Instantaneous voltage drop compensator (small capacity) SB seriesHandling Company
Otowa Electric Industry Co., Ltd.Click on the part number for more information about each product
Image | Part Number | Price (excluding tax) | Atmosphere | Overcurrent capacity during commercial operation | Mass | Load power factor range | Allowable input voltage range | Momentary sag compensation time (at rated load) | Repeated momentary sag withstand capacity | Momentary sag switching time | Vibration/shock | Rated current | Rated load power factor | Rated capacity | Rated frequency during compensation operation | Rated frequency during commercial operation | Rated frequency | Rated output voltage during compensation operation | Rated output voltage During commercial operation | Rated input voltage | Ambient humidity | Ambient temperature | Efficiency | Cooling method | Input capacity (including charging capacity) | Storage ambient temperature | Place of use | AC output phase number | AC input phase number | Standard |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
YS10BC48C11A |
Available upon quote |
A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes. |
150% of rated current (1 minute), 600% (1 cycle) |
Approximately 52kg |
Delay 0.7~1.0 |
93V~120V |
1.0 seconds |
10 seconds interval 100% voltage drop 0.3 seconds 5 times in a row |
No interruption |
A place where vibrations and shocks are not transmitted |
48A |
Delay 0.8 |
4.8kVA |
AC input frequency ±1% |
Depends on commercial input frequency |
50/60Hz±5% |
Commercial input voltage ±5% |
Depends on utility input voltage |
100V |
30~90%RH (no condensation) |
0℃~+40℃ (annual average below 30℃) |
97% or more |
Natural cooling |
5.8kVA |
0℃~+60℃ |
Indoor |
Single phase 2 wire |
Single phase 2 wire |
JIS, NRTL certified (UL1012), CE marking compliant (LVD/EMC Directive) |
|
YS20BC72C11A |
Available upon quote |
A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes. |
150% of rated current (1 minute), 600% (1 cycle) |
Approximately 56kg |
Delay 0.7~1.0 |
186V~264V |
1.0 seconds |
10 seconds interval 100% voltage drop 0.3 seconds 5 times in a row |
No interruption |
A place where vibrations and shocks are not transmitted |
36A |
Delay 0.8 |
7.2kVA |
AC input frequency ±1% |
Depends on commercial input frequency |
50/60Hz±5% |
Commercial input voltage ±5% |
Depends on utility input voltage |
200V |
30~90%RH (no condensation) |
0℃~+40℃ (annual average below 30℃) |
97% or more |
Natural cooling |
8.6kVA |
0℃~+60℃ |
Indoor |
Single phase 2 wire |
Single phase 2 wire |
JIS, NRTL certified (UL1012), CE marking compliant (LVD/EMC Directive) |
|
YS20BC96C11A |
Available upon quote |
A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes. |
150% of rated current (1 minute), 600% (1 cycle) |
Approximately 61kg |
Delay 0.7~1.0 |
186V~264V |
1.0 seconds |
10 seconds interval 100% voltage drop 0.3 seconds 5 times in a row |
No interruption |
A place where vibrations and shocks are not transmitted |
48A |
Delay 0.8 |
9.6kVA |
AC input frequency ±1% |
Depends on commercial input frequency |
50/60Hz±5% |
Commercial input voltage ±5% |
Depends on utility input voltage |
200V |
30~90%RH (no condensation) |
0℃~+40℃ (annual average below 30℃) |
97% or more |
Natural cooling |
11.5kVA |
0℃~+60℃ |
Indoor |
Single phase 2 wire |
Single phase 2 wire |
JIS, NRTL certified (UL1012), CE marking compliant (LVD/EMC Directive) |
|
SB20BC75C01A |
Available upon quote |
A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes. |
150% of rated current (1 minute), 20 times (1 cycle) |
Approximately 40kg |
Delay 0.7~1.0 |
185V~240V |
1.0 seconds (at 30% voltage drop) /0.3 seconds (at 100% voltage drop) |
10 seconds interval 100% voltage drop 0.3 seconds 5 times in a row |
No interruption |
A place where vibrations and shocks are not transmitted |
22A |
Delay 0.8 |
7.5kVA |
AC input frequency ±1% |
Depends on commercial input frequency |
50/60Hz±5% |
Commercial input voltage ±5% |
Depends on utility input voltage |
200V |
30~90%RH (no condensation) |
0℃~+40℃ (annual average below 30℃) |
98% or more |
Natural air cooling |
9kVA |
-20℃~+60℃ |
Indoor |
Three phase three wire |
Three phase three wire |
- | |
SB20BC10D01A |
Available upon quote |
A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes. |
150% of rated current (1 minute), 20 times (1 cycle) |
Approximately 70kg |
Delay 0.7~1.0 |
185V~240V |
1.0 seconds (at 30% voltage drop) /0.3 seconds (at 100% voltage drop) |
10 seconds interval 100% voltage drop 0.3 seconds 5 times in a row |
No interruption |
A place where vibrations and shocks are not transmitted |
29A |
Delay 0.8 |
10kVA |
AC input frequency ±1% |
Depends on commercial input frequency |
50/60Hz±5% |
Commercial input voltage ±5% |
Depends on utility input voltage |
200V |
30~90%RH (no condensation) |
0℃~+40℃ (annual average below 30℃) |
98% or more |
Natural air cooling |
12kVA |
-20℃~+60℃ |
Indoor |
Three phase three wire |
Three phase three wire |
- | |
SB20BC15D01A |
Available upon quote |
A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes. |
150% of rated current (1 minute), 20 times (1 cycle) |
Approximately 70kg |
Delay 0.7~1.0 |
185V~240V |
1.0 seconds (at 30% voltage drop) /0.3 seconds (at 100% voltage drop) |
10 seconds interval 100% voltage drop 0.3 seconds 5 times in a row |
No interruption |
A place where vibrations and shocks are not transmitted |
44A |
Delay 0.8 |
15kVA |
AC input frequency ±1% |
Depends on commercial input frequency |
50/60Hz±5% |
Commercial input voltage ±5% |
Depends on utility input voltage |
200V |
30~90%RH (no condensation) |
0℃~+40℃ (annual average below 30℃) |
98% or more |
Natural air cooling |
18kVA |
-20℃~+60℃ |
Indoor |
Three phase three wire |
Three phase three wire |
- | |
SB20BC20D01A |
Available upon quote |
A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes. |
150% of rated current (1 minute), 20 times (1 cycle) |
Approximately 115kg |
Delay 0.7~1.0 |
185V~240V |
1.0 seconds (at 30% voltage drop) /0.3 seconds (at 100% voltage drop) |
10 seconds interval 100% voltage drop 0.3 seconds 5 times in a row |
No interruption |
A place where vibrations and shocks are not transmitted |
58A |
Delay 0.8 |
20kVA |
AC input frequency ±1% |
Depends on commercial input frequency |
50/60Hz±5% |
Commercial input voltage ±5% |
Depends on utility input voltage |
200V |
30~90%RH (no condensation) |
0℃~+40℃ (annual average below 30℃) |
98% or more |
Natural air cooling |
24kVA |
-20℃~+60℃ |
Indoor |
Three phase three wire |
Three phase three wire |
- | |
SB20BC30D01A |
Available upon quote |
A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes. |
150% of rated current (1 minute), 20 times (1 cycle) |
Approximately 120kg |
Delay 0.7~1.0 |
185V~240V |
1.0 seconds (at 30% voltage drop) /0.3 seconds (at 100% voltage drop) |
10 seconds interval 100% voltage drop 0.3 seconds 5 times in a row |
No interruption |
A place where vibrations and shocks are not transmitted |
87A |
Delay 0.8 |
30kVA |
AC input frequency ±1% |
Depends on commercial input frequency |
50/60Hz±5% |
Commercial input voltage ±5% |
Depends on utility input voltage |
200V |
30~90%RH (no condensation) |
0℃~+40℃ (annual average below 30℃) |
98% or more |
Natural air cooling |
36kVA |
-20℃~+60℃ |
Indoor |
Three phase three wire |
Three phase three wire |
- | |
SB40BC30D01A |
Available upon quote |
A place free of dust (including conductive), smoke, corrosive gas (including disinfectants), flammable gas, steam, salt, and oil fumes. |
150% of rated current (1 minute), 20 times (1 cycle) |
Approximately 120kg |
Delay 0.7~1.0 |
370V~480V |
1.0 seconds (at 30% voltage drop) /0.3 seconds (at 100% voltage drop) |
10 seconds interval 100% voltage drop 0.3 seconds 5 times in a row |
No interruption |
A place where vibrations and shocks are not transmitted |
44A |
Delay 0.8 |
30kVA |
AC input frequency ±1% |
Depends on commercial input frequency |
50/60Hz±5% |
Commercial input voltage ±5% |
Depends on utility input voltage |
400V |
30~90%RH (no condensation) |
0℃~+40℃ (annual average below 30℃) |
98% or more |
Natural air cooling |
36kVA |
-20℃~+60℃ |
Indoor |
Three phase three wire |
Three phase three wire |
- |