Instantaneous voltage drop compensator (medium capacity) VB series-VB21BC30D01A
Instantaneous voltage drop compensator (medium capacity) VB series-Otowa Electric Industry Co., Ltd.

Instantaneous voltage drop compensator (medium capacity) VB series
Otowa Electric Industry Co., Ltd.


About This Product

■Features

1, Realization of miniaturization By adopting a transformerless system and rational design, it can be significantly reduced in size and weight. A bypass circuit is included as standard for maintenance. 2.Improved overcurrent capability A static switch with high overcurrent capability is used as the direct feed switch, achieving an overcurrent capability of 150% of the rated current for 1 minute and 600% of the rated current for 1 cycle. Even in the unlikely event that a device failure occurs, the direct power switch will remain switched on (on) and continue transmitting power to the load. 3. Uninterrupted switching For example, when a voltage drop occurs on the power supply side and lasts for 230ms, the load side maintains a constant voltage. Additionally, there is almost no output voltage fluctuation immediately after an instantaneous voltage sag occurs, allowing a smooth transition to compensation operation. Therefore, it can be used with confidence in high-tech equipment. 4.Supports instantaneous interruptions During compensation, the switch is turned off and the bidirectional converter supplies the full voltage to the load. Since this is a parallel method, even if the power supply side is momentarily interrupted (open), it can be compensated for (not possible with a series method). In the standard specifications, compensation can be made for approximately 1 second at 100% load factor, approximately 3 seconds at 70% load rate, and approximately 5 seconds at 50% load factor regardless of the voltage drop rate. 5. Compatible with regenerative loads If regenerated power is generated from the load side during instantaneous sag compensation, compensation can be continued by charging the regenerated power into the capacitor. 6. Reduced running costs Since there is no need to replace the battery for about 10 years and it is maintenance free, running costs can be significantly reduced compared to UPS. There are other product numbers as well.

  • Product

    Instantaneous voltage drop compensator (medium capacity) VB series

Share this product


270+ people viewing


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

10 Models of Instantaneous voltage drop compensator (medium capacity) VB series

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Atmosphere Overcurrent capacity during commercial operation Load power factor range Allowable input voltage range Momentary sag compensation time Repeated momentary sag withstand capacity Momentary sag switching time Vibration/shock Rated current Rated load power factor Rated capacity Rated frequency during compensation operation Rated frequency during commercial operation Rated frequency Rated output voltage during compensation operation Rated output voltage During commercial operation Rated input voltage External dimensions: W x H x D Ambient humidity Ambient temperature Efficiency Cooling method Input capacity (including charging capacity) Storage ambient temperature Place of use AC output phase number AC input phase number
Instantaneous voltage drop compensator (medium capacity) VB series-Part Number-VB21BC30D01A

VB21BC30D01A

Available upon quote

A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes.

150% of rated current (1 minute), 600% (1 cycle)

Delay 0.7~1.0

185V~240V

1 second (at rated load)

0.2 second voltage drop 5 times in a row Compensable

No interruption

Where vibrations and shocks are not transmitted

82A

Delay 0.8

30kVA

AC input frequency ±1%

Depends on commercial input frequency

50/60Hz±5%

Commercial input voltage ±5%

Depends on utility input voltage

210V (200V, 220V)

1,000×2,050×750mm

30~90%RH (no condensation)

0℃~+40℃ (However, the daily average is below 35℃)

98% (at rated output)

Forced air cooling

36kVA

-20℃~+60℃

Indoor

Three phase three wire

Three phase three wire

Instantaneous voltage drop compensator (medium capacity) VB series-Part Number-VB21BC50D01A

VB21BC50D01A

Available upon quote

A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes.

150% of rated current (1 minute), 600% (1 cycle)

Delay 0.7~1.0

185V~240V

1 second (at rated load)

0.2 second voltage drop 5 times in a row Compensable

No interruption

Where vibrations and shocks are not transmitted

137A

Delay 0.8

50kVA

AC input frequency ±1%

Depends on commercial input frequency

50/60Hz±5%

Commercial input voltage ±5%

Depends on utility input voltage

210V (200V, 220V)

1,000×2,050×750mm

30~90%RH (no condensation)

0℃~+40℃ (However, the daily average is below 35℃)

98% (at rated output)

Forced air cooling

60kVA

-20℃~+60℃

Indoor

Three phase three wire

Three phase three wire

Instantaneous voltage drop compensator (medium capacity) VB series-Part Number-VB21BC75D01A

VB21BC75D01A

Available upon quote

A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes.

150% of rated current (1 minute), 600% (1 cycle)

Delay 0.7~1.0

185V~240V

1 second (at rated load)

0.2 second voltage drop 5 times in a row Compensable

No interruption

Where vibrations and shocks are not transmitted

206A

Delay 0.8

75kVA

AC input frequency ±1%

Depends on commercial input frequency

50/60Hz±5%

Commercial input voltage ±5%

Depends on utility input voltage

210V (200V, 220V)

1,000×2,050×750mm

30~90%RH (no condensation)

0℃~+40℃ (However, the daily average is below 35℃)

98% (at rated output)

Forced air cooling

90kVA

-20℃~+60℃

Indoor

Three phase three wire

Three phase three wire

Instantaneous voltage drop compensator (medium capacity) VB series-Part Number-VB21BC10E01A

VB21BC10E01A

Available upon quote

A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes.

150% of rated current (1 minute), 600% (1 cycle)

Delay 0.7~1.0

185V~240V

1 second (at rated load)

0.2 second voltage drop 5 times in a row Compensable

No interruption

Where vibrations and shocks are not transmitted

275A

Delay 0.8

100kVA

AC input frequency ±1%

Depends on commercial input frequency

50/60Hz±5%

Commercial input voltage ±5%

Depends on utility input voltage

210V (200V, 220V)

1,000×2,050×750mm

30~90%RH (no condensation)

0℃~+40℃ (However, the daily average is below 35℃)

99% (at rated output)

Forced air cooling

120kVA

-20℃~+60℃

Indoor

Three phase three wire

Three phase three wire

Instantaneous voltage drop compensator (medium capacity) VB series-Part Number-VB21BC15E01A

VB21BC15E01A

Available upon quote

A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes.

150% of rated current (1 minute), 600% (1 cycle)

Delay 0.7~1.0

185V~240V

1 second (at rated load)

0.2 second voltage drop 5 times in a row Compensable

No interruption

Where vibrations and shocks are not transmitted

412A

Delay 0.8

150kVA

AC input frequency ±1%

Depends on commercial input frequency

50/60Hz±5%

Commercial input voltage ±5%

Depends on utility input voltage

210V (200V, 220V)

1,550×2,050×750mm

30~90%RH (no condensation)

0℃~+40℃ (However, the daily average is below 35℃)

99% (at rated output)

Forced air cooling

180kVA

-20℃~+60℃

Indoor

Three phase three wire

Three phase three wire

Instantaneous voltage drop compensator (medium capacity) VB series-Part Number-VB21BC20E01A

VB21BC20E01A

Available upon quote

A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes.

150% of rated current (1 minute), 600% (1 cycle)

Delay 0.7~1.0

185V~240V

1 second (at rated load)

0.2 second voltage drop 5 times in a row Compensable

No interruption

Where vibrations and shocks are not transmitted

550A

Delay 0.8

200kVA

AC input frequency ±1%

Depends on commercial input frequency

50/60Hz±5%

Commercial input voltage ±5%

Depends on utility input voltage

210V (200V, 220V)

1,550×2,050×750mm

30~90%RH (no condensation)

0℃~+40℃ (However, the daily average is below 35℃)

99% (at rated output)

Forced air cooling

240kVA

-20℃~+60℃

Indoor

Three phase three wire

Three phase three wire

Instantaneous voltage drop compensator (medium capacity) VB series-Part Number-VB42BC30D01A

VB42BC30D01A

Available upon quote

A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes.

150% of rated current (1 minute), 600% (1 cycle)

Delay 0.7~1.0

370V~480V

1 second (at rated load)

0.2 second voltage drop 5 times in a row Compensable

No interruption

Where vibrations and shocks are not transmitted

41A

Delay 0.8

30kVA

AC input frequency ±1%

Depends on commercial input frequency

50/60Hz±5%

Commercial input voltage ±5%

Depends on utility input voltage

420V (380V, 400V, 440V)

1,000×2,050×750mm

30~90%RH (no condensation)

0℃~+40℃ (However, the daily average is below 35℃)

98% (at rated output)

Forced air cooling

36kVA

-20℃~+60℃

Indoor

Three phase three wire

Three phase three wire

Instantaneous voltage drop compensator (medium capacity) VB series-Part Number-VB42BC50D01A

VB42BC50D01A

Available upon quote

A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes.

150% of rated current (1 minute), 600% (1 cycle)

Delay 0.7~1.0

370V~480V

1 second (at rated load)

0.2 second voltage drop 5 times in a row Compensable

No interruption

Where vibrations and shocks are not transmitted

69A

Delay 0.8

50kVA

AC input frequency ±1%

Depends on commercial input frequency

50/60Hz±5%

Commercial input voltage ±5%

Depends on utility input voltage

420V (380V, 400V, 440V)

1,000×2,050×750mm

30~90%RH (no condensation)

0℃~+40℃ (However, the daily average is below 35℃)

98% (at rated output)

Forced air cooling

60kVA

-20℃~+60℃

Indoor

Three phase three wire

Three phase three wire

Instantaneous voltage drop compensator (medium capacity) VB series-Part Number-VB42BC75D01A

VB42BC75D01A

Available upon quote

A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes.

150% of rated current (1 minute), 600% (1 cycle)

Delay 0.7~1.0

370V~480V

1 second (at rated load)

0.2 second voltage drop 5 times in a row Compensable

No interruption

Where vibrations and shocks are not transmitted

103A

Delay 0.8

75kVA

AC input frequency ±1%

Depends on commercial input frequency

50/60Hz±5%

Commercial input voltage ±5%

Depends on utility input voltage

420V (380V, 400V, 440V)

1,000×2,050×750mm

30~90%RH (no condensation)

0℃~+40℃ (However, the daily average is below 35℃)

98% (at rated output)

Forced air cooling

90kVA

-20℃~+60℃

Indoor

Three phase three wire

Three phase three wire

Instantaneous voltage drop compensator (medium capacity) VB series-Part Number-VB42BC10E01A

VB42BC10E01A

Available upon quote

A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes.

150% of rated current (1 minute), 600% (1 cycle)

Delay 0.7~1.0

370V~480V

1 second (at rated load)

0.2 second voltage drop 5 times in a row Compensable

No interruption

Where vibrations and shocks are not transmitted

137A

Delay 0.8

100kVA

AC input frequency ±1%

Depends on commercial input frequency

50/60Hz±5%

Commercial input voltage ±5%

Depends on utility input voltage

420V (380V, 400V, 440V)

1,000×2,050×750mm

30~90%RH (no condensation)

0℃~+40℃ (However, the daily average is below 35℃)

99% (at rated output)

Forced air cooling

120kVA

-20℃~+60℃

Indoor

Three phase three wire

Three phase three wire

Click on the part number for more information about each product

Other products of Otowa Electric Industry Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Otowa Electric Industry Co., Ltd.

About Company Handling This Product

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2025 Metoree