All Categories
History
Response Rate
100.0%
Response Time
18.6hours
Relatively Fast Response
Product
CO2 transmitter TKR100 seriesHandling Company
Hosansho Co., Ltd.Categories
Click on the part number for more information about each product
Image | Part Number | Price (excluding tax) | Power supply | Weight | Display unit | Measurement accuracy | Measuring range | Measurement method | Measurement period | Power consumption | Proofreading | Response time (90%) | External dimensions | Operating environment | Output range | Storage temperature | Analog output | Relay output |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
TKR100L |
Available upon quote |
DC24V/AC24V ±20% |
Approximately 105g |
Ppm |
±5% of reading ±30ppm (±3% of reading ±30ppm in automatic calibration mode) ±10%FS for 10,000ppm or more |
0~10,000ppm |
NDIR method |
3 seconds |
8VA or less |
Automatic calibration (every 7 days) /Manual calibration (recalibration for 10 minutes) |
150 seconds |
123×70×43mm |
-10℃~60℃/0%RH~95%RH, no condensation |
0~2,000/0~3,000/0~5,000/10,000ppm |
-30℃~70℃ |
DC4mA~20mA/DC0mA~20mA/DC2V~10V/DC0V~10V |
- | |
TKR100LR |
Available upon quote |
DC24V/AC24V ±20% |
Approximately 105g |
Ppm |
±5% of reading ±30ppm (±3% of reading ±30ppm in automatic calibration mode) ±10%FS for 10,000ppm or more |
0~10,000ppm |
NDIR method |
3 seconds |
8VA or less |
Automatic calibration (every 7 days) /Manual calibration (recalibration for 10 minutes) |
150 seconds |
123×70×43mm |
-10℃~60℃/0%RH~95%RH, no condensation |
0~2,000/0~3,000/0~5,000/10,000ppm |
-30℃~70℃ |
DC4mA~20mA/DC0mA~20mA/DC2V~10V/DC0V~10V |
1 point, contact capacity 1A/AC125V, "open" when OFF |
|
TKR100LR05 |
Available upon quote |
DC24V/AC24V ±20% |
Approximately 105g |
Ppm |
±5% of reading ±30ppm (±3% of reading ±30ppm in automatic calibration mode) ±10%FS for 10,000ppm or more |
0~50,000ppm |
NDIR method |
3 seconds |
8VA or less |
Automatic calibration (every 7 days) /Manual calibration (recalibration for 10 minutes) |
150 seconds |
123×70×43mm |
-10℃~60℃/0%RH~95%RH, no condensation |
0~10,000/0~20,000/0~30,000/0~50,000ppm (TKR100LR05) |
-30℃~70℃ |
DC4mA~20mA/DC0mA~20mA/DC2V~10V/DC0V~10V |
1 point, contact capacity 1A/AC125V, "open" when OFF |
|
TKR100 |
Available upon quote |
DC24V/AC24V ±20% |
Approximately 105g |
Ppm |
±5% of reading ±30ppm (±3% of reading ±30ppm in automatic calibration mode) ±10%FS for 10,000ppm or more |
0~10,000ppm |
NDIR method |
3 seconds |
8VA or less |
Automatic calibration (every 7 days) /Manual calibration (recalibration for 10 minutes) |
150 seconds |
123×70×43mm |
-10℃~60℃/0%RH~95%RH, no condensation |
0~2,000/0~3,000/0~5,000/10,000ppm |
-30℃~70℃ |
DC4mA~20mA/DC0mA~20mA/DC2V~10V/DC0V~10V |
- |
Click on the part number for more information about each product
Reviews shown here are reviews of companies.
Reviews shown here are reviews of companies.
Response Rate
100.0%
Response Time
18.6hrs