Top Runner Molded Transformer TOP ECOⅡ Series T2ME-50K-CHandling Company
Fuji Electrode Industry Co., Ltd.Categories
Image | Part Number | Price (excluding tax) | Load loss Wc (W) | Installation location | Heat resistance class | Insulation strength Lightning impulse test voltage | Insulation strength Winding voltage | Insulation strength AC test voltage | Short impedance (%) | Number of phases | No-load loss Wi (W) | Temperature rise limit (K) | Elevation | Circuit voltage waveform | Frequency (Hz) | Ambient temperature | Voltage balance in three-phase circuits | Energy consumption efficiency (W) standard value | Energy consumption efficiency (W) typical value |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
T2ME-50K-C |
Available upon quote |
622 |
Indoor |
F |
60kV |
6kV class, 400V class, 200V class |
22kV, 4kV, 2kV |
3.3 |
Single phase |
131 |
95 |
Less than 1,000m |
The voltage waveform of the circuit to which the transformer is connected must be approximately a sine wave. |
50 or 63 |
-5~40℃ Daily average temperature: less than 35℃, annual average temperature: less than 20℃ |
The voltages of the three-phase circuit to which the three-phase transformer is connected are approximately balanced. |
236 |
231 |