Product
Single-phase power regulator (thyristor unit SCR) THV-10 (20A, 30A, 45A, 60A, 80A, 100A)Handling Company
RKC INSTRUMENTCategories
Items marked with have different values depending on the model number.
Click on the part number for more information about each product
Product Image | Part Number | Price (excluding tax) | Absolute humidity | Alarm output | Applicable load phase control | Base up setting (output bias) | Control method | Control power supply voltage | Cooling method | Gradient setting | Heater burnout alarm, current limiter function, etc. | Input sampling period | Input signal | Input/output plug side connector included | Insulation resistance | Insulation voltage | Leakage current when output is OFF | Load power supply voltage | Manual settings | Minimum load current | Output limiter (lower limit) | Output limiter (upper limit) | Output limiter time at startup | Output voltage range | Permissible ambient humidity | Permissible ambient temperature | Power consumption | Power frequency | Rated current | Startup output limiter (upper limit) | Transmission output or communication function | Zero cross control |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
THV-10PZ020-5*NNN-N |
Available upon quote | MAX.W.C 29g/m3 dry air at 101.3kPa | No alarm output | Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less) | -9.9~100.0% (front key) | Phase control/zero cross control method (Factory: Phase control) | AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V | Natural cooling |
0.00~2.00 (front key) 0.0~100.0% [External setting device (volume)] |
No function | 10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz | DC0~10V | None |
Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V Between power terminal and input terminal: 20MΩ or more, DC500V |
Between main circuit terminal and heatsink: AC2,500V, 1 minute Between power terminal and heatsink: AC2,500V, 1 minute Between main circuit terminal and input terminal: AC2,500V, 1 minute Between power terminal and input terminal: AC2,300V, 1 minute |
Approximately AC27mA rms or less (Load voltage 200V rms 60Hz Ta=25℃) |
AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V |
0.0~100.0% (front key) 0.0~100.0% [External setting device (volume)] |
0.6A (at 98% output of rated voltage) | 0.0~100.0% (front key) | 0.0~100.0% (front key) | 0~600 seconds (front key) |
0~98% of load power supply voltage (Excluding voltage drop due to fuse) |
5~95%RH (no condensation) | -15~+55℃ (guaranteed operation range) |
6VA or less (at AC100V) Inrush current 5.6A or less 8VA or less (at AC240V) Inrush current 13.3A or less |
50/60Hz shared (automatic detection) Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz |
AC20A | 0.0~100.0% (front key) | No function | Resistive load | |
THV-10PZ020-5*NNA-N |
Available upon quote | MAX.W.C 29g/m3 dry air at 101.3kPa | No alarm output | Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less) | -9.9~100.0% (front key) | Phase control/zero cross control method (Factory: Phase control) | AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V | Natural cooling |
0.00~2.00 (front key) 0.0~100.0% [External setting device (volume)] |
No function | 10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz | DC0~10V | None |
Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V Between power terminal and input terminal: 20MΩ or more, DC500V |
Between main circuit terminal and heatsink: AC2,500V, 1 minute Between power terminal and heatsink: AC2,500V, 1 minute Between main circuit terminal and input terminal: AC2,500V, 1 minute Between power terminal and input terminal: AC2,300V, 1 minute |
Approximately AC27mA rms or less (Load voltage 200V rms 60Hz Ta=25℃) |
AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V |
0.0~100.0% (front key) 0.0~100.0% [External setting device (volume)] |
0.6A (at 98% output of rated voltage) | 0.0~100.0% (front key) | 0.0~100.0% (front key) | 0~600 seconds (front key) |
0~98% of load power supply voltage (Excluding voltage drop due to fuse) |
5~95%RH (no condensation) | -15~+55℃ (guaranteed operation range) |
6VA or less (at AC100V) Inrush current 5.6A or less 8VA or less (at AC240V) Inrush current 13.3A or less |
50/60Hz shared (automatic detection) Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz |
AC20A | 0.0~100.0% (front key) |
Transmission output [continuous voltage output DC0-10V] *Transmission output plug side connector included |
Resistive load | |
THV-10PZ020-5*NNB-N |
Available upon quote | MAX.W.C 29g/m3 dry air at 101.3kPa | No alarm output | Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less) | -9.9~100.0% (front key) | Phase control/zero cross control method (Factory: Phase control) | AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V | Natural cooling |
0.00~2.00 (front key) 0.0~100.0% [External setting device (volume)] |
No function | 10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz | DC0~10V | None |
Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V Between power terminal and input terminal: 20MΩ or more, DC500V |
Between main circuit terminal and heatsink: AC2,500V, 1 minute Between power terminal and heatsink: AC2,500V, 1 minute Between main circuit terminal and input terminal: AC2,500V, 1 minute Between power terminal and input terminal: AC2,300V, 1 minute |
Approximately AC27mA rms or less (Load voltage 200V rms 60Hz Ta=25℃) |
AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V |
0.0~100.0% (front key) 0.0~100.0% [External setting device (volume)] |
0.6A (at 98% output of rated voltage) | 0.0~100.0% (front key) | 0.0~100.0% (front key) | 0~600 seconds (front key) |
0~98% of load power supply voltage (Excluding voltage drop due to fuse) |
5~95%RH (no condensation) | -15~+55℃ (guaranteed operation range) |
6VA or less (at AC100V) Inrush current 5.6A or less 8VA or less (at AC240V) Inrush current 13.3A or less |
50/60Hz shared (automatic detection) Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz |
AC20A | 0.0~100.0% (front key) |
Communication (RS-485) [RKC standard communication] *Communication plug side connector included |
Resistive load | |
THV-10PZ020-5*NNC-N |
Available upon quote | MAX.W.C 29g/m3 dry air at 101.3kPa | No alarm output | Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less) | -9.9~100.0% (front key) | Phase control/zero cross control method (Factory: Phase control) | AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V | Natural cooling |
0.00~2.00 (front key) 0.0~100.0% [External setting device (volume)] |
No function | 10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz | DC0~10V | None |
Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V Between power terminal and input terminal: 20MΩ or more, DC500V |
Between main circuit terminal and heatsink: AC2,500V, 1 minute Between power terminal and heatsink: AC2,500V, 1 minute Between main circuit terminal and input terminal: AC2,500V, 1 minute Between power terminal and input terminal: AC2,300V, 1 minute |
Approximately AC27mA rms or less (Load voltage 200V rms 60Hz Ta=25℃) |
AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V |
0.0~100.0% (front key) 0.0~100.0% [External setting device (volume)] |
0.6A (at 98% output of rated voltage) | 0.0~100.0% (front key) | 0.0~100.0% (front key) | 0~600 seconds (front key) |
0~98% of load power supply voltage (Excluding voltage drop due to fuse) |
5~95%RH (no condensation) | -15~+55℃ (guaranteed operation range) |
6VA or less (at AC100V) Inrush current 5.6A or less 8VA or less (at AC240V) Inrush current 13.3A or less |
50/60Hz shared (automatic detection) Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz |
AC20A | 0.0~100.0% (front key) |
Communication (RS-485) [MODBUS communication] *Communication plug side connector included |
Resistive load | |
THV-10PZ020-5*NAN-N |
Available upon quote | MAX.W.C 29g/m3 dry air at 101.3kPa | 1 point alarm output *Input/output plug side connector is required. | Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less) | -9.9~100.0% (front key) | Phase control/zero cross control method (Factory: Phase control) | AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V | Natural cooling |
0.00~2.00 (front key) 0.0~100.0% [External setting device (volume)] |
No function | 10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz | DC0~10V | None |
Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V Between power terminal and input terminal: 20MΩ or more, DC500V |
Between main circuit terminal and heatsink: AC2,500V, 1 minute Between power terminal and heatsink: AC2,500V, 1 minute Between main circuit terminal and input terminal: AC2,500V, 1 minute Between power terminal and input terminal: AC2,300V, 1 minute |
Approximately AC27mA rms or less (Load voltage 200V rms 60Hz Ta=25℃) |
AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V |
0.0~100.0% (front key) 0.0~100.0% [External setting device (volume)] |
0.6A (at 98% output of rated voltage) | 0.0~100.0% (front key) | 0.0~100.0% (front key) | 0~600 seconds (front key) |
0~98% of load power supply voltage (Excluding voltage drop due to fuse) |
5~95%RH (no condensation) | -15~+55℃ (guaranteed operation range) |
6VA or less (at AC100V) Inrush current 5.6A or less 8VA or less (at AC240V) Inrush current 13.3A or less |
50/60Hz shared (automatic detection) Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz |
AC20A | 0.0~100.0% (front key) | No function | Resistive load | |
THV-10PZ020-5*NAA-N |
Available upon quote | MAX.W.C 29g/m3 dry air at 101.3kPa | 1 point alarm output *Input/output plug side connector is required. | Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less) | -9.9~100.0% (front key) | Phase control/zero cross control method (Factory: Phase control) | AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V | Natural cooling |
0.00~2.00 (front key) 0.0~100.0% [External setting device (volume)] |
No function | 10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz | DC0~10V | None |
Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V Between power terminal and input terminal: 20MΩ or more, DC500V |
Between main circuit terminal and heatsink: AC2,500V, 1 minute Between power terminal and heatsink: AC2,500V, 1 minute Between main circuit terminal and input terminal: AC2,500V, 1 minute Between power terminal and input terminal: AC2,300V, 1 minute |
Approximately AC27mA rms or less (Load voltage 200V rms 60Hz Ta=25℃) |
AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V |
0.0~100.0% (front key) 0.0~100.0% [External setting device (volume)] |
0.6A (at 98% output of rated voltage) | 0.0~100.0% (front key) | 0.0~100.0% (front key) | 0~600 seconds (front key) |
0~98% of load power supply voltage (Excluding voltage drop due to fuse) |
5~95%RH (no condensation) | -15~+55℃ (guaranteed operation range) |
6VA or less (at AC100V) Inrush current 5.6A or less 8VA or less (at AC240V) Inrush current 13.3A or less |
50/60Hz shared (automatic detection) Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz |
AC20A | 0.0~100.0% (front key) |
Transmission output [continuous voltage output DC0-10V] *Transmission output plug side connector included |
Resistive load | |
THV-10PZ020-5*NAB-N |
Available upon quote | MAX.W.C 29g/m3 dry air at 101.3kPa | 1 point alarm output *Input/output plug side connector is required. | Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less) | -9.9~100.0% (front key) | Phase control/zero cross control method (Factory: Phase control) | AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V | Natural cooling |
0.00~2.00 (front key) 0.0~100.0% [External setting device (volume)] |
No function | 10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz | DC0~10V | None |
Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V Between power terminal and input terminal: 20MΩ or more, DC500V |
Between main circuit terminal and heatsink: AC2,500V, 1 minute Between power terminal and heatsink: AC2,500V, 1 minute Between main circuit terminal and input terminal: AC2,500V, 1 minute Between power terminal and input terminal: AC2,300V, 1 minute |
Approximately AC27mA rms or less (Load voltage 200V rms 60Hz Ta=25℃) |
AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V |
0.0~100.0% (front key) 0.0~100.0% [External setting device (volume)] |
0.6A (at 98% output of rated voltage) | 0.0~100.0% (front key) | 0.0~100.0% (front key) | 0~600 seconds (front key) |
0~98% of load power supply voltage (Excluding voltage drop due to fuse) |
5~95%RH (no condensation) | -15~+55℃ (guaranteed operation range) |
6VA or less (at AC100V) Inrush current 5.6A or less 8VA or less (at AC240V) Inrush current 13.3A or less |
50/60Hz shared (automatic detection) Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz |
AC20A | 0.0~100.0% (front key) |
Communication (RS-485) [RKC standard communication] *Communication plug side connector included |
Resistive load | |
THV-10PZ020-5*NAC-N |
Available upon quote | MAX.W.C 29g/m3 dry air at 101.3kPa | 1 point alarm output *Input/output plug side connector is required. | Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less) | -9.9~100.0% (front key) | Phase control/zero cross control method (Factory: Phase control) | AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V | Natural cooling |
0.00~2.00 (front key) 0.0~100.0% [External setting device (volume)] |
No function | 10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz | DC0~10V | None |
Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V Between power terminal and input terminal: 20MΩ or more, DC500V |
Between main circuit terminal and heatsink: AC2,500V, 1 minute Between power terminal and heatsink: AC2,500V, 1 minute Between main circuit terminal and input terminal: AC2,500V, 1 minute Between power terminal and input terminal: AC2,300V, 1 minute |
Approximately AC27mA rms or less (Load voltage 200V rms 60Hz Ta=25℃) |
AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V |
0.0~100.0% (front key) 0.0~100.0% [External setting device (volume)] |
0.6A (at 98% output of rated voltage) | 0.0~100.0% (front key) | 0.0~100.0% (front key) | 0~600 seconds (front key) |
0~98% of load power supply voltage (Excluding voltage drop due to fuse) |
5~95%RH (no condensation) | -15~+55℃ (guaranteed operation range) |
6VA or less (at AC100V) Inrush current 5.6A or less 8VA or less (at AC240V) Inrush current 13.3A or less |
50/60Hz shared (automatic detection) Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz |
AC20A | 0.0~100.0% (front key) |
Communication (RS-485) [MODBUS communication] *Communication plug side connector included |
Resistive load | |
THV-10PZ020-5*HNN-N |
Available upon quote | MAX.W.C 29g/m3 dry air at 101.3kPa | No alarm output | Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less) | -9.9~100.0% (front key) | Phase control/zero cross control method (Factory: Phase control) | AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V | Natural cooling |
0.00~2.00 (front key) 0.0~100.0% [External setting device (volume)] |
Heater burnout alarm, current limiter function, constant current control function, transformer primary side control protection function, power proportional control included | 10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz | DC0~10V | None |
Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V Between power terminal and input terminal: 20MΩ or more, DC500V |
Between main circuit terminal and heatsink: AC2,500V, 1 minute Between power terminal and heatsink: AC2,500V, 1 minute Between main circuit terminal and input terminal: AC2,500V, 1 minute Between power terminal and input terminal: AC2,300V, 1 minute |
Approximately AC27mA rms or less (Load voltage 200V rms 60Hz Ta=25℃) |
AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V |
0.0~100.0% (front key) 0.0~100.0% [External setting device (volume)] |
0.6A (at 98% output of rated voltage) | 0.0~100.0% (front key) | 0.0~100.0% (front key) | 0~600 seconds (front key) |
0~98% of load power supply voltage (Excluding voltage drop due to fuse) |
5~95%RH (no condensation) | -15~+55℃ (guaranteed operation range) |
6VA or less (at AC100V) Inrush current 5.6A or less 8VA or less (at AC240V) Inrush current 13.3A or less |
50/60Hz shared (automatic detection) Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz |
AC20A | 0.0~100.0% (front key) | No function | Resistive load | |
THV-10PZ020-5*HNA-N |
Available upon quote | MAX.W.C 29g/m3 dry air at 101.3kPa | No alarm output | Resistive load, transformer primary side control (magnetic flux density approximately 1.25T or less) | -9.9~100.0% (front key) | Phase control/zero cross control method (Factory: Phase control) | AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V | Natural cooling |
0.00~2.00 (front key) 0.0~100.0% [External setting device (volume)] |
Heater burnout alarm, current limiter function, constant current control function, transformer primary side control protection function, power proportional control included | 10ms when power frequency is 50Hz, 8.33ms when power frequency is 60Hz | DC0~10V | None |
Between main circuit terminal, power supply terminal and heatsink: 20MΩ or more, DC500V Between main circuit terminal, heatsink and input terminal: 20MΩ or more, DC500V Between power terminal and input terminal: 20MΩ or more, DC500V |
Between main circuit terminal and heatsink: AC2,500V, 1 minute Between power terminal and heatsink: AC2,500V, 1 minute Between main circuit terminal and input terminal: AC2,500V, 1 minute Between power terminal and input terminal: AC2,300V, 1 minute |
Approximately AC27mA rms or less (Load voltage 200V rms 60Hz Ta=25℃) |
AC85~264V (including power supply voltage fluctuation) Rating: AC100~240V |
0.0~100.0% (front key) 0.0~100.0% [External setting device (volume)] |
0.6A (at 98% output of rated voltage) | 0.0~100.0% (front key) | 0.0~100.0% (front key) | 0~600 seconds (front key) |
0~98% of load power supply voltage (Excluding voltage drop due to fuse) |
5~95%RH (no condensation) | -15~+55℃ (guaranteed operation range) |
6VA or less (at AC100V) Inrush current 5.6A or less 8VA or less (at AC240V) Inrush current 13.3A or less |
50/60Hz shared (automatic detection) Frequency fluctuation: Load power supply voltage 50Hz±1Hz, 60Hz±1.2Hz, control power supply voltage 50Hz±2Hz, 60Hz±2Hz |
AC20A | 0.0~100.0% (front key) |
Transmission output [continuous voltage output DC0-10V] *Transmission output plug side connector included |
Resistive load |
Click on the part number for more information about each product