All Categories
History
Product
Industrial large lithium ion storage battery EPESS-40Handling Company
Edison Power Co., Ltd.Categories
Image | Part Number | Price (excluding tax) | When switching power | Weight | Driving power factor | Communication method | Installation location | Storage battery board | Fire service law | Expected lifespan | Maximum operating voltage | Capacity | Rated voltage | Rated capacity | Rated frequency | Rated output voltage | Rated output | Frequency | Surrounding environment | Ambient humidity | Ambient temperature | Switching time | Output capacity | Cooling method | Protection related | Power conditioner section rated voltage | System input power | Number of cycles | Inverter method |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
EPESS-40 |
Available upon quote |
Maximum approximately 80dB (0.5 seconds) Normally less than 50dB |
Approximately 600kg |
0.95 or more (at rated operation) |
Ethernet |
Indoor/outdoor |
W680mm × D860mm × H2,120mm × 1set |
Correspondence |
10~15 years (environmental temperature 25℃, DOD80%) |
About DC 380~400V |
9.9kW x 1~5 systems |
DC350V |
40kWh |
50/60Hz |
Three-phase 200V (also compatible with single-phase 100V and 200V with Scott transformer) |
9.9kW / 19.8kW / 29.7kW / 39.6kW / 49.5kW |
50/60Hz |
No salt damage, dust, vibration, or corrosive gas |
Relative humidity 25℃~90%RH (no condensation) |
0~45℃ (-10~45℃ during storage) |
During power outage: Approximately 15~20 seconds |
Approximately 15kW~100kW |
Natural air cooling |
Compliant with grid connection regulations (overvoltage, undervoltage, overfrequency, underfrequency, FRT requirements) |
Three-phase 3-wire AC202V |
Three-phase 3-wire 200V 50/60Hz |
4,000~6,000 cycles (environmental temperature 25℃, DOD80%) |
Voltage type current control |
Reviews shown here are reviews of companies.
Reviews shown here are reviews of companies.