Multifunctional DC-AC inverter "NTN-5K Series" that can be used with three-phase, four-wire and connect up to 6 units in parallel.-NTN-5K-124
Multifunctional DC-AC inverter "NTN-5K Series" that can be used with three-phase, four-wire and connect up to 6 units in parallel.-Earth Power Co., Ltd.

Multifunctional DC-AC inverter "NTN-5K Series" that can be used with three-phase, four-wire and connect up to 6 units in parallel.
Earth Power Co., Ltd.


About This Product

■NTN-5K introduction This is an integrated inverter that combines the functions of an AC-DC charger, DC-AC inverter, and AC bypass. NTN-5K has a built-in "active current sharing function" that can share the most active current without waste, and up to 6 devices can be connected in parallel to provide higher output. You can now build a larger system with this single product, even if you have a capacity that could not be handled up until now, without the need for additional products. ■Main unit performance ・Perfect sine wave output (distortion rate: 3%) ・Three-phase four-wire inverter that reduces resistance loss ・Surge power capacity: Up to twice the rated output power (10KW) capacity ・Switchable output voltage and output frequency (DIP S.W) ・Input/output status can be checked on Status LED display ・Wide temperature range from -30℃ to +70℃ (see derating) ・Polymer coating on internal base ■Function ・DC-AC inverter/charger/UPS function (AC bypass) Built-in function DC Input/AC Input/AC Output (see system diagram) ・UPS function (AC bypass) switching time within 10ms ・Maximum 30KW parallel connection possible (N+1 unit) ・Supports MODBus-RTU/CANBus protocol communication ・Remote ON/OFF possible with R.C remote function ■Safety ・Primary and secondary side insulation design ・Battery low voltage cutoff (over discharge protection) ・Protection: reverse connection, low voltage, overvoltage, short circuit overload, overtemperature, etc. ■Standards ・Safety standards, EMC EMISSION, vibration test withstand voltage, insulation resistance conducted ・Standards: CB, TUV, EAC, AS/NZS, FC, CE, UKCA, UL (compliant) ■Notes ・Ordered products ・NTN-5K Series is a product of Taiwan MEAN WELL ENTERPRISES CO., LTD. Our company (Earth Power Co., Ltd.) owns the sales rights in Japan. - Jointly developed with MEAN WELL and sold with improved electrical characteristics specifications for Japan.

  • Product

    Multifunctional DC-AC inverter "NTN-5K Series" that can be used with three-phase, four-wire and connect up to 6 units in parallel.

Share this product


170+ people viewing

Last viewed: 6 hours ago


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

5 Models of Multifunctional DC-AC inverter "NTN-5K Series" that can be used with three-phase, four-wire and connect up to 6 units in parallel.

Items marked with have different values depending on the model number.

Click on the part number for more information about each product

Product Image Part Number Price (excluding tax) Charging current Charging range Communication Continuous output Efficiency Float charge Input side current Input side protection low voltage Input side protection overvoltage Input voltage range Instantaneous output Maximum charging power Maximum output No-load standby power Operating humidity range Operating temperature range Output frequency Output side protection Output voltage fluctuation value Output waveform Overload Parc charge Rated input voltage Remote control Reverse connection Side rated output voltage Storage temperature range Temperature compensation UPS mode When power is OFF
Multifunctional DC-AC inverter "NTN-5K Series" that can be used with three-phase, four-wire and connect up to 6 units in parallel.-Part Number-NTN-5K-124

NTN-5K-124

Available upon quote 120A DC21.0V~DC30.0V MODBus-RTU (RS-485) /CANBus 4,000W 89.00% DC27.6V 200A Alarm DC22.0V and DC0.5V
Shutoff DC20.0V SatDC0.5V
Restart DC25.0V SatDC0.5V
Overvoltage alarm OC31.0V DC0.5V
Overvoltage cutoff DC33.0V SatDC0.5V
Restart DC30.0V and DC0.5V
DC20.0V~DC33.0V 7,000W 3,600W (10sec) 5,600W
(180sec) 4,600W
Power save OFF:2.5A
Power save ON: When the side standby power connection load capacity is 10W or less,
Automatically shifts to power saving mode <25W
20%~90%RH
(No condensation)
-30~70℃ At the time of shipment: 60-shi 0.1Hz (50-shi 0.1Hz/60-shi 0.1Hz switchable) Overtemperature After overvoltage protection is detected and operation stops, automatic recovery occurs when temperature is resolved.
Short circuit Disconnect the connection and turn the power back on to recover.
circuit breaker 50A
3.0% (input side: rated output value at DC25.0V/DC50.0V) Sine wave (distortion rate: 3.0% or less) 180 seconds 105~115% of load capacity
115~140% of load capacity for 10 seconds
DC28.8V DC24V Output side ON/OFF remote terminal (RC terminal) Error After disconnecting all connections
Recovers when power is turned on again
Factory shipped AC110V (AC100V/AC115V/AC120V switchable) -30~+70℃ External temperature sensor AC input range AC100V AC110V AC115V AC120V 16%
Frequency range 45Hz~65Hz
Switching time Inverter mode UPS mode Switching in 001 seconds
≦1mA
Multifunctional DC-AC inverter "NTN-5K Series" that can be used with three-phase, four-wire and connect up to 6 units in parallel.-Part Number-NTN-5K-148

NTN-5K-148

Available upon quote 60A DC42.0V~DC60.0V MODBus-RTU (RS-485) /CANBus 4,000W 91.00% DC55.2V 100A Alarm DC44.0V and DC1.0V
Cutoff DC40.0V and DC1.0V
Restart DC50.0V and DC1.0V
Overvoltage alarm DC62.0V and DC1.0V
Overvoltage cutoff DC66.0V and DC1.0V
Restart DC60.0V and DC1.0V
DC40.0V~DC66.0V 8,000W 3,600W (10sec) 6,000W
(180sec) 4,600W
Power save OFF: 1.4A
Power save ON: When the side standby power connection load capacity is 10W or less,
Automatically shifts to power saving mode <25W
20%~90%RH
(No condensation)
-30~70℃ At the time of shipment: 60-shi 0.1Hz (50-shi 0.1Hz/60-shi 0.1Hz switchable) Overtemperature After overvoltage protection is detected and operation stops, automatic recovery occurs when temperature is resolved.
Short circuit Disconnect the connection and turn the power back on to recover.
circuit breaker 50A
3.0% (input side: rated output value at DC25.0V/DC50.0V) Sine wave (distortion rate: 3.0% or less) 180 seconds 105~115% of load capacity
115~150% of load capacity for 10 seconds
DC57.6V DC48V Output side ON/OFF remote terminal (RC terminal) Error After disconnecting all connections
Recovers when power is turned on again
Factory shipped AC110V (AC100V/AC115V/AC120V switchable) -30~+70℃ External temperature sensor AC input range AC100V AC110V AC115V AC120V 16%
Frequency range 45Hz~65Hz
Switching time Inverter mode UPS mode Switching in 001 seconds
≦1mA
Multifunctional DC-AC inverter "NTN-5K Series" that can be used with three-phase, four-wire and connect up to 6 units in parallel.-Part Number-NTN-5K-224

NTN-5K-224

Available upon quote 135A DC21.0V~DC30.0V MODBus-RTU (RS-485) /CANBus 5,000W 91.00% DC27.6V 240A Alarm DC22.0V SatDC0.5V
Shutoff DC20.0V SatDC0.5V
Restart DC25.0V and DC0.5V
Overvoltage alarm DC31.0V and DC0.5V
Overvoltage cutoff DC33.0V and DC0.5V
Restart DC30.0V and DC0.5V
DC20.0V~DC33.0V 8,000W 4,050W (10sec) 7,000W
(180sec) 5,750W
Power save OFF:2.5A
Power save ON: When the side standby power connection load capacity is 10W or less,
Automatically shifts to power saving mode <25W
20%~90%RH
(No condensation)
-30~70℃ When shipped: 50-shi 0.1Hz (50-shi 0.1Hz/60-shi 0.1Hz switchable) Overtemperature After overvoltage protection is detected and operation stops, automatic recovery occurs when temperature is resolved.
Short circuit Disconnect the connection and turn the power back on to recover.
circuit breaker 35A
3.0% (input side: rated output value at DC25.0V/DC50.0V/DC400) Sine wave (distortion rate: 3.0% or less) 180 seconds 105~115% of load capacity
115~140% of load capacity for 10 seconds
DC28.8V DC24V Output side ON/OFF remote terminal (RC terminal) Error After disconnecting all connections
Recovers when power is turned on again
At time of shipment: AC230V (AC200V/AC220V/AC240V switchable) -30~+70℃ External temperature sensor AC input range AC200V AC220V AC230V AC240V 16%
Frequency range 45Hz~65Hz
Switching time Inverter mode UPS mode Switching in 001 seconds
≦1mA
Multifunctional DC-AC inverter "NTN-5K Series" that can be used with three-phase, four-wire and connect up to 6 units in parallel.-Part Number-NTN-5K-248

NTN-5K-248

Available upon quote 70A DC42.0V~DC60.0V MODBus-RTU (RS-485) /CANBus 5,000W 93.00% DC55.2V 120A Alarm DC44.0V SatDC1.0V
Shutoff DC40.0V SatDC1.0V
Restart DC50.0V and DC1.0V
Overvoltage alarm DC62.0V and DC1.0V
Overvoltage cutoff DC66.0V and DC1.0V
Restart DC60.0V and DC1.0V
DC40.0V~DC66.0V 8,000W 4,200W (10sec) 7,500W
(180sec) 5,750W
Power save OFF: 1.4A
Power save ON: When the side standby power connection load capacity is 10W or less,
Automatically shifts to power saving mode <25W
20%~90%RH
(No condensation)
-30~70℃ When shipped: 50-shi 0.1Hz (50-shi 0.1Hz/60-shi 0.1Hz switchable) Overtemperature After overvoltage protection is detected and operation stops, automatic recovery occurs when temperature is resolved.
Short circuit Disconnect the connection and turn the power back on to recover.
circuit breaker 35A
3.0% (input side: rated output value at DC25.0V/DC50.0V/DC400) Sine wave (distortion rate: 3.0% or less) 180 seconds 105~115% of load capacity
115~150% of load capacity for 10 seconds
DC57.6V DC48V Output side ON/OFF remote terminal (RC terminal) Error After disconnecting all connections
Recovers when power is turned on again
At time of shipment: AC230V (AC200V/AC220V/AC240V switchable) -30~+70℃ External temperature sensor AC input range AC200V AC220V AC230V AC240V 16%
Frequency range 45Hz~65Hz
Switching time Inverter mode UPS mode Switching in 001 seconds
≦1mA
Multifunctional DC-AC inverter "NTN-5K Series" that can be used with three-phase, four-wire and connect up to 6 units in parallel.-Part Number-NTN-5K-2380

NTN-5K-2380

Available upon quote 11.3A DC300V~DC400V MODBus-RTU (RS-485) /CANBus 5,000W 94.50% DC385V 16A Alarm DC300.0V SatDC5.0V
Shutoff DC280.0V SatDC5.0V
Restart DC335.0V and DC5.0V
Overvoltage alarm DC420.0V and DC5.0V
Overvoltage cutoff DC430.0V and DC5.0V
Restart DC400.0V and DC5.0V
DC280V~DC430V 10,000W 4,520W (10sec) 7,500W
(180sec) 5,750W
Power save OFF:0.2A
Power save ON: When the side standby power connection load capacity is 10W or less,
Automatically shifts to power saving mode <25W
20%~90%RH
(No condensation)
-30~70℃ When shipped: 50-shi 0.1Hz (50-shi 0.1Hz/60-shi 0.1Hz switchable) Overtemperature After overvoltage protection is detected and operation stops, automatic recovery occurs when temperature is resolved.
Short circuit Disconnect the connection and turn the power back on to recover.
circuit breaker 35A
3.0% (input side: rated output value at DC25.0V/DC50.0V/DC400) Sine wave (distortion rate: 3.0% or less) 180 seconds 105~115% of load capacity
115~150% of load capacity for 10 seconds
DC400V DC380V Output side ON/OFF remote terminal (RC terminal) Error After disconnecting all connections
Recovers when power is turned on again
At time of shipment: AC230V (AC200V/AC220V/AC240V switchable) -30~+70℃ External temperature sensor AC input range AC200V AC220V AC230V AC240V 16%
Frequency range 45Hz~65Hz
Switching time Inverter mode UPS mode Switching in 001 seconds
≦1mA

Click on the part number for more information about each product

Customers who viewed this product also viewed

Other products of Earth Power Co., Ltd.


View more products of Earth Power Co., Ltd.

About Company Handling This Product

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree