All Categories
History
Product
Adopts a closed-type large-capacity hot water circulation system Commercial use EcoCute heat pump (rated 30kW) Cold region specificationHandling Company
Showa Iron Works Co., Ltd.Categories
Image | Part Number | Price (excluding tax) | System configuration System remote control | System configuration Heat pump unit | System configuration Hot water storage unit | Heat pump unit breaker capacity (A) | Heat pump unit intermediate period (kW) | Heat pump unit winter (kW) | Heat pump unit refrigerant | Heat pump unit summer (kW) | Heat pump unit external dimensions (mm) | Heat pump unit Cold region winter (kW) | Heat pump unit Annual heating efficiency in cold regions | Heat pump unit annual heating efficiency | Heat pump unit maximum current (A) | Heat pump unit frosting period (kW) | Heat pump unit mass (kg) | Heat pump unit power supply (V) | Heat pump unit hot water storage heating capacity/hot water storage heating power consumption | Hot water storage unit cabinet material | Hot water storage unit breaker capacity (A) | Hot water storage unit external dimensions (mm) | Hot water storage unit water side maximum working pressure (kPa) | Hot water storage unit Hot water storage unit capacity (L) | Hot water storage unit hot water tank specifications | Hot water storage unit mass | Hot water storage unit mass Standard specifications (when full) (kg) | Hot water storage unit Piping diameter Heat pump unit connection | Hot water storage unit Piping diameter Drainage connection port | Hot water storage unit Piping diameter Water supply/hot water connection | Hot water storage unit Piping diameter Hot water return port | Hot water storage unit power supply (V) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
![]() |
EWTH-3043J (T) |
Available upon quote |
SRC-Q1 ×1 unit |
SJHP-301K ×1 unit |
EWTH-43J (T) |
50 |
30.0/6.98 (30.0/9.80) |
30.0/7.44 (30.0/9.76) |
CO2 (R744) |
30.0/6.48 (30.0/10.6) |
1,690 × 1,350 × 720+35 (piping connection port) / unit |
30.0/10.7 (30.0/11.0) |
3.4 (Applicable only to cold region specifications) |
4.0 (cold region specifications only) |
42 |
30.0/10.7 (30.0/11.5) |
375 |
Three phase 200 (50/60Hz) |
Standard (high temperature) |
Galvalume (Al-Zn alloy plating) steel plate |
5 |
2,480×1,950×2,655 |
490 (Reducing valve setting pressure is 450) |
4,000 |
Material: SUS444, plate thickness: t=4mm, 1 tank sealed type, insulation material: GW24K 50mm |
Economy specification (full) (kg): 1,320 (5,320) |
1,510 (5,810) |
Rc3/4 (20A) (connected via connection header) |
40A (JIS10K) |
40A (JIS10K) |
20A (JIS10K) |
Single phase 200 (50/60Hz) |