Program controller (temperature controller) PF900-PF900-MNN-3*4NNN
Program controller (temperature controller) PF900-RKC INSTRUMENT

Program controller (temperature controller) PF900
RKC INSTRUMENT

RKC INSTRUMENT's Response Status

Response Rate

100.0%

Response Time

15.5hours

Relatively Fast Response


About This Product

■Large capacity Program of up to 1,024 segments

・Program settings can be made in the range of 99 patterns x 10 segments to 10 patterns x 99 segments. - With 32 patterns x 32 segments, a maximum of 1,024 segment programs are possible when all patterns are linked.

■Time signal output function/segment signal output function selectable

You can select either the time signal output function, which outputs at the time set within the pattern, or the segment signal output function, which outputs the signal set for each segment.

■Level PID and segment PID can be selected

- Level PID and segment PID can be used separately for each segment. - Setting values ​​can be registered in 8 levels (level PID) or 8 types of memory groups (segment PID).

■Equipped with new control algorithm “RSS (Ramp Soak Stabilizer)”

Control stability is improved by simultaneously improving followability at the start of ramp control and suppressing overshoot when transitioning to soak control.

■Easy setup "Front loader communication + program setting tool"

Loader communication + dedicated program setting tool allows you to visually and easily set programs with complex patterns.

■You can choose from two types: green display/white display.

You can choose from two types: PF900 (PV display: green, SV display: orange, pattern display: white) and PF901 (PV display: white, SV display: white, pattern display: white). *Other product numbers are available.

  • Product

    Program controller (temperature controller) PF900

Share this product


250+ people viewing

Last viewed: 22 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

10 Models of Program controller (temperature controller) PF900

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Power supply voltage Square root calculation function Communication function Digital input (DI 1 to 6) Permissible ambient temperature Influence of permissible input conductors Inrush current Power consumption Specifying factory settings Output program pattern number selection Output 3 (OUT3) Output 2 (OUT2) Output 1 (OUT1) Effects of power outage Effect of signal source resistance Link pattern number Memory backup Number of program memories Program control Time accuracy Pattern repeat execution count Pattern end output time Digital output Digital filter Time signal Memory group number Number of segment memories Segment repeat execution count Segment time Sampling period PV ratio PV bias CT input or opening feedback resistance input
Program controller (temperature controller) PF900-Part Number-PF900-MNN-3*4NNN

PF900-MNN-3*4NNN

Available upon quote

AC/DC24V

Arithmetic formula: PV = √ (input value) × PV ratio + PV bias
Low level cutoff: 0.00~25.00% of span

None

-10~+55℃

Approximately 0.01% of span (resistance temperature detector input) *within a maximum of 10Ω per wire

AC24V specification: 8.5A or less
DC24V specification: 6.0A or less

AC24V specification: 8.5VA<6.2VA>
DC24V specification: 230mA<173mA>

None

0~ (128÷maximum number of segments)
*No assignment when set to 0
*Maximum number of segments: Number of segments in the setting of number of patterns x number of segments

No output 3

No output 2

Relay contact output

No effect on power outages of 20ms or less

0.2μV/Ω (thermocouple input)

0~99 patterns *No pattern link when set to 0

Data backup using non-volatile memory (FRAM)
Data storage retention period: Approximately 10 years
Number of rewrites: Approximately 10 billion times
(However, the storage period of the product varies depending on the storage environment and usage environment)

Up to 99 patterns (variable)

±0.01% of Reading or input sampling time, whichever is greater

1~10,000 times
*Execute infinite times with 10,000 settings

0 hours 00 minutes to 500 hours 00 minutes or 0 minutes 00 seconds to 500 minutes 00 seconds
*Continues ON when set to 0

DO4 points DO1~4 (relay contact) *Standard equipment

Can be set from 0.1 to 100.0 seconds (OFF at 0 seconds)

0~16
*No assignment when set to 0

Up to 1,024 segments
*However, the maximum number of segments per pattern is within 99 segments.
*Hold, step, fast forward/rewind functions included

1~9,999 times
*1 setting disables segment repeat

0 hours 0 minutes to 500 hours 00 minutes or 0 minutes 0 seconds to 500 minutes 00 seconds

0.1 seconds (switchable to 0.05 seconds/0.25 seconds)

0.001~9.999

±input range span

No input

Program controller (temperature controller) PF900-Part Number-PF900-MNN-3*4N1N

PF900-MNN-3*4N1N

Available upon quote

AC/DC24V

Arithmetic formula: PV = √ (input value) × PV ratio + PV bias
Low level cutoff: 0.00~25.00% of span

Communication 1: RS-232C Communication 2: None/6 digital inputs DI 1~6

-10~+55℃

Approximately 0.01% of span (resistance temperature detector input) *within a maximum of 10Ω per wire

AC24V specification: 8.5A or less
DC24V specification: 6.0A or less

AC24V specification: 8.5VA<6.2VA>
DC24V specification: 230mA<173mA>

None

0~ (128÷maximum number of segments)
*No assignment when set to 0
*Maximum number of segments: Number of segments in the setting of number of patterns x number of segments

No output 3

No output 2

Relay contact output

No effect on power outages of 20ms or less

0.2μV/Ω (thermocouple input)

0~99 patterns *No pattern link when set to 0

Data backup using non-volatile memory (FRAM)
Data storage retention period: Approximately 10 years
Number of rewrites: Approximately 10 billion times
(However, the storage period of the product varies depending on the storage environment and usage environment)

Up to 99 patterns (variable)

±0.01% of Reading or input sampling time, whichever is greater

1~10,000 times
*Execute infinite times with 10,000 settings

0 hours 00 minutes to 500 hours 00 minutes or 0 minutes 00 seconds to 500 minutes 00 seconds
*Continues ON when set to 0

DO4 points DO1~4 (relay contact) *Standard equipment

Can be set from 0.1 to 100.0 seconds (OFF at 0 seconds)

0~16
*No assignment when set to 0

Up to 1,024 segments
*However, the maximum number of segments per pattern is within 99 segments.
*Hold, step, fast forward/rewind functions included

1~9,999 times
*1 setting disables segment repeat

0 hours 0 minutes to 500 hours 00 minutes or 0 minutes 0 seconds to 500 minutes 00 seconds

0.1 seconds (switchable to 0.05 seconds/0.25 seconds)

0.001~9.999

±input range span

No input

Program controller (temperature controller) PF900-Part Number-PF900-MNN-3*4N4N

PF900-MNN-3*4N4N

Available upon quote

AC/DC24V

Arithmetic formula: PV = √ (input value) × PV ratio + PV bias
Low level cutoff: 0.00~25.00% of span

Communication 1: RS-422A Communication 2: None/6 digital inputs DI 1~6

-10~+55℃

Approximately 0.01% of span (resistance temperature detector input) *within a maximum of 10Ω per wire

AC24V specification: 8.5A or less
DC24V specification: 6.0A or less

AC24V specification: 8.5VA<6.2VA>
DC24V specification: 230mA<173mA>

None

0~ (128÷maximum number of segments)
*No assignment when set to 0
*Maximum number of segments: Number of segments in the setting of number of patterns x number of segments

No output 3

No output 2

Relay contact output

No effect on power outages of 20ms or less

0.2μV/Ω (thermocouple input)

0~99 patterns *No pattern link when set to 0

Data backup using non-volatile memory (FRAM)
Data storage retention period: Approximately 10 years
Number of rewrites: Approximately 10 billion times
(However, the storage period of the product varies depending on the storage environment and usage environment)

Up to 99 patterns (variable)

±0.01% of Reading or input sampling time, whichever is greater

1~10,000 times
*Execute infinite times with 10,000 settings

0 hours 00 minutes to 500 hours 00 minutes or 0 minutes 00 seconds to 500 minutes 00 seconds
*Continues ON when set to 0

DO4 points DO1~4 (relay contact) *Standard equipment

Can be set from 0.1 to 100.0 seconds (OFF at 0 seconds)

0~16
*No assignment when set to 0

Up to 1,024 segments
*However, the maximum number of segments per pattern is within 99 segments.
*Hold, step, fast forward/rewind functions included

1~9,999 times
*1 setting disables segment repeat

0 hours 0 minutes to 500 hours 00 minutes or 0 minutes 0 seconds to 500 minutes 00 seconds

0.1 seconds (switchable to 0.05 seconds/0.25 seconds)

0.001~9.999

±input range span

No input

Program controller (temperature controller) PF900-Part Number-PF900-MNN-3*4N5N

PF900-MNN-3*4N5N

Available upon quote

AC/DC24V

Arithmetic formula: PV = √ (input value) × PV ratio + PV bias
Low level cutoff: 0.00~25.00% of span

Communication 1: RS-485 Communication 2: None/6 digital inputs DI 1~6

-10~+55℃

Approximately 0.01% of span (resistance temperature detector input) *within a maximum of 10Ω per wire

AC24V specification: 8.5A or less
DC24V specification: 6.0A or less

AC24V specification: 8.5VA<6.2VA>
DC24V specification: 230mA<173mA>

None

0~ (128÷maximum number of segments)
*No assignment when set to 0
*Maximum number of segments: Number of segments in the setting of number of patterns x number of segments

No output 3

No output 2

Relay contact output

No effect on power outages of 20ms or less

0.2μV/Ω (thermocouple input)

0~99 patterns *No pattern link when set to 0

Data backup using non-volatile memory (FRAM)
Data storage retention period: Approximately 10 years
Number of rewrites: Approximately 10 billion times
(However, the storage period of the product varies depending on the storage environment and usage environment)

Up to 99 patterns (variable)

±0.01% of Reading or input sampling time, whichever is greater

1~10,000 times
*Execute infinite times with 10,000 settings

0 hours 00 minutes to 500 hours 00 minutes or 0 minutes 00 seconds to 500 minutes 00 seconds
*Continues ON when set to 0

DO4 points DO1~4 (relay contact) *Standard equipment

Can be set from 0.1 to 100.0 seconds (OFF at 0 seconds)

0~16
*No assignment when set to 0

Up to 1,024 segments
*However, the maximum number of segments per pattern is within 99 segments.
*Hold, step, fast forward/rewind functions included

1~9,999 times
*1 setting disables segment repeat

0 hours 0 minutes to 500 hours 00 minutes or 0 minutes 0 seconds to 500 minutes 00 seconds

0.1 seconds (switchable to 0.05 seconds/0.25 seconds)

0.001~9.999

±input range span

No input

Program controller (temperature controller) PF900-Part Number-PF900-MNN-3*4NWN

PF900-MNN-3*4NWN

Available upon quote

AC/DC24V

Arithmetic formula: PV = √ (input value) × PV ratio + PV bias
Low level cutoff: 0.00~25.00% of span

Communication 1: RS-232C Communication 2: RS-485/6 digital inputs DI 1~6

-10~+55℃

Approximately 0.01% of span (resistance temperature detector input) *within a maximum of 10Ω per wire

AC24V specification: 8.5A or less
DC24V specification: 6.0A or less

AC24V specification: 8.5VA<6.2VA>
DC24V specification: 230mA<173mA>

None

0~ (128÷maximum number of segments)
*No assignment when set to 0
*Maximum number of segments: Number of segments in the setting of number of patterns x number of segments

No output 3

No output 2

Relay contact output

No effect on power outages of 20ms or less

0.2μV/Ω (thermocouple input)

0~99 patterns *No pattern link when set to 0

Data backup using non-volatile memory (FRAM)
Data storage retention period: Approximately 10 years
Number of rewrites: Approximately 10 billion times
(However, the storage period of the product varies depending on the storage environment and usage environment)

Up to 99 patterns (variable)

±0.01% of Reading or input sampling time, whichever is greater

1~10,000 times
*Execute infinite times with 10,000 settings

0 hours 00 minutes to 500 hours 00 minutes or 0 minutes 00 seconds to 500 minutes 00 seconds
*Continues ON when set to 0

DO4 points DO1~4 (relay contact) *Standard equipment

Can be set from 0.1 to 100.0 seconds (OFF at 0 seconds)

0~16
*No assignment when set to 0

Up to 1,024 segments
*However, the maximum number of segments per pattern is within 99 segments.
*Hold, step, fast forward/rewind functions included

1~9,999 times
*1 setting disables segment repeat

0 hours 0 minutes to 500 hours 00 minutes or 0 minutes 0 seconds to 500 minutes 00 seconds

0.1 seconds (switchable to 0.05 seconds/0.25 seconds)

0.001~9.999

±input range span

No input

Program controller (temperature controller) PF900-Part Number-PF900-MNN-3*4NXN

PF900-MNN-3*4NXN

Available upon quote

AC/DC24V

Arithmetic formula: PV = √ (input value) × PV ratio + PV bias
Low level cutoff: 0.00~25.00% of span

Communication 1: RS-485 Communication 2: RS-485/6 digital inputs DI 1~6

-10~+55℃

Approximately 0.01% of span (resistance temperature detector input) *within a maximum of 10Ω per wire

AC24V specification: 8.5A or less
DC24V specification: 6.0A or less

AC24V specification: 8.5VA<6.2VA>
DC24V specification: 230mA<173mA>

None

0~ (128÷maximum number of segments)
*No assignment when set to 0
*Maximum number of segments: Number of segments in the setting of number of patterns x number of segments

No output 3

No output 2

Relay contact output

No effect on power outages of 20ms or less

0.2μV/Ω (thermocouple input)

0~99 patterns *No pattern link when set to 0

Data backup using non-volatile memory (FRAM)
Data storage retention period: Approximately 10 years
Number of rewrites: Approximately 10 billion times
(However, the storage period of the product varies depending on the storage environment and usage environment)

Up to 99 patterns (variable)

±0.01% of Reading or input sampling time, whichever is greater

1~10,000 times
*Execute infinite times with 10,000 settings

0 hours 00 minutes to 500 hours 00 minutes or 0 minutes 00 seconds to 500 minutes 00 seconds
*Continues ON when set to 0

DO4 points DO1~4 (relay contact) *Standard equipment

Can be set from 0.1 to 100.0 seconds (OFF at 0 seconds)

0~16
*No assignment when set to 0

Up to 1,024 segments
*However, the maximum number of segments per pattern is within 99 segments.
*Hold, step, fast forward/rewind functions included

1~9,999 times
*1 setting disables segment repeat

0 hours 0 minutes to 500 hours 00 minutes or 0 minutes 0 seconds to 500 minutes 00 seconds

0.1 seconds (switchable to 0.05 seconds/0.25 seconds)

0.001~9.999

±input range span

No input

Program controller (temperature controller) PF900-Part Number-PF900-MNN-3*4NYN

PF900-MNN-3*4NYN

Available upon quote

AC/DC24V

Arithmetic formula: PV = √ (input value) × PV ratio + PV bias
Low level cutoff: 0.00~25.00% of span

Communication 1: None Communication 2: RS-485/6 digital inputs DI 1~6

-10~+55℃

Approximately 0.01% of span (resistance temperature detector input) *within a maximum of 10Ω per wire

AC24V specification: 8.5A or less
DC24V specification: 6.0A or less

AC24V specification: 8.5VA<6.2VA>
DC24V specification: 230mA<173mA>

None

0~ (128÷maximum number of segments)
*No assignment when set to 0
*Maximum number of segments: Number of segments in the setting of number of patterns x number of segments

No output 3

No output 2

Relay contact output

No effect on power outages of 20ms or less

0.2μV/Ω (thermocouple input)

0~99 patterns *No pattern link when set to 0

Data backup using non-volatile memory (FRAM)
Data storage retention period: Approximately 10 years
Number of rewrites: Approximately 10 billion times
(However, the storage period of the product varies depending on the storage environment and usage environment)

Up to 99 patterns (variable)

±0.01% of Reading or input sampling time, whichever is greater

1~10,000 times
*Execute infinite times with 10,000 settings

0 hours 00 minutes to 500 hours 00 minutes or 0 minutes 00 seconds to 500 minutes 00 seconds
*Continues ON when set to 0

DO4 points DO1~4 (relay contact) *Standard equipment

Can be set from 0.1 to 100.0 seconds (OFF at 0 seconds)

0~16
*No assignment when set to 0

Up to 1,024 segments
*However, the maximum number of segments per pattern is within 99 segments.
*Hold, step, fast forward/rewind functions included

1~9,999 times
*1 setting disables segment repeat

0 hours 0 minutes to 500 hours 00 minutes or 0 minutes 0 seconds to 500 minutes 00 seconds

0.1 seconds (switchable to 0.05 seconds/0.25 seconds)

0.001~9.999

±input range span

No input

Program controller (temperature controller) PF900-Part Number-PF900-MNN-3*4NDN

PF900-MNN-3*4NDN

Available upon quote

AC/DC24V

Arithmetic formula: PV = √ (input value) × PV ratio + PV bias
Low level cutoff: 0.00~25.00% of span

6 digital inputs DI 1~6

-10~+55℃

Approximately 0.01% of span (resistance temperature detector input) *within a maximum of 10Ω per wire

AC24V specification: 8.5A or less
DC24V specification: 6.0A or less

AC24V specification: 8.5VA<6.2VA>
DC24V specification: 230mA<173mA>

None

0~ (128÷maximum number of segments)
*No assignment when set to 0
*Maximum number of segments: Number of segments in the setting of number of patterns x number of segments

No output 3

No output 2

Relay contact output

No effect on power outages of 20ms or less

0.2μV/Ω (thermocouple input)

0~99 patterns *No pattern link when set to 0

Data backup using non-volatile memory (FRAM)
Data storage retention period: Approximately 10 years
Number of rewrites: Approximately 10 billion times
(However, the storage period of the product varies depending on the storage environment and usage environment)

Up to 99 patterns (variable)

±0.01% of Reading or input sampling time, whichever is greater

1~10,000 times
*Execute infinite times with 10,000 settings

0 hours 00 minutes to 500 hours 00 minutes or 0 minutes 00 seconds to 500 minutes 00 seconds
*Continues ON when set to 0

DO4 points DO1~4 (relay contact) *Standard equipment

Can be set from 0.1 to 100.0 seconds (OFF at 0 seconds)

0~16
*No assignment when set to 0

Up to 1,024 segments
*However, the maximum number of segments per pattern is within 99 segments.
*Hold, step, fast forward/rewind functions included

1~9,999 times
*1 setting disables segment repeat

0 hours 0 minutes to 500 hours 00 minutes or 0 minutes 0 seconds to 500 minutes 00 seconds

0.1 seconds (switchable to 0.05 seconds/0.25 seconds)

0.001~9.999

±input range span

No input

Program controller (temperature controller) PF900-Part Number-PF900-MNN-3*4TNN

PF900-MNN-3*4TNN

Available upon quote

AC/DC24V

Arithmetic formula: PV = √ (input value) × PV ratio + PV bias
Low level cutoff: 0.00~25.00% of span

None

-10~+55℃

Approximately 0.01% of span (resistance temperature detector input) *within a maximum of 10Ω per wire

AC24V specification: 8.5A or less
DC24V specification: 6.0A or less

AC24V specification: 8.5VA<6.2VA>
DC24V specification: 230mA<173mA>

None

0~ (128÷maximum number of segments)
*No assignment when set to 0
*Maximum number of segments: Number of segments in the setting of number of patterns x number of segments

No output 3

No output 2

Relay contact output

No effect on power outages of 20ms or less

0.2μV/Ω (thermocouple input)

0~99 patterns *No pattern link when set to 0

Data backup using non-volatile memory (FRAM)
Data storage retention period: Approximately 10 years
Number of rewrites: Approximately 10 billion times
(However, the storage period of the product varies depending on the storage environment and usage environment)

Up to 99 patterns (variable)

±0.01% of Reading or input sampling time, whichever is greater

1~10,000 times
*Execute infinite times with 10,000 settings

0 hours 00 minutes to 500 hours 00 minutes or 0 minutes 00 seconds to 500 minutes 00 seconds
*Continues ON when set to 0

DO4 points DO1~4 (relay contact) *Standard equipment

Can be set from 0.1 to 100.0 seconds (OFF at 0 seconds)

0~16
*No assignment when set to 0

Up to 1,024 segments
*However, the maximum number of segments per pattern is within 99 segments.
*Hold, step, fast forward/rewind functions included

1~9,999 times
*1 setting disables segment repeat

0 hours 0 minutes to 500 hours 00 minutes or 0 minutes 0 seconds to 500 minutes 00 seconds

0.1 seconds (switchable to 0.05 seconds/0.25 seconds)

0.001~9.999

±input range span

2 CT input points

Program controller (temperature controller) PF900-Part Number-PF900-MNN-3*4T1N

PF900-MNN-3*4T1N

Available upon quote

AC/DC24V

Arithmetic formula: PV = √ (input value) × PV ratio + PV bias
Low level cutoff: 0.00~25.00% of span

Communication 1: RS-232C Communication 2: None - 6 digital inputs DI 1~6

-10~+55℃

Approximately 0.01% of span (resistance temperature detector input) *within a maximum of 10Ω per wire

AC24V specification: 8.5A or less
DC24V specification: 6.0A or less

AC24V specification: 8.5VA<6.2VA>
DC24V specification: 230mA<173mA>

None

0~ (128÷maximum number of segments)
*No assignment when set to 0
*Maximum number of segments: Number of segments in the setting of number of patterns x number of segments

No output 3

No output 2

Relay contact output

No effect on power outages of 20ms or less

0.2μV/Ω (thermocouple input)

0~99 patterns *No pattern link when set to 0

Data backup using non-volatile memory (FRAM)
Data storage retention period: Approximately 10 years
Number of rewrites: Approximately 10 billion times
(However, the storage period of the product varies depending on the storage environment and usage environment)

Up to 99 patterns (variable)

±0.01% of Reading or input sampling time, whichever is greater

1~10,000 times
*Execute infinite times with 10,000 settings

0 hours 00 minutes to 500 hours 00 minutes or 0 minutes 00 seconds to 500 minutes 00 seconds
*Continues ON when set to 0

DO4 points DO1~4 (relay contact) *Standard equipment

Can be set from 0.1 to 100.0 seconds (OFF at 0 seconds)

0~16
*No assignment when set to 0

Up to 1,024 segments
*However, the maximum number of segments per pattern is within 99 segments.
*Hold, step, fast forward/rewind functions included

1~9,999 times
*1 setting disables segment repeat

0 hours 0 minutes to 500 hours 00 minutes or 0 minutes 0 seconds to 500 minutes 00 seconds

0.1 seconds (switchable to 0.05 seconds/0.25 seconds)

0.001~9.999

±input range span

2 CT input points

Click on the part number for more information about each product

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Temperature Controllers Products

Other products of RKC INSTRUMENT

Reviews shown here are reviews of companies.


View more products of RKC INSTRUMENT

About Company Handling This Product

Response Rate

100.0%


Response Time

15.5hrs

Company Overview

RKC Instrument has been continually growing for over half a century and strives to be a solution provider of m...

See More

  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree