CO2 transmitter for freezers/frozen warehouses TKR100BZ/TKR100LBZ-TKR100BZ
CO2 transmitter for freezers/frozen warehouses TKR100BZ/TKR100LBZ-TKR100LBZ
CO2 transmitter for freezers/frozen warehouses TKR100BZ/TKR100LBZ-Hosansho Co., Ltd.

CO2 transmitter for freezers/frozen warehouses TKR100BZ/TKR100LBZ
Hosansho Co., Ltd.


About This Product

■Measurement principle/product overview There are methods to detect CO2 concentration in the atmosphere, such as NDIR, solid electrolyte sensor, and photoacoustic spectroscopy (PAS), but generally an analyzer called NDIR (Non Dispersive Infrared Gas Anaryzer) is used. In the case of CO2 molecules, it has the property of selectively absorbing infrared rays with a wavelength of 4.26 microns. When CO2 molecules are present in high concentrations, they will be absorbed more strongly. NDIR takes advantage of this property. When the gas to be measured is passed through a tube (cell) with an infrared light source and an optical sensor element fixed at both ends, at low concentrations the attenuation of the incident light is small, and at high concentrations the attenuation increases. ■Product overview ・CO2 transmitter TKR100BZ is a device that detects the carbon dioxide concentration in a cold storage warehouse and converts it to analog output. ・The measurement range is 0 to 10,000ppm (BZ/LBZ), 0 to 50,000ppm (BZ05/LBZ05), and the corresponding output DC4 to 20mA/0 to 10V is output. (range switchable) ・The operating temperature range is -40 to 40℃. (No condensation allowed) ・Equipped with automatic calibration/manual calibration function ・The board surface is treated to resist condensation. (Not waterproof) ・A dustproof filter is attached to the slit part. ・TKR100LBZ/LBZ05 displays the current CO2 concentration on the small LCD. ■Features ・Can be used in ultra-low temperature environments of -40℃. (Operating temperature range: -40 to 40℃) ・Measurement range is 0 to 10,000ppm (BZ/LBZ), 0 to 50,000ppm (BZ05/LBZ05) - Equipped with an automatic calibration function that can automatically correct discrepancies due to aging. - Analog output can be selected as current output or voltage output. ・TKR100BZ/BZ05 is a low-cost popular model without an LCD display. -A dustproof filter is attached to the slit part of the case to prevent dust from entering.

  • Product

    CO2 transmitter for freezers/frozen warehouses TKR100BZ/TKR100LBZ

Share this product


110+ people viewing


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

4 Models of CO2 transmitter for freezers/frozen warehouses TKR100BZ/TKR100LBZ

Items marked with have different values depending on the model number.

Click on the part number for more information about each product

Product Image Part Number Price (excluding tax) Analog output Display unit External dimensions Measurement accuracy Measurement method Measurement period Measuring range Operating environment Output range Output resolution Power consumption Power supply Proofreading Response time (90%) Storage temperature Weight
CO2 transmitter for freezers/frozen warehouses TKR100BZ/TKR100LBZ-Part Number-TKR100BZ

TKR100BZ

Available upon quote DC4mA~20mA/DC0mA~20mA/DC2V~10V/DC0V~10V - 123×70×43mm ±5% of reading ±50ppm (-40~0℃), ±5% of reading ±150ppm (0~40℃) NDIR method 2 seconds 0~10,000ppm -40℃~40℃/0%RH~95%RH, no condensation 0~2,000/0~3,000/0~5,000/10,000ppm 8bit 8VA or less DC24V/AC24V ±20% Automatic calibration (every 7 days) /Manual calibration (recalibration for 10 minutes) 70 seconds -40℃~70℃ Approximately 105g
CO2 transmitter for freezers/frozen warehouses TKR100BZ/TKR100LBZ-Part Number-TKR100BZ05

TKR100BZ05

Available upon quote DC4mA~20mA/DC0mA~20mA/DC2V~10V/DC0V~10V - 123×70×43mm ±5% of reading value ±50ppm (-40~0℃), ±5% of reading value ±150ppm (0~40℃), ±10%FS for 10,000ppm or more NDIR method 2 seconds 0~50,000ppm -40℃~40℃/0%RH~95%RH, no condensation 0~10,000/0~20,000/0~30,000/0~50,000ppm 8bit 8VA or less DC24V/AC24V ±20% Automatic calibration (every 7 days) /Manual calibration (recalibration for 10 minutes) 70 seconds -40℃~70℃ Approximately 105g
CO2 transmitter for freezers/frozen warehouses TKR100BZ/TKR100LBZ-Part Number-TKR100LBZ

TKR100LBZ

Available upon quote DC4mA~20mA/DC0mA~20mA/DC2V~10V/DC0V~10V Ppm 123×70×43mm ±5% of reading ±50ppm (-40~0℃), ±5% of reading ±150ppm (0~40℃) NDIR method 2 seconds 0~10,000ppm -40℃~40℃/0%RH~95%RH, no condensation 0~2,000/0~3,000/0~5,000/10,000ppm 8bit 8VA or less DC24V/AC24V ±20% Automatic calibration (every 7 days) /Manual calibration (recalibration for 10 minutes) 70 seconds -40℃~70℃ Approximately 105g
CO2 transmitter for freezers/frozen warehouses TKR100BZ/TKR100LBZ-Part Number-TKR100LBZ05

TKR100LBZ05

Available upon quote DC4mA~20mA/DC0mA~20mA/DC2V~10V/DC0V~10V Ppm 123×70×43mm ±5% of reading value ±50ppm (-40~0℃), ±5% of reading value ±150ppm (0~40℃), ±10%FS for 10,000ppm or more NDIR method 2 seconds 0~50,000ppm -40℃~40℃/0%RH~95%RH, no condensation 0~10,000/0~20,000/0~30,000/0~50,000ppm 8bit 8VA or less DC24V/AC24V ±20% Automatic calibration (every 7 days) /Manual calibration (recalibration for 10 minutes) 70 seconds -40℃~70℃ Approximately 105g

Click on the part number for more information about each product

Customers who viewed this product also viewed

Other products of Hosansho Co., Ltd.


View more products of Hosansho Co., Ltd.

About Company Handling This Product

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree