All Categories

History

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)-RCUP1320LZ3T
Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)-Kyushu Kiden Co., Ltd.

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)
Kyushu Kiden Co., Ltd.

Kyushu Kiden Co., Ltd.'s Response Status

Response Rate

100.0%

Response Time

38.9hours


About This Product

■Summary

Water-cooled cooling screw (for low temperatures) / Equipped with a shell and tube condenser. By increasing the lower limit of cooling water outlet temperature from 22℃ to 17℃, we have been able to save energy throughout the year.

■Expansion of scope of use

By increasing the lower limit of cooling water outlet temperature from 22℃ to 17℃, we have been able to save energy throughout the year.

■Simplification of legal procedures such as high-pressure gas production notifications

There are no products eligible for permission application.

■Cycle configuration

The compressor is equipped with an A-type screw compressor that uses a cyclone oil separator, the brine cooler uses a plate heat exchanger, and the condenser uses a shell and tube heat exchanger.

■Control function

Equipped with control functions such as instantaneous power failure recovery control, power failure automatic recovery control (selectivity), and demand control function.

  • Product

    Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)

Share this product


880+ people viewing

Last viewed: 4 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

7 Models of Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)

Click on the part number for more information about each product

Image Part Number Price (excluding tax) High Pressure Gas Safety Act classification Power supply Power supply (on-site connection) Electrical characteristics Operating current (A) Electrical characteristics Power consumption (kW) Electrical characteristics Starting current (maximum ending) (A) Electrical characteristics Power factor (%) Driving switch Indicator light Equivalent horsepower (horsepower) Lubricating oil type Lubricating oil amount (L) Legal refrigeration capacity (tons) Capacity control range (%) Exterior (Munsell symbol) Dimensions Height (mm) Dimensions Width (mm) Dimensions Depth (mm) Compressor Motor rated output (number of poles) (kW) Compressor Lubricating oil temperature adjustment device Compressor model Condenser Refrigerant pressure gauge Refrigerant control device Refrigerant type Refrigerant amount (kg) Cooling capacity (kW) Cooling COP Usage range Brine side heat exchanger model
Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)-Part Number-RCUP1320LZ3T

RCUP1320LZ3T

Available upon quote

No notification required

Three phase 200V 50/60Hz

85.2/104

25.1/30.5

240/285

85/85

Push button switch/remote - with hand switch (remote control contacts will be prepared on site)

Green…Power supply
Red…driving
Orange...Alarm

40

Freor UX300

8

11.46/13.82

100~15・Stop (Brine outlet temperature: 5~-10℃ specifications), 100~50・Stop (Brine outlet temperature: -11~-25℃ specifications)

Light green (10G 5/2)

1,524

914

1,660

22 (2)

Oil heater (150W)

Semi-hermetic screw

Shell and tube type

Compound meter (high pressure x 1, low pressure x 1)

Electronic expansion valve + driver board

R407C

38

62/72

2.47/2.36

Brine outlet temperature -25℃~5℃

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)-Part Number-RCUP1700LZ3T

RCUP1700LZ3T

Available upon quote

No notification required

Three phase 200V 50/60Hz

100/121

29.5/36.0

240/285

85/86

Push button switch/remote - with hand switch (remote control contacts will be prepared on site)

Green…Power supply
Red…driving
Orange...Alarm

50

Freor UX300

8

14.02/16.90

100~15・Stop (Brine outlet temperature: 5~-10℃ specifications), 100~50・Stop (Brine outlet temperature: -11~-25℃ specifications)

Light green (10G 5/2)

1,524

914

1,660

30 (2)

Oil heater (150W)

Semi-hermetic screw

Shell and tube type

Compound meter (high pressure x 1, low pressure x 1)

Electronic expansion valve + driver board

R407C

38

77/89

2.61/2.47

Brine outlet temperature -25℃~5℃

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)-Part Number-RCUP2000LZ3T

RCUP2000LZ3T

Available upon quote

50Hz: No notification required 60Hz: Manufacturing notification

Three phase 200V 50/60Hz

123/146

36.2/44.5

311/340

85/88

Push button switch/remote - with hand switch (remote control contacts will be prepared on site)

Green…Power supply
Red…driving
Orange...Alarm

60

Freor UX300

6

17.30/20.84

100~15・Stop (Brine outlet temperature: 5~-10℃ specifications), 100~50・Stop (Brine outlet temperature: -11~-25℃ specifications)

Light green (10G 5/2)

1,524

914

1,660

37 (2)

Oil heater (150W)

Semi-hermetic screw

Shell and tube type

Compound meter (high pressure x 1, low pressure x 1)

Electronic expansion valve + driver board

R407C

34

92/106

2.54/2.38

Brine outlet temperature -25℃~5℃

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)-Part Number-RCUP2650LZ3T

RCUP2650LZ3T

Available upon quote

Manufacturing notification

Three phase 200V 50/60Hz

163/198

49.2/60.9

376/398

87/89

Push button switch/remote - with hand switch (remote control contacts will be prepared on site)

Green…Power supply
Red…driving
Orange...Alarm

80

Freor UX300

10

21.30/25.67

100~15・Stop (Brine outlet temperature: 5~-10℃ specifications), 100~50・Stop (Brine outlet temperature: -11~-25℃ specifications)

Light green (10G 5/2)

1,524

914

1,660

45 (2)

Oil heater (150W)

Semi-hermetic screw

Shell and tube type

Compound meter (high pressure x 1, low pressure x 1)

Electronic expansion valve + driver board

R407C

32

124/144

2.52/2.36

Brine outlet temperature -25℃~5℃

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)-Part Number-RCUP3350LZ3T

RCUP3350LZ3T

Available upon quote

Manufacturing notification

Three phase 200V 50/60Hz

204/250

60.0/74.6

376/398

85/86

Push button switch/remote - with hand switch (remote control contacts will be prepared on site)

Green…Power supply
Red…driving
Orange...Alarm

100

Freor UX300

8×2

28.04/33.80

100~15・Stop (Brine outlet temperature: 5~-10℃ specifications), 100~50・Stop (Brine outlet temperature: -11~-25℃ specifications)

Light green (10G 5/2)

1,672

1,685

1,660

30 (2) ×2

Oil heater (150W) ×2

Semi-hermetic screw

Shell and tube type

Compound meter (high pressure x 2, low pressure x 2)

Electronic expansion valve + driver board

R407C

38×2

152/173

2.53/2.32

Brine outlet temperature -25℃~5℃

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)-Part Number-RCUP4000LZ3T

RCUP4000LZ3T

Available upon quote

Manufacturing notification

Three phase 200V 50/60Hz

249/296

73.2/90.1

376/398

85/88

Push button switch/remote - with hand switch (remote control contacts will be prepared on site)

Green…Power supply
Red…driving
Orange...Alarm

120

Freor UX300

9×2

34.60/41.68

100~15・Stop (Brine outlet temperature: 5~-10℃ specifications), 100~50・Stop (Brine outlet temperature: -11~-25℃ specifications)

Light green (10G 5/2)

1,672

1,685

1,660

37 (2) ×2

Oil heater (150W) ×2

Semi-hermetic screw

Shell and tube type

Compound meter (high pressure x 2, low pressure x 2)

Electronic expansion valve + driver board

R407C

34×2

178/205

2.43/2.28

Brine outlet temperature -25℃~5℃

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/continuous control)-Part Number-RCUP5100LZ3T

RCUP5100LZ3T

Available upon quote

Manufacturing notification

Three phase 200V 50/60Hz

320/348

96.4/106

376/398

87/88

Push button switch/remote - with hand switch (remote control contacts will be prepared on site)

Green…Power supply
Red…driving
Orange...Alarm

150

Freor UX300

9×2

42.60/46.51

100~15・Stop (Brine outlet temperature: 5~-10℃ specifications), 100~50・Stop (Brine outlet temperature: -11~-25℃ specifications)

Light green (10G 5/2)

1,672

1,685

1,660

45 (2) ×2/45 (2) +37 (2)

Oil heater (150W) ×2

Semi-hermetic screw

Shell and tube type

Compound meter (high pressure x 2, low pressure x 2)

Electronic expansion valve + driver board

R407C

32×2

240/250

2.49/2.36

Brine outlet temperature -25℃~5℃

Plate type

Click on the part number for more information about each product

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Chiller Units Products

Other products of Kyushu Kiden Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Kyushu Kiden Co., Ltd.

About Company Handling This Product

Response Rate

100.0%


Response Time

38.9hrs


Company Review

5.0
  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree