Digital indicating controller (temperature controller) CB series-CB100FK01-M*NN-NN/N
Digital indicating controller (temperature controller) CB series-RKC INSTRUMENT

Digital indicating controller (temperature controller) CB series
RKC INSTRUMENT


About This Product

■Equipped with control status discrimination type self-tuning function - Automatically tunes PID constants when it is determined that control is disrupted. -Auto tuning function is also available. ■ Close-contact instrumentation possible We have realized close-contact instrumentation that can effectively utilize the area of ​​the control panel and operation panel. ■Communication function (RS-485) can be installed (optional) - Communication function (RS-485) allows multi-drop connection of up to 31 units. - RKC standard and MODBUS protocol can be selected. ■Dust-proof and drip-proof structure (optional) The dust-proof and drip-proof structure (optional) is compatible with harsh usage environments and is equivalent to IP66 (65), allowing it to be used not only in dust but also in water. *Front direction when installing the panel. CB100: IP66 equivalent, other models: IP65 equivalent ■RUN/STOP function Control can be started/stopped (RUN/STOP) by pressing the R/S key on the front panel for about 1 second. ■Heating/cooling PID control By performing heating/cooling PID control, it is possible to handle control objects that generate self-heating, contributing to energy savings. In addition, overlap/dead bands can be set depending on the strength of the cooling gain and the size of the time constant. ■Temperature alarm Depending on your application, you can select up to two points from among the following: upper limit deviation alarm, lower limit deviation alarm, upper limit deviation alarm, within-range deviation alarm, upper limit input value alarm, lower limit input value alarm, upper limit set value alarm, and lower limit set value alarm. Additionally, an alarm standby action can be added to the deviation alarm and input value alarm to cancel the alarm state when the power is turned on. Please specify the power supply voltage to be used separately. AC100~240V or AC24V or DC24V *Other product numbers are available.

  • Product

    Digital indicating controller (temperature controller) CB series

Share this product


190+ people viewing

Last viewed: 15 hours ago


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

10 Models of Digital indicating controller (temperature controller) CB series

Items marked with have different values depending on the model number.

Click on the part number for more information about each product

Product Image Part Number Price (excluding tax) 1st alarm 2nd alarm Applicable standards Body color Communication function Control operation Effect of external resistance Effect of input lead resistance Effects of power outage Input/range Insulation resistance Memory backup Number of input points Operation during input short circuit Operation when input wire is disconnected Other conditions Output 1 (OUT1) Control output Output 2 (OUT2) Control output PV bias When temperature input PV bias When voltage/current input Permissible ambient humidity Permissible ambient temperature Sampling period Usage atmosphere Waterproof and dustproof structure Weight Withstand voltage
Digital indicating controller (temperature controller) CB series-Part Number-CB100FK01-M*NN-NN/N

CB100FK01-M*NN-NN/N

Available upon quote None None CE marking compliant, UL, cUL certified product
Compliant with RoHS Directive
*The triac drive trigger output does not comply with or correspond to CE marking, UL, or cUL.
White tone None PID operation (reverse operation) Approx. 0.2μV/Ω (thermocouple input) Approximately 0.01 [%/Ω] of reading value (RTD input) *Maximum within 10Ω per wire Power outages of 20msec or less will not affect operation. *Any further power outage will result in the initial state. Thermocouple: K, 0~200℃ Between measurement terminal and ground DC 500V 20MΩ or more
Between power terminal and ground DC 500V 20MΩ or more
Data backup using non-volatile memory (approximately 10 years) 1 point Downscale (RTD input) Upscale No external noise and no direct vibration or impact.
A place that is not exposed to direct sunlight.
Relay contact output None (for control action F or D) -1,999~+9,999℃ or -199.9~+999.9℃ -span~+span 45~85%RH 0~50℃ 0.5 seconds No corrosive or flammable gases, and no heavy dust.
No waterproof/dustproof structure Approximately 170g Between measurement terminal and ground: AC 1,000V for 1 minute
Between power terminal and ground: AC 1,500V for 1 minute
Digital indicating controller (temperature controller) CB series-Part Number-CB100FK01-M*NN-NN/A

CB100FK01-M*NN-NN/A

Available upon quote None None CE marking compliant, UL, cUL certified product
Compliant with RoHS Directive
*The triac drive trigger output does not comply with or correspond to CE marking, UL, or cUL.
Black tone None PID operation (reverse operation) Approx. 0.2μV/Ω (thermocouple input) Approximately 0.01 [%/Ω] of reading value (RTD input) *Maximum within 10Ω per wire Power outages of 20msec or less will not affect operation. *Any further power outage will result in the initial state. Thermocouple: K, 0~200℃ Between measurement terminal and ground DC 500V 20MΩ or more
Between power terminal and ground DC 500V 20MΩ or more
Data backup using non-volatile memory (approximately 10 years) 1 point Downscale (RTD input) Upscale No external noise and no direct vibration or impact.
A place that is not exposed to direct sunlight.
Relay contact output None (for control action F or D) -1,999~+9,999℃ or -199.9~+999.9℃ -span~+span 45~85%RH 0~50℃ 0.5 seconds No corrosive or flammable gases, and no heavy dust.
No waterproof/dustproof structure Approximately 170g Between measurement terminal and ground: AC 1,000V for 1 minute
Between power terminal and ground: AC 1,500V for 1 minute
Digital indicating controller (temperature controller) CB series-Part Number-CB100FK01-M*NN-N1/A

CB100FK01-M*NN-N1/A

Available upon quote None None CE marking compliant, UL, cUL certified product
Compliant with RoHS Directive
*The triac drive trigger output does not comply with or correspond to CE marking, UL, or cUL.
Black tone None PID operation (reverse operation) Approx. 0.2μV/Ω (thermocouple input) Approximately 0.01 [%/Ω] of reading value (RTD input) *Maximum within 10Ω per wire Power outages of 20msec or less will not affect operation. *Any further power outage will result in the initial state. Thermocouple: K, 0~200℃ Between measurement terminal and ground DC 500V 20MΩ or more
Between power terminal and ground DC 500V 20MΩ or more
Data backup using non-volatile memory (approximately 10 years) 1 point Downscale (RTD input) Upscale No external noise and no direct vibration or impact.
A place that is not exposed to direct sunlight.
Relay contact output None (for control action F or D) -1,999~+9,999℃ or -199.9~+999.9℃ -span~+span 45~85%RH 0~50℃ 0.5 seconds No corrosive or flammable gases, and no heavy dust.
Waterproof and dustproof structure available Approximately 170g Between measurement terminal and ground: AC 1,000V for 1 minute
Between power terminal and ground: AC 1,500V for 1 minute
Digital indicating controller (temperature controller) CB series-Part Number-CB100FK01-M*NN-5N/N

CB100FK01-M*NN-5N/N

Available upon quote None None CE marking compliant, UL, cUL certified product
Compliant with RoHS Directive
*The triac drive trigger output does not comply with or correspond to CE marking, UL, or cUL.
White tone RS-485 (RKC standard protocol) PID operation (reverse operation) Approx. 0.2μV/Ω (thermocouple input) Approximately 0.01 [%/Ω] of reading value (RTD input) *Maximum within 10Ω per wire Power outages of 20msec or less will not affect operation. *Any further power outage will result in the initial state. Thermocouple: K, 0~200℃ Between measurement terminal and ground DC 500V 20MΩ or more
Between power terminal and ground DC 500V 20MΩ or more
Data backup using non-volatile memory (approximately 10 years) 1 point Downscale (RTD input) Upscale No external noise and no direct vibration or impact.
A place that is not exposed to direct sunlight.
Relay contact output None (for control action F or D) -1,999~+9,999℃ or -199.9~+999.9℃ -span~+span 45~85%RH 0~50℃ 0.5 seconds No corrosive or flammable gases, and no heavy dust.
No waterproof/dustproof structure Approximately 170g Between measurement terminal and ground: AC 1,000V for 1 minute
Between power terminal and ground: AC 1,500V for 1 minute
Digital indicating controller (temperature controller) CB series-Part Number-CB100FK01-M*NN-5N/A

CB100FK01-M*NN-5N/A

Available upon quote None None CE marking compliant, UL, cUL certified product
Compliant with RoHS Directive
*The triac drive trigger output does not comply with or correspond to CE marking, UL, or cUL.
Black tone RS-485 (RKC standard protocol) PID operation (reverse operation) Approx. 0.2μV/Ω (thermocouple input) Approximately 0.01 [%/Ω] of reading value (RTD input) *Maximum within 10Ω per wire Power outages of 20msec or less will not affect operation. *Any further power outage will result in the initial state. Thermocouple: K, 0~200℃ Between measurement terminal and ground DC 500V 20MΩ or more
Between power terminal and ground DC 500V 20MΩ or more
Data backup using non-volatile memory (approximately 10 years) 1 point Downscale (RTD input) Upscale No external noise and no direct vibration or impact.
A place that is not exposed to direct sunlight.
Relay contact output None (for control action F or D) -1,999~+9,999℃ or -199.9~+999.9℃ -span~+span 45~85%RH 0~50℃ 0.5 seconds No corrosive or flammable gases, and no heavy dust.
No waterproof/dustproof structure Approximately 170g Between measurement terminal and ground: AC 1,000V for 1 minute
Between power terminal and ground: AC 1,500V for 1 minute
Digital indicating controller (temperature controller) CB series-Part Number-CB100FK01-M*NN-51/A

CB100FK01-M*NN-51/A

Available upon quote None None CE marking compliant, UL, cUL certified product
Compliant with RoHS Directive
*The triac drive trigger output does not comply with or correspond to CE marking, UL, or cUL.
Black tone RS-485 (RKC standard protocol) PID operation (reverse operation) Approx. 0.2μV/Ω (thermocouple input) Approximately 0.01 [%/Ω] of reading value (RTD input) *Maximum within 10Ω per wire Power outages of 20msec or less will not affect operation. *Any further power outage will result in the initial state. Thermocouple: K, 0~200℃ Between measurement terminal and ground DC 500V 20MΩ or more
Between power terminal and ground DC 500V 20MΩ or more
Data backup using non-volatile memory (approximately 10 years) 1 point Downscale (RTD input) Upscale No external noise and no direct vibration or impact.
A place that is not exposed to direct sunlight.
Relay contact output None (for control action F or D) -1,999~+9,999℃ or -199.9~+999.9℃ -span~+span 45~85%RH 0~50℃ 0.5 seconds No corrosive or flammable gases, and no heavy dust.
Waterproof and dustproof structure available Approximately 170g Between measurement terminal and ground: AC 1,000V for 1 minute
Between power terminal and ground: AC 1,500V for 1 minute
Digital indicating controller (temperature controller) CB series-Part Number-CB100FK01-M*NA-NN/N

CB100FK01-M*NA-NN/N

Available upon quote None Upper limit deviation alarm CE marking compliant, UL, cUL certified product
Compliant with RoHS Directive
*The triac drive trigger output does not comply with or correspond to CE marking, UL, or cUL.
White tone None PID operation (reverse operation) Approx. 0.2μV/Ω (thermocouple input) Approximately 0.01 [%/Ω] of reading value (RTD input) *Maximum within 10Ω per wire Power outages of 20msec or less will not affect operation. *Any further power outage will result in the initial state. Thermocouple: K, 0~200℃ Between measurement terminal and ground DC 500V 20MΩ or more
Between power terminal and ground DC 500V 20MΩ or more
Data backup using non-volatile memory (approximately 10 years) 1 point Downscale (RTD input) Upscale No external noise and no direct vibration or impact.
A place that is not exposed to direct sunlight.
Relay contact output None (for control action F or D) -1,999~+9,999℃ or -199.9~+999.9℃ -span~+span 45~85%RH 0~50℃ 0.5 seconds No corrosive or flammable gases, and no heavy dust.
No waterproof/dustproof structure Approximately 170g Between measurement terminal and ground: AC 1,000V for 1 minute
Between power terminal and ground: AC 1,500V for 1 minute
Digital indicating controller (temperature controller) CB series-Part Number-CB100FK01-M*NA-NN/A

CB100FK01-M*NA-NN/A

Available upon quote None Upper limit deviation alarm CE marking compliant, UL, cUL certified product
Compliant with RoHS Directive
*The triac drive trigger output does not comply with or correspond to CE marking, UL, or cUL.
Black tone None PID operation (reverse operation) Approx. 0.2μV/Ω (thermocouple input) Approximately 0.01 [%/Ω] of reading value (RTD input) *Maximum within 10Ω per wire Power outages of 20msec or less will not affect operation. *Any further power outage will result in the initial state. Thermocouple: K, 0~200℃ Between measurement terminal and ground DC 500V 20MΩ or more
Between power terminal and ground DC 500V 20MΩ or more
Data backup using non-volatile memory (approximately 10 years) 1 point Downscale (RTD input) Upscale No external noise and no direct vibration or impact.
A place that is not exposed to direct sunlight.
Relay contact output None (for control action F or D) -1,999~+9,999℃ or -199.9~+999.9℃ -span~+span 45~85%RH 0~50℃ 0.5 seconds No corrosive or flammable gases, and no heavy dust.
No waterproof/dustproof structure Approximately 170g Between measurement terminal and ground: AC 1,000V for 1 minute
Between power terminal and ground: AC 1,500V for 1 minute
Digital indicating controller (temperature controller) CB series-Part Number-CB100FK01-M*NA-N1/A

CB100FK01-M*NA-N1/A

Available upon quote None Upper limit deviation alarm CE marking compliant, UL, cUL certified product
Compliant with RoHS Directive
*The triac drive trigger output does not comply with or correspond to CE marking, UL, or cUL.
Black tone None PID operation (reverse operation) Approx. 0.2μV/Ω (thermocouple input) Approximately 0.01 [%/Ω] of reading value (RTD input) *Maximum within 10Ω per wire Power outages of 20msec or less will not affect operation. *Any further power outage will result in the initial state. Thermocouple: K, 0~200℃ Between measurement terminal and ground DC 500V 20MΩ or more
Between power terminal and ground DC 500V 20MΩ or more
Data backup using non-volatile memory (approximately 10 years) 1 point Downscale (RTD input) Upscale No external noise and no direct vibration or impact.
A place that is not exposed to direct sunlight.
Relay contact output None (for control action F or D) -1,999~+9,999℃ or -199.9~+999.9℃ -span~+span 45~85%RH 0~50℃ 0.5 seconds No corrosive or flammable gases, and no heavy dust.
Waterproof and dustproof structure available Approximately 170g Between measurement terminal and ground: AC 1,000V for 1 minute
Between power terminal and ground: AC 1,500V for 1 minute
Digital indicating controller (temperature controller) CB series-Part Number-CB100FK01-M*NA-5N/N

CB100FK01-M*NA-5N/N

Available upon quote None Upper limit deviation alarm CE marking compliant, UL, cUL certified product
Compliant with RoHS Directive
*The triac drive trigger output does not comply with or correspond to CE marking, UL, or cUL.
White tone RS-485 (RKC standard protocol) PID operation (reverse operation) Approx. 0.2μV/Ω (thermocouple input) Approximately 0.01 [%/Ω] of reading value (RTD input) *Maximum within 10Ω per wire Power outages of 20msec or less will not affect operation. *Any further power outage will result in the initial state. Thermocouple: K, 0~200℃ Between measurement terminal and ground DC 500V 20MΩ or more
Between power terminal and ground DC 500V 20MΩ or more
Data backup using non-volatile memory (approximately 10 years) 1 point Downscale (RTD input) Upscale No external noise and no direct vibration or impact.
A place that is not exposed to direct sunlight.
Relay contact output None (for control action F or D) -1,999~+9,999℃ or -199.9~+999.9℃ -span~+span 45~85%RH 0~50℃ 0.5 seconds No corrosive or flammable gases, and no heavy dust.
No waterproof/dustproof structure Approximately 170g Between measurement terminal and ground: AC 1,000V for 1 minute
Between power terminal and ground: AC 1,500V for 1 minute

Click on the part number for more information about each product