Product
Earth Leakage Measurement Instrument / Logger I0R (I Zero R) Logger I0R700VHandling Company
Sanwa Electric Meter Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | AC voltage (ACV) accuracy | AC voltage (ACV) measurement range | Battery life | Dimensions/mass | External output | I0R mode Io accuracy | I0R mode Io measurement range | I0R mode Ior accuracy | I0R mode Ior measurement range | I0R mode MΩ accuracy | I0R mode MΩ measurement range | Input signal | Measurement circuit | Measurement mode | Motor mode Io accuracy | Motor mode Io measurement range | Motor mode Ior accuracy | Motor mode Ior measurement range | Motor mode MΩ accuracy | Motor mode MΩ measurement range | Power supply | Sample rate |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
I0R700V |
Available upon quote | ± (1%+3) (When using CT sensor Φ40mm) | 0.0V~600.0V | Continuous approximately 20 hours (alkaline battery) | H102×W179×D48mm/approx. 584g | SD card, USB, alarm output | ± (1%+40) (When using CT sensor Φ40mm) | 0.000mA~999.999mA | ± (1%+40+Io*0.005) (When using CT sensor Φ40mm) | 0.000mA~999.999mA | Not specified (calculated value) (when using CT sensor Φ40mm) | 0.00MΩ~99.99MΩ |
Current: CT sensor (Φ40mm/Φ68mm/Φ110mm) Voltage: R, S, T, E or U, V, W, E (4 inputs) |
Single phase, three phase delta connection, three phase star connection (Grounding circuit and inverter only support three-phase power supply) |
I0R mode, motor mode | ± (1%+40) (When using CT sensor Φ40mm) | 0.000mA~99.999mA | ± (1%+40+Io*0.005) (When using CT sensor Φ40mm) | 0.000mA~99.999mA | Not specified (calculated value) (when using CT sensor Φ40mm) | 0.00MΩ~99.99MΩ | 6 AA alkaline batteries (LR6), dedicated AC adapter (AD-I0R700) | Numerical part 1 time/sec |