Emergency gas engine generator Gas Denkun SGS-125K-SGS-125K
Emergency gas engine generator Gas Denkun SGS-125K-Shoei Co., Ltd.

Emergency gas engine generator Gas Denkun SGS-125K
Shoei Co., Ltd.

Shoei Co., Ltd.'s Response Status

Response Rate

100.0%

Response Time

16.4hours

Relatively Fast Response


About This Product

Features of Shoei's emergency gas engine power generation device "Gasden-kun"

■ Generator that protects 24 hours a day, 365 days a year

In automatic operation mode, the engine starts 5 seconds after a power outage is detected and starts supplying power in about 25 seconds. After the power is restored, the engine automatically stops and switches to commercial power, so generator fuel is not wasted.

■Works hard even during long power outages

Operates continuously for 72 hours (3 days) in case of emergency. (You need to have enough fuel for 3 days.)

■Self-diagnosis with automatic test run

It has a built-in automatic test run function, which starts the engine regularly (weekly/monthly) and notifies you with a buzzer and lamp inside the generator in the event of an abnormality, allowing you to take precautions in advance to ensure you are fully prepared in the event of an emergency.

■Do not worry about the installation location

The small SGS-4000BT (5kW model) is about the size of a tatami mat and can be installed in general homes and small offices where space is limited. In addition, it weighs less than 300 kg, so it can be installed on a rooftop depending on the conditions.

■Pollution Control Basic Law

It has environmental performance that easily clears the emission standards set by the Ministry of the Environment's Air Pollution Control Law, and as it does not fall under the category of ``facilities that generate soot and smoke,'' it has been introduced in areas with ordinances.

■From small machines to cubicle type

All models meet the standards for cubicle-type substation equipment for generators of 10 kW or more based on the Fire Prevention Ordinance of the Ministry of Internal Affairs and Communications Fire and Disaster Management Agency (Note: Existing models), so the power generation capacity Regardless of the situation, it is possible to submit a notification for the installation of a fire department in any area in Japan.

■Distance of power generation equipment (Fire Service Act)

According to the ``Emergency Power Supply (Private Power Generation Equipment) Test Standards'' of the Fire and Disaster Management Agency of the Ministry of Internal Affairs and Communications, private power generation equipment must be installed with the holding distance shown in Table 1.5.5.

■Notes

Due to improvements, product specifications and appearance are subject to change without notice.

  • Product

    Emergency gas engine generator Gas Denkun SGS-125K

Share this product


110+ people viewing

Last viewed: 4 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

1 Models of Emergency gas engine generator Gas Denkun SGS-125K

Image Part Number Price (excluding tax) Equipped with overcurrent protection device Equipment alarm stop function Equipment display function Equipped with automatic test driving function Equipped with battery charger Equipped battery Generator voltage adjustment method Generator phase number Generator type Generator rated current Generator rated voltage Generator rated frequency Generator rated output Generator excitation method Generator power factor Total engine displacement Engine fuel consumption (max) Engine ignition method Engine lubricant amount Engine type Engine rated speed Engine starting method Engine name Engine fuel Engine gas pipe connection port Engine gas pressure Engine engine oil Other separation distance all around Other weight Other housing plate thickness Other dimensions Other paint colors (Munsell value)
Emergency gas engine generator Gas Denkun SGS-125K-Part Number-SGS-125K

SGS-125K

Available upon quote

Attached AC100V

Voltage/current/power/engine speed/event history

MCCB400A/MCCB500A

Voltage abnormality (excess/insufficient) / Overcurrent/Frequency abnormality (excess/insufficient) / Engine speed/Cooling water rise/Gas leak alarm/Oil pressure drop/Battery voltage abnormality (excess/insufficient) /Internal temperature rise

CCA925 class

25.5L

AVR type

Three-phase 4-wire (100V cannot be used. Please contact us if you want to use 100V.)

Rotating field generator

375A/450A

200V

50Hz/60Hz

130kVA (104kW) /156kVA (125kW)

Self-exciting

0.8

8,800cc

17.1m2/h/20.2m2/h (There are slight differences depending on the outside temperature and gas supplier, but the amount of natural vaporization is said to be approximately 25m2 when 50kg of LP gas is vaporized.)

Electronically controlled

7.6L

Water-cooled 4-stroke V8 engine

1,500rpm/1,800rpm

Starter motor type

PSIIndustrialPowertrain8.8L

LPG

40A

2.8kPa

5W-30 (SM grade or higher)

3,000mm or more (This may vary depending on the site.)

2,100kg or less

2.0mm or more

Width 1,321mm Depth 3,429mm Height 2,184mm

Dark gray

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Emergency Power Generators Products

Other products of Shoei Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Shoei Co., Ltd.

About Company Handling This Product

Response Rate

100.0%


Response Time

16.4hrs

  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree