All Categories

History

Top Runner Oil-immersed Transformer TOP ECOⅡ Series T2SP-75K-W-T2SP-75K-W
Top Runner Oil-immersed Transformer TOP ECOⅡ Series T2SP-75K-W-Fuji Electrode Industry Co., Ltd.

Top Runner Oil-immersed Transformer TOP ECOⅡ Series T2SP-75K-W
Fuji Electrode Industry Co., Ltd.

Fuji Electrode Industry Co., Ltd.'s Response Status

Response Rate

100.0%

Response Time

6.9hours

Fast Response


About This Product

We will build a next-generation energy society rich in creativity through reliable energy control technology. Features

■Further improvement in energy saving performance

The iron core is made entirely of high-grade silicon steel, a low-loss magnetic material, and the coil conductor has an increased conductor cross-sectional area, which further reduces no-load loss and load loss compared to conventional low-loss transformers. has been realized.

■Strengthening seismic performance

In order to prevent ground faults and short circuits at the transformer terminals in the event of an earthquake, we are equipped with a displacement suppression seat that suppresses the amount of relative displacement between the transformer body and the panel housing. In addition, the seismic performance can be further strengthened with an optional seismic attenuation device. (Displacement suppression seat is standard equipment for 75 to 1,000kVA.)

■Compact design

By using superior materials and manufacturing methods, we have achieved high efficiency with the same installation space as the TOP ECO series.

■Low noise

High-grade iron core material is used to reduce the noise level of the transformer.

■What is the top runner method?

The Top Runner method is a method for establishing energy conservation standards under the "Act on the Rational Use of Energy (Energy Saving Law)," and it evaluates the energy consumption efficiency of specific equipment designated by the Energy Saving Law as the best among currently commercialized products. The idea is to exceed the performance of the product currently in use. The first evaluation standard for oil-immersed transformers was started in 2006 and has been in operation, but the second evaluation standard began in April 2014 as "Top Runner Transformer 2014.

  • Product

    Top Runner Oil-immersed Transformer TOP ECOⅡ Series T2SP-75K-W

Share this product


50+ people viewing

Last viewed: 23 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

1 Models of Top Runner Oil-immersed Transformer TOP ECOⅡ Series T2SP-75K-W

Image Part Number Price (excluding tax) Installation location Heat resistance class Total mass (kg) Insulation strength Lightning impulse withstand voltage Insulation strength Winding voltage Insulation strength Pressure withstand voltage Temperature rise limit (K) Oil Temperature rise limit (K) Winding Oil amount (L) Elevation Standard painted product Capacity (kVA) Circuit voltage waveform Frequency (Hz) Ambient temperature Voltage balance in three-phase circuits
Top Runner Oil-immersed Transformer TOP ECOⅡ Series T2SP-75K-W-Part Number-T2SP-75K-W

T2SP-75K-W

Available upon quote

Indoor and outdoor

A

370

60kV

6kV class, 400V class, 200V class

22kV, 4kV, 2kV

60

65

79

Less than 1,000m

Munsell symbol N5.5 Full gloss

75

The voltage waveform of the circuit to which the transformer is connected must be approximately a sine wave.

50

-20~40℃ Daily average temperature: less than 35℃, annual average temperature: less than 20℃

The voltages of the three-phase circuit to which the three-phase transformer is connected are approximately balanced.

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More High Voltage Transformers Products

Other products of Fuji Electrode Industry Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Fuji Electrode Industry Co., Ltd.

About Company Handling This Product

Response Rate

100.0%


Response Time

6.9hrs


Company Review

5.0
  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree