Product
Uninterruptible power supply UPS medium large capacity UNIPARA mini HIVERTER-UP101esHandling Company
Kyushu Kiden Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | AC input Number of phases and wires | AC input frequency tolerance range | AC input input power factor | AC input rated frequency | AC input rated voltage | AC input voltage tolerance range | AC output Number of phases and wires | AC output rated capacity | AC output rated frequency | AC output rated load power factor | AC output rated voltage | AC output voltage adjustment range | Circuit method Bypass circuit configuration | Circuit method Power supply method | DC input Number of storage battery cells | DC input nominal voltage | DC input voltage tolerance range | Environmental conditions Ambient temperature | Environmental conditions Noise | Environmental conditions Relative humidity | Output performance External synchronization frequency range | Output performance Frequency accuracy (internal synchronization) | Output performance Output voltage accuracy | Output performance Overload capacity Bypass circuit | Output performance Overload capacity Inverter | Output performance Voltage transient fluctuation | Output performance Voltage transient fluctuation recovery time | Output performance Voltage unbalance ratio | Output performance Voltage waveform distortion rate | UPS main body standard paint color |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
HIVERTER-UP101es |
Available upon quote | Three phase three wire | Within ±5% | 95% or more | 50/60Hz | 200V, 210V, 220V |
Within ±10% Load factor 60% or more, less than 80%: -10% to -20% (can be operated for 10 minutes) Load factor less than 60%: -10% to -30% (can be operated for 10 minutes) |
Three phase three wire | 10~50kVA | 50/60Hz |
0.8 (lag) Variation range: 0.7 (delay) ~1.0 |
200V, 210V, 220V | Within -1~+5% |
Uninterrupted bypass circuit Built-in maintenance bypass circuit |
Constant inverter power supply system | 102~138 cells | 204V~276V | 182V~308V |
0℃~40℃ Recommended 25℃ |
65dB (A) or less Front 1m, height 1.5m |
15~90% (no condensation) | Within ±1.0% | Within ±0.01% | Within ±1.0% | 1,000%…1 cycle |
120%…1 minute 150%…3 seconds 180%…0.1 seconds |
Power outage/power restoration: within ±2.0% Load 0⇔100%: within ±5.0% |
Within 50ms | Within ±1.5% |
Linear load: within 2.5% Nonlinear load: within 5.0% |
JEM standard color (5Y7/1) |