All Categories

History

Lightning recorder-OLR-31C
Lightning recorder-Otowa Electric Industry Co., Ltd.

About This Product

■Features

1. Record and display the level of surge current that has entered the grounding wire, etc. and the time it was detected. Useful for verifying the effectiveness and maintaining SPD (surge arrester). 2.Data is recorded on SD memory card Since it is recorded as text data, it can be displayed on a computer without using special software. 3. Outputs contact when detecting surge current or SPD deterioration (A contact for 1 second) 4. Compatible with RoHS regulated substances (OLR-31P only)

  • Product

    Lightning recorder

Share this product


60+ people viewing

Last viewed: 5 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

2 Models of Lightning recorder

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Power supply Adaptation Mass Number of records Recording medium Record Maximum allowable current Contact output (A contact) Installation Operating polarity Usage environment Operating temperature range CT
Lightning recorder-Part Number-OLR-31C

OLR-31C

Available upon quote

2 AAA alkaline batteries (continuous use period: approximately 2 years)

Grounding of SPD for solar system power supply (Class I, Class II, Class III), SPD for power supply (Class I, Class II, Class III), SPD for control power circuit, SPD for signal line, SPD for telephone line, etc. line

Main body: Approx. 450g
CT section: approx. 100g

Up to 999 items

SD memory card 2GB (included)

・Surge current level (8/20μs) 100A, 500A, 1,000A and its time
・SPD deteriorated contact operation (when connected to SPD) and its time

25kA (8/20μs and 10/350μs)

During surge current detection and SPD degraded contact operation

DIN rail

Positive/negative (but not determined)

Indoor use

During measurement: 0℃~+50℃ (no condensation)
Display: -5℃~+50℃ (No condensation)

Clamp type CT (inner diameter: φ32)

Lightning recorder-Part Number-OLR-31P

OLR-31P

Available upon quote

2 AAA alkaline batteries (continuous use period: approximately 2 years)

Grounding of SPD for solar system power supply (Class I, Class II, Class III), SPD for power supply (Class I, Class II, Class III), SPD for control power circuit, SPD for signal line, SPD for telephone line, etc. line

Main body: Approx. 450g
CT section: approx. 30g

Up to 999 items

SD memory card 2GB (included)

・Surge current level (8/20μs) 100A, 500A, 1,000A and its time
・SPD deteriorated contact operation (when connected to SPD) and its time

25kA (8/20μs and 10/350μs)

During surge current detection and SPD degraded contact operation

DIN rail

Positive/negative (but not determined)

Indoor use

During measurement: 0℃~+50℃ (no condensation)
Display: -5℃~+50℃ (No condensation)

Through-type CT (inner diameter: φ19)

Click on the part number for more information about each product

Other products of Otowa Electric Industry Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Otowa Electric Industry Co., Ltd.

About Company Handling This Product

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2025 Metoree