Circuit valve, primary pressure regulating valve Differential pressure regulating valve (for water/hot water) FD-2H type-FD-2H-B (nominal diameter 15)
Circuit valve, primary pressure regulating valve Differential pressure regulating valve (for water/hot water) FD-2H type-Ben Co., Ltd.

Circuit valve, primary pressure regulating valve Differential pressure regulating valve (for water/hot water) FD-2H type
Ben Co., Ltd.


About This Product

Used as a relief valve for pumps in closed circuits of air conditioning and heating/cooling equipment in high-rise buildings. In the case of an open circuit system, a primary pressure regulating valve is used as the relief valve of the pump, but in the case of a closed circuit system, a differential pressure regulating valve is used because the pump must be operated at a constant flow rate regardless of the load.

■Place of use

・Air conditioning equipment ・Heating and cooling equipment

■Main features

・Used as a pump relief valve in a closed circuit. - An NBR disc is used for the valve body.

  • Product

    Circuit valve, primary pressure regulating valve Differential pressure regulating valve (for water/hot water) FD-2H type

Share this product


30+ people viewing


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

1 Models of Circuit valve, primary pressure regulating valve Differential pressure regulating valve (for water/hot water) FD-2H type

Image Part Number Price (excluding tax) Valve type Mounting position Nominal diameter Painting (inside) Painting (exterior) Material (diaphragm disc) Material (main body) Material (main parts) Fluid temperature End connection Setting pressure adjustment range Applicable fluid
Circuit valve, primary pressure regulating valve Differential pressure regulating valve (for water/hot water) FD-2H type-Part Number-FD-2H-B (nominal diameter 15)

FD-2H-B (nominal diameter 15)

$ 1,306.50〜

Differential pressure regulating valve

Upright installation on horizontal piping

15~150 (1/2~6)

Rust prevention oil

Metallic blue, cap: red

NBR

F.C.

CAC406, SUS

5~90℃

JIS 10K RF flange

・Nominal diameter 80 or less L: 0.05~0.35MPa, H: 0.3~0.7MPa
・Nominal diameter 100 or more L: 0.05~0.35MPa, H: 0.3~0.5MPa

Hot water

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Pressure Regulators Products

Other products of Ben Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Ben Co., Ltd.

About Company Handling This Product

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2025 Metoree