All Categories

History

Demand monitoring device Energy saving system Power line communication load control system PLC Super Max II Load control transmitter PLC-SM013T-PLC-SM013T
Demand monitoring device Energy saving system Power line communication load control system PLC Super Max II Load control transmitter PLC-SM013T-Osaki Electric Industry Co., Ltd.

Demand monitoring device Energy saving system Power line communication load control system PLC Super Max II Load control transmitter PLC-SM013T
Osaki Electric Industry Co., Ltd.

Osaki Electric Industry Co., Ltd.'s Response Status

Response Rate

100.0%

Response Time

24.1hours

Relatively Fast Response


About This Product

■Features

Electrical wiring is transformed into a control line. Existing power distribution lines are used as the route for the load control signal from the demand control device itself, making construction easy and low cost, and allows quick response to load additions and relocations.

■When connecting to a three-phase three-wire bank

The load control transmitter PLC-SM013T connects to an ungrounded wire. Connect the load control receiver PLC-SM123R (for 200V) in phase with the transmitter. Phase order and polarity do not matter. Load control receiver PLC-SM113R (for 100V) cannot be used.

■When connecting to a single-phase 3-wire bank

The load control transmitter PLC-SM013T connects to two wires other than the neutral wire. Connect the PLC-SM113R or PLC-SM123R to the load control receiver depending on the voltage. Phase order and polarity do not matter.

■Notes on system installation

・Although we have taken sufficient technical measures to prevent noise, signal transmission may not be possible if the power supply environment is extremely poor. ・It is not recommended to install this product in facilities where medical equipment or other systems that have a serious impact on human life or property are installed. - Regarding the control of systems such as air conditioners, please consult the manufacturer regarding technical possibilities.

  • Product

    Demand monitoring device Energy saving system Power line communication load control system PLC Super Max II Load control transmitter PLC-SM013T

Share this product


180+ people viewing

Last viewed: 13 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

1 Models of Demand monitoring device Energy saving system Power line communication load control system PLC Super Max II Load control transmitter PLC-SM013T

Image Part Number Price (excluding tax) Power line power frequency Power line voltage Power line bank capacity Communication method Transmitter injection current Mass Display Alarm LED Display Contact control status LED Display Operation LED Power consumption Maximum transmission distance Rated voltage Rated frequency External dimensions Installation method Output Alarm output points Output Alarm output Contact signal Input load control signal number of points Input Load control signal Contact signal Input output level monitor Usage environment Frequency band used
Demand monitoring device Energy saving system Power line communication load control system PLC Super Max II Load control transmitter PLC-SM013T-Part Number-PLC-SM013T

PLC-SM013T

$ 975.00〜

50/60Hz±2Hz (automatic switching)

AC220V or less

500kVA or less

Power line communication method
(Unidirectional: transmitter → receiver)

12A or less (at voltage 200V)

Approximately 2kg

When the device is abnormal: Flashing When normal: Off Color: Red

16 input contacts Lights up when ON Color: Red

When powering on: Lit When sending: Blinking Color: Red

When transmitting: 400VA or less When standing by: 12VA or less

300m

AC100V±10%

50/60Hz±2Hz
(However, ±1Hz for transmission)

175 (W) × 250 (H) × 75 (D) mm

Wall-mounted

1 point

No-voltage B contact AC250V 5A (resistive load)

16 points

No-voltage A contact or open collector DC12V or less

1 point (for power line communication monitor)

Temperature: 0℃~50℃ Humidity: 90%RH or less (non-condensing)

Less than 10kHz

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Power Monitorings Products

Other products of Osaki Electric Industry Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Osaki Electric Industry Co., Ltd.

About Company Handling This Product

Response Rate

100.0%


Response Time

24.1hrs

  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree