Product
Analog insulation resistance meter (Megger) [3 ranges] PDM5219SHandling Company
Sanwa Electric Meter Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | AC rectification method | AC voltage (ACV) | AC voltage (ACV) tolerance | Battery consumption display | Dimensions/mass | Direct current voltage (DCV) | Direct current voltage (DCV) tolerance | EMC directive, RoHS directive | IP rating | Maximum power consumption | Measurable number of times | Meter specifications | Operating environment conditions | Operating temperature/humidity | Power supply | Rated current | Rated measurement voltage | Safety standards | Scale (MΩ) | Scale (MΩ) Tolerance | Storage temperature/humidity |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Analog insulation resistance meter PDM5219S |
Available upon quote | Half-wave rectification method (average value indication effective value conversion) | 600V | Within ±5% of maximum scale value (Sine wave AC: 50~60Hz) | Battery Check Check with range | H144×W99×D43 mm/approx. 310 g (body) | 60V | Within ±5% of maximum scale value | IEC61326 (EMC), EN50581 (RoHS) | IP20 (with measurement probe attached) | Approximately 2.6W | 500 times (5 seconds ON / 25 seconds OFF) | Internal magnet type tote band method, 48μA | Altitude below 2,000m/Environmental pollution level II | 80%RH or less at 0℃~43℃ | 6LF22 / 6LR61 (9V alkaline battery) 9V x 1 | 1.0~1.2mA | 125V/250V/500V | IEC61010 CAT.Ⅲ600V |
0.02~0.1~50~100MΩ 500V/250V/125V |
Within ±5% of indicated value (first effective measurement range: 0.1~50MΩ) Within ±10% of indicated value (Second effective measurement range: 0.02M~0.1MΩ, or 50MΩ~100MΩ) |
-10℃~50℃, 70%RH or less, no condensation |