1 minute

Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V
Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V
Between power terminal and input terminal: 20MΩ or more, DC500V

MAX.W.C 29g/m3 dry air at 101.3kPa

6VA or less (at AC100V) Inrush current 5.6A or less
8VA or less (at AC240V) Inrush current 13.3A or less

0.6A (at 98% output of rated voltage)

AC20A

0.00~2.00 (front key)
0.0~100.0% [External setting device (volume)]

Phase control/zero cross control method (Factory: Phase control)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

0~98% of load power supply voltage
(Excluding voltage drop due to fuse)

0.0~100.0% (front key)

0.0~100.0% (front key)

Approximately AC27mA rms or less
(Load voltage 200V rms 60Hz Ta=25℃)

Natural cooling

DC0~10V

None

Transmission output [continuous voltage output DC0-10V]
*Transmission output plug side connector included

-9.9~100.0% (front key)

No function

Resistive load

0.0~100.0% (front key)
0.0~100.0% [External setting device (volume)]

10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz

Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-Part Number-THV-10PZ020-5*NNB-N

THV-10PZ020-5*NNB-N

Available upon quote

50/60Hz shared (automatic detection)
Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz

Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less)

0~600 seconds (front key)

0.0~100.0% (front key)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

No alarm output

5~95%RH (no condensation)

-15~+55℃ (guaranteed operation range)

Between main circuit terminal and heatsink: AC2,500V, 1 minute
Between power terminal and heatsink: AC2,500V, 1 minute
Between main circuit terminal and input terminal: AC2,500V, 1 minute
Between power terminal and input terminal: AC2,300V, 1 minute

Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V
Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V
Between power terminal and input terminal: 20MΩ or more, DC500V

MAX.W.C 29g/m3 dry air at 101.3kPa

6VA or less (at AC100V) Inrush current 5.6A or less
8VA or less (at AC240V) Inrush current 13.3A or less

0.6A (at 98% output of rated voltage)

AC20A

0.00~2.00 (front key)
0.0~100.0% [External setting device (volume)]

Phase control/zero cross control method (Factory: Phase control)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

0~98% of load power supply voltage
(Excluding voltage drop due to fuse)

0.0~100.0% (front key)

0.0~100.0% (front key)

Approximately AC27mA rms or less
(Load voltage 200V rms 60Hz Ta=25℃)

Natural cooling

DC0~10V

None

Communication (RS-485) [RKC standard communication]
*Communication plug side connector included

-9.9~100.0% (front key)

No function

Resistive load

0.0~100.0% (front key)
0.0~100.0% [External setting device (volume)]

10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz

Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-Part Number-THV-10PZ020-5*NNC-N

THV-10PZ020-5*NNC-N

Available upon quote

50/60Hz shared (automatic detection)
Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz

Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less)

0~600 seconds (front key)

0.0~100.0% (front key)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

No alarm output

5~95%RH (no condensation)

-15~+55℃ (guaranteed operation range)

Between main circuit terminal and heatsink: AC2,500V, 1 minute
Between power terminal and heatsink: AC2,500V, 1 minute
Between main circuit terminal and input terminal: AC2,500V, 1 minute
Between power terminal and input terminal: AC2,300V, 1 minute

Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V
Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V
Between power terminal and input terminal: 20MΩ or more, DC500V

MAX.W.C 29g/m3 dry air at 101.3kPa

6VA or less (at AC100V) Inrush current 5.6A or less
8VA or less (at AC240V) Inrush current 13.3A or less

0.6A (at 98% output of rated voltage)

AC20A

0.00~2.00 (front key)
0.0~100.0% [External setting device (volume)]

Phase control/zero cross control method (Factory: Phase control)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

0~98% of load power supply voltage
(Excluding voltage drop due to fuse)

0.0~100.0% (front key)

0.0~100.0% (front key)

Approximately AC27mA rms or less
(Load voltage 200V rms 60Hz Ta=25℃)

Natural cooling

DC0~10V

None

Communication (RS-485) [MODBUS communication]
*Communication plug side connector included

-9.9~100.0% (front key)

No function

Resistive load

0.0~100.0% (front key)
0.0~100.0% [External setting device (volume)]

10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz

Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-Part Number-THV-10PZ020-5*NAN-N

THV-10PZ020-5*NAN-N

Available upon quote

50/60Hz shared (automatic detection)
Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz

Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less)

0~600 seconds (front key)

0.0~100.0% (front key)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

1 point alarm output *Input/output plug side connector is required.

5~95%RH (no condensation)

-15~+55℃ (guaranteed operation range)

Between main circuit terminal and heatsink: AC2,500V, 1 minute
Between power terminal and heatsink: AC2,500V, 1 minute
Between main circuit terminal and input terminal: AC2,500V, 1 minute
Between power terminal and input terminal: AC2,300V, 1 minute

Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V
Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V
Between power terminal and input terminal: 20MΩ or more, DC500V

MAX.W.C 29g/m3 dry air at 101.3kPa

6VA or less (at AC100V) Inrush current 5.6A or less
8VA or less (at AC240V) Inrush current 13.3A or less

0.6A (at 98% output of rated voltage)

AC20A

0.00~2.00 (front key)
0.0~100.0% [External setting device (volume)]

Phase control/zero cross control method (Factory: Phase control)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

0~98% of load power supply voltage
(Excluding voltage drop due to fuse)

0.0~100.0% (front key)

0.0~100.0% (front key)

Approximately AC27mA rms or less
(Load voltage 200V rms 60Hz Ta=25℃)

Natural cooling

DC0~10V

None

No function

-9.9~100.0% (front key)

No function

Resistive load

0.0~100.0% (front key)
0.0~100.0% [External setting device (volume)]

10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz

Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-Part Number-THV-10PZ020-5*NAA-N

THV-10PZ020-5*NAA-N

Available upon quote

50/60Hz shared (automatic detection)
Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz

Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less)

0~600 seconds (front key)

0.0~100.0% (front key)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

1 point alarm output *Input/output plug side connector is required.

5~95%RH (no condensation)

-15~+55℃ (guaranteed operation range)

Between main circuit terminal and heatsink: AC2,500V, 1 minute
Between power terminal and heatsink: AC2,500V, 1 minute
Between main circuit terminal and input terminal: AC2,500V, 1 minute
Between power terminal and input terminal: AC2,300V, 1 minute

Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V
Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V
Between power terminal and input terminal: 20MΩ or more, DC500V

MAX.W.C 29g/m3 dry air at 101.3kPa

6VA or less (at AC100V) Inrush current 5.6A or less
8VA or less (at AC240V) Inrush current 13.3A or less

0.6A (at 98% output of rated voltage)

AC20A

0.00~2.00 (front key)
0.0~100.0% [External setting device (volume)]

Phase control/zero cross control method (Factory: Phase control)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

0~98% of load power supply voltage
(Excluding voltage drop due to fuse)

0.0~100.0% (front key)

0.0~100.0% (front key)

Approximately AC27mA rms or less
(Load voltage 200V rms 60Hz Ta=25℃)

Natural cooling

DC0~10V

None

Transmission output [continuous voltage output DC0-10V]
*Transmission output plug side connector included

-9.9~100.0% (front key)

No function

Resistive load

0.0~100.0% (front key)
0.0~100.0% [External setting device (volume)]

10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz

Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-Part Number-THV-10PZ020-5*NAB-N

THV-10PZ020-5*NAB-N

Available upon quote

50/60Hz shared (automatic detection)
Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz

Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less)

0~600 seconds (front key)

0.0~100.0% (front key)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

1 point alarm output *Input/output plug side connector is required.

5~95%RH (no condensation)

-15~+55℃ (guaranteed operation range)

Between main circuit terminal and heatsink: AC2,500V, 1 minute
Between power terminal and heatsink: AC2,500V, 1 minute
Between main circuit terminal and input terminal: AC2,500V, 1 minute
Between power terminal and input terminal: AC2,300V, 1 minute

Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V
Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V
Between power terminal and input terminal: 20MΩ or more, DC500V

MAX.W.C 29g/m3 dry air at 101.3kPa

6VA or less (at AC100V) Inrush current 5.6A or less
8VA or less (at AC240V) Inrush current 13.3A or less

0.6A (at 98% output of rated voltage)

AC20A

0.00~2.00 (front key)
0.0~100.0% [External setting device (volume)]

Phase control/zero cross control method (Factory: Phase control)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

0~98% of load power supply voltage
(Excluding voltage drop due to fuse)

0.0~100.0% (front key)

0.0~100.0% (front key)

Approximately AC27mA rms or less
(Load voltage 200V rms 60Hz Ta=25℃)

Natural cooling

DC0~10V

None

Communication (RS-485) [RKC standard communication]
*Communication plug side connector included

-9.9~100.0% (front key)

No function

Resistive load

0.0~100.0% (front key)
0.0~100.0% [External setting device (volume)]

10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz

Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-Part Number-THV-10PZ020-5*NAC-N

THV-10PZ020-5*NAC-N

Available upon quote

50/60Hz shared (automatic detection)
Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz

Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less)

0~600 seconds (front key)

0.0~100.0% (front key)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

1 point alarm output *Input/output plug side connector is required.

5~95%RH (no condensation)

-15~+55℃ (guaranteed operation range)

Between main circuit terminal and heatsink: AC2,500V, 1 minute
Between power terminal and heatsink: AC2,500V, 1 minute
Between main circuit terminal and input terminal: AC2,500V, 1 minute
Between power terminal and input terminal: AC2,300V, 1 minute

Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V
Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V
Between power terminal and input terminal: 20MΩ or more, DC500V

MAX.W.C 29g/m3 dry air at 101.3kPa

6VA or less (at AC100V) Inrush current 5.6A or less
8VA or less (at AC240V) Inrush current 13.3A or less

0.6A (at 98% output of rated voltage)

AC20A

0.00~2.00 (front key)
0.0~100.0% [External setting device (volume)]

Phase control/zero cross control method (Factory: Phase control)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

0~98% of load power supply voltage
(Excluding voltage drop due to fuse)

0.0~100.0% (front key)

0.0~100.0% (front key)

Approximately AC27mA rms or less
(Load voltage 200V rms 60Hz Ta=25℃)

Natural cooling

DC0~10V

None

Communication (RS-485) [MODBUS communication]
*Communication plug side connector included

-9.9~100.0% (front key)

No function

Resistive load

0.0~100.0% (front key)
0.0~100.0% [External setting device (volume)]

10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz

Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-Part Number-THV-10PZ020-5*HNN-N

THV-10PZ020-5*HNN-N

Available upon quote

50/60Hz shared (automatic detection)
Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz

Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less)

0~600 seconds (front key)

0.0~100.0% (front key)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

No alarm output

5~95%RH (no condensation)

-15~+55℃ (guaranteed operation range)

Between main circuit terminal and heatsink: AC2,500V, 1 minute
Between power terminal and heatsink: AC2,500V, 1 minute
Between main circuit terminal and input terminal: AC2,500V, 1 minute
Between power terminal and input terminal: AC2,300V, 1 minute

Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V
Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V
Between power terminal and input terminal: 20MΩ or more, DC500V

MAX.W.C 29g/m3 dry air at 101.3kPa

6VA or less (at AC100V) Inrush current 5.6A or less
8VA or less (at AC240V) Inrush current 13.3A or less

0.6A (at 98% output of rated voltage)

AC20A

0.00~2.00 (front key)
0.0~100.0% [External setting device (volume)]

Phase control/zero cross control method (Factory: Phase control)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

0~98% of load power supply voltage
(Excluding voltage drop due to fuse)

0.0~100.0% (front key)

0.0~100.0% (front key)

Approximately AC27mA rms or less
(Load voltage 200V rms 60Hz Ta=25℃)

Natural cooling

DC0~10V

None

No function

-9.9~100.0% (front key)

Heater burnout alarm, current limiter function, constant current control function, transformer primary side control protection function, power proportional control included

Resistive load

0.0~100.0% (front key)
0.0~100.0% [External setting device (volume)]

10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz

Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)-Part Number-THV-10PZ020-5*HNA-N

THV-10PZ020-5*HNA-N

Available upon quote

50/60Hz shared (automatic detection)
Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz

Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less)

0~600 seconds (front key)

0.0~100.0% (front key)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

No alarm output

5~95%RH (no condensation)

-15~+55℃ (guaranteed operation range)

Between main circuit terminal and heatsink: AC2,500V, 1 minute
Between power terminal and heatsink: AC2,500V, 1 minute
Between main circuit terminal and input terminal: AC2,500V, 1 minute
Between power terminal and input terminal: AC2,300V, 1 minute

Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V
Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V
Between power terminal and input terminal: 20MΩ or more, DC500V

MAX.W.C 29g/m3 dry air at 101.3kPa

6VA or less (at AC100V) Inrush current 5.6A or less
8VA or less (at AC240V) Inrush current 13.3A or less

0.6A (at 98% output of rated voltage)

AC20A

0.00~2.00 (front key)
0.0~100.0% [External setting device (volume)]

Phase control/zero cross control method (Factory: Phase control)

AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V

0~98% of load power supply voltage
(Excluding voltage drop due to fuse)

0.0~100.0% (front key)

0.0~100.0% (front key)

Approximately AC27mA rms or less
(Load voltage 200V rms 60Hz Ta=25℃)

Natural cooling

DC0~10V

None

Transmission output [continuous voltage output DC0-10V]
*Transmission output plug side connector included

-9.9~100.0% (front key)

Heater burnout alarm, current limiter function, constant current control function, transformer primary side control protection function, power proportional control included

Resistive load

0.0~100.0% (front key)
0.0~100.0% [External setting device (volume)]

10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz

Click on the part number for more information about each product

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Thyristors Products

Other products of RKC INSTRUMENT

Reviews shown here are reviews of companies.


View more products of RKC INSTRUMENT

About Company Handling This Product

Response Rate

100.0%


Response Time

14.3hrs

Company Overview

RKC Instrument has been continually growing for over half a century and strives to be a solution provider of m...

See More

  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree