Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-HBA-T120P-5
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-RKC INSTRUMENT

Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130
RKC INSTRUMENT


About This Product

■What is a heater burnout alarm? This is a device that monitors the current value flowing to the heater with a CT (current detector) and outputs an output through a contact when the heater is disconnected. We offer models whose controller output supports relay contact, SSR drive, phase control, zero cross control, etc. Panel mounting or DIN rail mounting is possible. ■HBA-T120 (for single-phase power regulator control) Built-in MCU automatically sets load current. Used for phase control and zero cross control using a power regulator. *Compatible CT: MCTL-6-P-N (load current up to 30A), MCTL-12-S56-10L-N (load current up to 100A), relay contact/SSR drive control system also available ■HBA-T130 (for three-phase power regulator control system) Built-in MCU automatically sets load current. Used for phase control and zero cross control using a three-phase power regulator. *Compatible CT: MCTL-6-P-N (load current up to 30A), MCTL-12-S56-10L-N (load current up to 100A), 2 CTs are used, relay contact/SSR drive control system is also possible *Other product numbers are available.

  • Product

    Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130

Share this product


340+ people viewing

Last viewed: 7 hours ago


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

10 Models of Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130

Items marked with have different values depending on the model number.

Click on the part number for more information about each product

Product Image Part Number Price (excluding tax) Alarm output Alarm setting accuracy Applicable control method Insulation resistance Load current Load setting accuracy Mass Permissible ambient humidity Permissible ambient temperature Power supply voltage Settable range Type Withstand voltage
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-Part Number-HBA-T120P-5

HBA-T120P-5

Available upon quote 1 point, relay contact output, AC220V, 1A (resistive load) Within ±3% of the rated capacity of the alarm body
*However, if the load voltage is 30% or less of the rating, it will be outside the accuracy range.
For phase control system DC500V 50MΩ between each input/output terminal 5A (using current detector MCTL-6-P-N) Within ±3% of the rated capacity of the alarm body Approximately 300g 45~85%RH (no condensation) 0~50℃ AC90~242V (including power supply voltage fluctuation), 50/60Hz common (rated AC100~220V) Set at a current reduction rate of 0 to 30% of the rated capacity of the alarm body (0 to 15% of alarm set value x 2) For thyristor power regulator drive control system (single phase) AC1,500V between each input/output terminal for 1 minute
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-Part Number-HBA-T120P-30

HBA-T120P-30

Available upon quote 1 point, relay contact output, AC220V, 1A (resistive load) Within ±3% of the rated capacity of the alarm body
*However, if the load voltage is 30% or less of the rating, it will be outside the accuracy range.
For phase control system DC500V 50MΩ between each input/output terminal 30A (using current detector MCTL-6-P-N) Within ±3% of the rated capacity of the alarm body Approximately 300g 45~85%RH (no condensation) 0~50℃ AC90~242V (including power supply voltage fluctuation), 50/60Hz common (rated AC100~220V) Set at a current reduction rate of 0 to 30% of the rated capacity of the alarm body (0 to 15% of alarm set value x 2) For thyristor power regulator drive control system (single phase) AC1,500V between each input/output terminal for 1 minute
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-Part Number-HBA-T120P-100

HBA-T120P-100

Available upon quote 1 point, relay contact output, AC220V, 1A (resistive load) Within ±3% of the rated capacity of the alarm body
*However, if the load voltage is 30% or less of the rating, it will be outside the accuracy range.
For phase control system DC500V 50MΩ between each input/output terminal 100A (using current detector MCTL-12-S56-10L-N) Within ±3% of the rated capacity of the alarm body Approximately 300g 45~85%RH (no condensation) 0~50℃ AC90~242V (including power supply voltage fluctuation), 50/60Hz common (rated AC100~220V) Set at a current reduction rate of 0 to 30% of the rated capacity of the alarm body (0 to 15% of alarm set value x 2) For thyristor power regulator drive control system (single phase) AC1,500V between each input/output terminal for 1 minute
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-Part Number-HBA-T120Z-5

HBA-T120Z-5

Available upon quote 1 point, relay contact output, AC220V, 1A (resistive load) Within ±3% of the rated capacity of the alarm body
*However, if the load voltage is 30% or less of the rating, it will be outside the accuracy range.
For zero cross control system DC500V 50MΩ between each input/output terminal 5A (using current detector MCTL-6-P-N) Within ±3% of the rated capacity of the alarm body Approximately 300g 45~85%RH (no condensation) 0~50℃ AC90~242V (including power supply voltage fluctuation), 50/60Hz common (rated AC100~220V) Set at a current reduction rate of 0 to 30% of the rated capacity of the alarm body (0 to 15% of alarm set value x 2) For thyristor power regulator drive control system (single phase) AC1,500V between each input/output terminal for 1 minute
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-Part Number-HBA-T120Z-30

HBA-T120Z-30

Available upon quote 1 point, relay contact output, AC220V, 1A (resistive load) Within ±3% of the rated capacity of the alarm body
*However, if the load voltage is 30% or less of the rating, it will be outside the accuracy range.
For zero cross control system DC500V 50MΩ between each input/output terminal 30A (using current detector MCTL-6-P-N) Within ±3% of the rated capacity of the alarm body Approximately 300g 45~85%RH (no condensation) 0~50℃ AC90~242V (including power supply voltage fluctuation), 50/60Hz common (rated AC100~220V) Set at a current reduction rate of 0 to 30% of the rated capacity of the alarm body (0 to 15% of alarm set value x 2) For thyristor power regulator drive control system (single phase) AC1,500V between each input/output terminal for 1 minute
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-Part Number-HBA-T120Z-100

HBA-T120Z-100

Available upon quote 1 point, relay contact output, AC220V, 1A (resistive load) Within ±3% of the rated capacity of the alarm body
*However, if the load voltage is 30% or less of the rating, it will be outside the accuracy range.
For zero cross control system DC500V 50MΩ between each input/output terminal 100A (using current detector MCTL-12-S56-10L-N) Within ±3% of the rated capacity of the alarm body Approximately 300g 45~85%RH (no condensation) 0~50℃ AC90~242V (including power supply voltage fluctuation), 50/60Hz common (rated AC100~220V) Set at a current reduction rate of 0 to 30% of the rated capacity of the alarm body (0 to 15% of alarm set value x 2) For thyristor power regulator drive control system (single phase) AC1,500V between each input/output terminal for 1 minute
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-Part Number-HBA-T130P-5

HBA-T130P-5

Available upon quote 1 point, relay contact output, AC220V, 1A (resistive load) Within ±3% of the rated capacity of the alarm body
*However, if the load voltage is 30% or less of the rating, it will be outside the accuracy range.
For phase control system DC500V 50MΩ between each input/output terminal 5A (using current detector MCTL-6-P-N) Within ±3% of the rated capacity of the alarm body Approximately 350g 45~85%RH (no condensation) 0~50℃ AC90~242V (including power supply voltage fluctuation), 50/60Hz common (rated AC100~220V) Set at a current reduction rate of 0 to 30% of the rated capacity of the alarm body (0 to 15% of alarm set value x 2) For thyristor power regulator drive control system (for three-phase) AC1,500V between each input/output terminal for 1 minute
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-Part Number-HBA-T130P-30

HBA-T130P-30

Available upon quote 1 point, relay contact output, AC220V, 1A (resistive load) Within ±3% of the rated capacity of the alarm body
*However, if the load voltage is 30% or less of the rating, it will be outside the accuracy range.
For phase control system DC500V 50MΩ between each input/output terminal 30A (using current detector MCTL-6-P-N) Within ±3% of the rated capacity of the alarm body Approximately 350g 45~85%RH (no condensation) 0~50℃ AC90~242V (including power supply voltage fluctuation), 50/60Hz common (rated AC100~220V) Set at a current reduction rate of 0 to 30% of the rated capacity of the alarm body (0 to 15% of alarm set value x 2) For thyristor power regulator drive control system (for three-phase) AC1,500V between each input/output terminal for 1 minute
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-Part Number-HBA-T130P-100

HBA-T130P-100

Available upon quote 1 point, relay contact output, AC220V, 1A (resistive load) Within ±3% of the rated capacity of the alarm body
*However, if the load voltage is 30% or less of the rating, it will be outside the accuracy range.
For phase control system DC500V 50MΩ between each input/output terminal 100A (using current detector MCTL-12-S56-10L-N) Within ±3% of the rated capacity of the alarm body Approximately 350g 45~85%RH (no condensation) 0~50℃ AC90~242V (including power supply voltage fluctuation), 50/60Hz common (rated AC100~220V) Set at a current reduction rate of 0 to 30% of the rated capacity of the alarm body (0 to 15% of alarm set value x 2) For thyristor power regulator drive control system (for three-phase) AC1,500V between each input/output terminal for 1 minute
Heater burnout alarm with built-in MCU for single-phase/three-phase power regulator (DIN rail mounting type) HBA-T120/HBA-T130-Part Number-HBA-T130Z-5

HBA-T130Z-5

Available upon quote 1 point, relay contact output, AC220V, 1A (resistive load) Within ±3% of the rated capacity of the alarm body
*However, if the load voltage is 30% or less of the rating, it will be outside the accuracy range.
For zero cross control system DC500V 50MΩ between each input/output terminal 5A (using current detector MCTL-6-P-N) Within ±3% of the rated capacity of the alarm body Approximately 350g 45~85%RH (no condensation) 0~50℃ AC90~242V (including power supply voltage fluctuation), 50/60Hz common (rated AC100~220V) Set at a current reduction rate of 0 to 30% of the rated capacity of the alarm body (0 to 15% of alarm set value x 2) For thyristor power regulator drive control system (for three-phase) AC1,500V between each input/output terminal for 1 minute

Click on the part number for more information about each product