All Categories

History

Circuit valve, primary pressure regulating valve Water fall prevention valve (for water/hot water) WVMS-02 type-WVMS-02-B (nominal diameter 80)
Circuit valve, primary pressure regulating valve Water fall prevention valve (for water/hot water) WVMS-02 type-Ben Co., Ltd.

Circuit valve, primary pressure regulating valve Water fall prevention valve (for water/hot water) WVMS-02 type
Ben Co., Ltd.


About This Product

It is installed in the return pipe of an open circuit in air conditioning equipment that uses cold and hot water as a heat source, and the valve closes immediately when the pump stops, preventing water from falling into the return pipe. During operation, the valve opening is adjusted according to the flow rate, and the pressure in the outbound and return pipes is maintained at an appropriate level, providing stable pressure conditions to the air conditioner.

■Place of use

・Air conditioning equipment ・Heating and cooling equipment

■Main features

- Stable operation can be easily achieved by adjusting the sensitivity by adjusting the needle valve opening according to the usage conditions. ・It has good responsiveness to pressure changes, and the valve closes quickly when the pump is stopped. - The basic valve part and pilot valve part can be easily disassembled, making maintenance such as adjustment, repair, and parts replacement easy. - Excess flow rate can be limited by the lift limit mechanism.

  • Product

    Circuit valve, primary pressure regulating valve Water fall prevention valve (for water/hot water) WVMS-02 type

Share this product


20+ people viewing


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

1 Models of Circuit valve, primary pressure regulating valve Water fall prevention valve (for water/hot water) WVMS-02 type

Image Part Number Price (excluding tax) Accumulation Valve type Primary side applicable pressure Mounting position Downflow pressure Nominal diameter Basic valve painting (inner surface) Material (diaphragm disc) Material (valve seat) Material (main body) Fluid temperature End connection Pressure test (water pressure) Setting pressure adjustment range Applicable fluid
Circuit valve, primary pressure regulating valve Water fall prevention valve (for water/hot water) WVMS-02 type-Part Number-WVMS-02-B (nominal diameter 80)

WVMS-02-B (nominal diameter 80)

$ 5,460.00〜

Within set pressure x 10% (minimum value 0.03MPa)

Water fall prevention valve

1.0MPa or less

Upright installation on horizontal piping

・Set pressure adjustment range (L) 0.05~0.35MPa: Within set pressure x 20% (minimum value 0.03MPa)
・Set pressure adjustment range (H) 0.3~0.7MPa: Within set pressure x 15%

80~200 (3~8)

Liquid epoxy resin for water supply

NBR

CAC406

F.C.

5~60℃

JIS 10K RF flange

1.5MPa at water pressure

L:0.05~0.35MPa, H:0.3~0.7MPa

·water
・Hot water

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Pressure Regulators Products

Other products of Ben Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Ben Co., Ltd.

About Company Handling This Product

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2025 Metoree