Circulation water volume L/min
Cold water entrance temperature when cooling ° C
Cooling ability KW
External dimensions D mm
External dimensions H mm
External dimensions W mm
Heat exchanger
Heat exchanger loss head M
Inverter variable frequency Hz
Name output kw
Piping connection diameter
Refrigerant
power supply
At the time of heating when heated water in the entrance ° C
Humidification capacity (Cooling humidification unit) KW
Part Number
MR-1800HV-TR/MR-1800CV-TRProduct
High corrosion and vibration -resistant seawater inverter cooling heating unit (heat pump chiller)Handling Company
Poec Co., Ltd.Categories
Image | Price (excluding tax) | At the time of heating when heated water in the entrance ° C () | Circulation water volume L/min () | Cold water entrance temperature when cooling ° C () | Cooling ability KW () | External dimensions D mm () | External dimensions H mm () | External dimensions W mm () | Heat exchanger () | Heat exchanger loss head M () | Humidification capacity (Cooling humidification unit) KW () | Inverter variable frequency Hz () | Name output kw () | Piping connection diameter () | Refrigerant () | power supply () |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
![]() |
Available upon quote | 7 ~ 30 | 240 | 5 to 25 | 50.4 (80Hz) | 1.19 | 2,200 | 2,283 | Double tube with grooves (outer pipe: grooved copper pipe, inner tube: titanium tube) | 5.7 | 55.4 (80Hz) | 30 ~ 80 | 4.5 × 2 | 65A (flange) | R410A | 3ø 200V 50/60Hz |