Product
Energy meter Built-in EM Single-phase 2-wire/Single-phase 3-wire/Three-phase 3-wire A1D-RLS27V, A2D-RLS27V, A3D-RLS27VHandling Company
Osaki Electric Industry Co., Ltd.Categories
Items marked with have different values depending on the model number.
Click on the part number for more information about each product
Product Image | Part Number | Price (excluding tax) | Current circuit apparent power (VA) | Installation/connection method | Instrument constant (pulse/kWs) /110V | Instrument constant (pulse/kWs) 100V | Instrument constant (pulse/kWs) 200V | Instrument constant (pulse/kWs) 220V | Instrument constant (pulse/kWs) 240V | Mass (g) | Phase wire system | Pulse constant 10^n (pulse/kWh) | Pulse constant specific (1) /5A | Pulse constant specific (2) /5A | Pulse width 10n | Pulse width Front metering pulse | Pulse width specific (1) | Pulse width specific (2) | Rated current (A) | Rated frequency (Hz) | Rated voltage (V) | S27 type transmitter specifications AC/DC | S27 type transmitter specifications On-resistance (Ω) | S27 type transmitter specifications Output method | S27 type transmitter specifications Polarity | S27 type transmitter specifications Pulse capacity | S27 type transmitter specifications Pulse current | S27 type transmitter specifications Pulse voltage | S27 type transmitter specifications Wire type | Terminal cover | Type approval number | Voltage circuit apparent power (VA) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
A1D-RLS27V |
Available upon quote | 1S-1L: 0.08 or less | Embedded mounting/rear connection | 2,000 | 2,000 | 1,000 | - | 750 | Approximately 450 | Single phase 2 wire | Select one from 1/10/ (multiplication factor), 1/ (multiplication factor), 10/ (multiplication factor), 100/ (multiplication factor) |
100V, /110V: 4,000 pulse/kWh 200V, 240V: 2,000 pulse/kWh |
100V, /110V: 100,000 pulse/kWh 200V, 240V: 50,000 pulse/kWh |
Select one of 120, 240, 520, 820, 1020±15msec | 21μsec or more | 240±15msec (fixed) | 20±5msec (fixed) | /5 | 50 or 60 | 100, /110, 200, 240 |
(1), (2): AC/DC (3) :Direct |
(1), (2): 50 or less (3) :NULL |
Transmission pulse (1) C1A-C1B No-voltage a contact (photomos relay) Transmission pulse (2) C2A-C2B No-voltage a contact (Photomos relay) Transmission pulse (3) C1-C2 No-voltage a contact (photocoupler) |
(1), (2): None (3): Yes |
(1), (2): 10VA or less (3): 0.15VA or less |
(1), (2): 0.1A DC or 0.07A AC or less (3): 0.03A DC or less |
(1), (2): 175V DC or 120V AC or less (3): 35V DC or less |
2 wires | Standard equipment | No. 4596 | P1-P2: 1.09 or less | |
A2D-RLS27V |
Available upon quote | 1S-1L, 3S-3L: 0.08 or less | Embedded mounting/rear connection | - | 1,000 | - | - | - | Approximately 460 | Single phase 3 wire | Select one from 1/10/ (multiplication factor), 1/ (multiplication factor), 10/ (multiplication factor), 100/ (multiplication factor) | 2,000 pulses/kWh | 50,000 pulses/kWh | Select one of 120, 240, 520, 820, 1020±15msec | 21μsec or more | 240±15msec (fixed) | 20±5msec (fixed) | /5 | 50 or 60 | 100 |
(1), (2): AC/DC (3) :Direct |
(1), (2): 50 or less (3) :NULL |
Transmission pulse (1) C1A-C1B No-voltage a contact (photomos relay) Transmission pulse (2) C2A-C2B No-voltage a contact (Photomos relay) Transmission pulse (3) C1-C2 No-voltage a contact (photocoupler) |
(1), (2): None (3): Yes |
(1), (2): 10VA or less (3): 0.15VA or less |
(1), (2): 0.1A DC or 0.07A AC or less (3): 0.03A DC or less |
(1), (2): 175V DC or 120V AC or less (3): 35V DC or less |
2 wires | Standard equipment | No. 4597 |
P1-P2: 0.75 or less P3-P2: 0.02 or less |
|
A3D-RLS27V |
Available upon quote | 1S-1L, 3S-3L: 0.08 or less | Embedded mounting/rear connection | 1,000 | 1,000 | 500 | 500 | - | Approximately 460 | Three-phase three-wire system | Select one from 1/10/ (multiplication factor), 1/ (multiplication factor), 10/ (multiplication factor), 100/ (multiplication factor) |
100V, /110V: 2,000 pulse/kWh 200V, 200V: 1,000 pulse/kWh |
100V, /110V: 50,000 pulse/kWh 200V, 200V: 25,000 pulse/kWh |
Select one from 120, 240, 520, 820, 1020±15msec | 21μsec or more | 240±15msec (fixed) | 20±5msec (fixed) | /5 | 50 or 60 |
100, /110, 200, (220) *() indicates that the test cannot be verified. |
(1), (2): AC/DC (3) :Direct |
(1), (2): 50 or less (3) :NULL |
Transmission pulse (1) C1A-C1B No-voltage a contact (photomos relay) Transmission pulse (2) C2A-C2B No-voltage a contact (Photomos relay) Transmission pulse (3) C1-C2 No-voltage a contact (photocoupler) |
(1), (2): None (3): Yes |
(1), (2): 10VA or less (3): 0.15VA or less |
(1), (2): 0.1A DC or 0.07A AC or less (3): 0.03A DC or less |
(1), (2): 175V DC or 120V AC or less (3): 35V DC or less |
2 wires | Standard equipment | No. 4598 |
P1-P2: 0.99 or less P3-P2: 0.07 or less |
Click on the part number for more information about each product