Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)-RCUP90L2
Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)-Kyushu Kiden Co., Ltd.

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)
Kyushu Kiden Co., Ltd.

Kyushu Kiden Co., Ltd.'s Response Status

Response Rate

100.0%

Response Time

38.9hours


About This Product

■Using environmentally friendly refrigerants

We use HFC refrigerant R407C, which has zero ozone depletion coefficient.

■Enhanced control functions

By adopting an electronic circuit for the control circuit, functions such as operating pressure display, brine inlet/outlet temperature display, and individual alarm display function have been enhanced.

■Compressor rotation function <RCUP450/600/900L2>

The base operating machine of the compressor will be changed to equalize the operating time of each compressor.

■Momentary power failure recovery control

If a momentary power outage occurs, operation will automatically resume in the operating mode before the power outage after recovery.

■Can be switched to outlet temperature control

At the time of shipment, the brine inlet temperature control specification is specified. Even if brine outlet temperature control is required for factory production process cooling, it can be changed by switching on the main unit.

■[Brine temperature control]

You can select the return temperature difference (thermo ON/OFF difference) for temperature control from 2, 3, or 4 degrees Celsius.

  • Product

    Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)

Share this product


780+ people viewing

Last viewed: 59 minutes ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

7 Models of Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)

Click on the part number for more information about each product

Image Part Number Price (excluding tax) High Pressure Gas Safety Act classification Power supply Operation circuit power supply Power supply Power supply (on-site connection) Electrical characteristics Operating current (A) Electrical characteristics Power consumption (kW) Electrical characteristics Starting current (maximum ending) (A) Electrical characteristics Power factor (%) Piping connection port Condenser (inlet/outlet) Piping connection port Brine cooler (inlet/outlet) Driving switch Indicator light Equivalent horsepower (horsepower) Legal refrigeration capacity (tons) Capacity control range (%) Exterior (Munsell symbol) Dimensions Height (mm) Dimensions Width (mm) Dimensions Depth (mm) Compressor Motor rated output (number of poles) (kW) Compressor Lubricating oil temperature adjustment device Compressor model Condenser Refrigerant pressure gauge Refrigerant control device Refrigerant type Refrigerant amount (kg) Cooling capacity (kW) Cooling COP Protection device Brine side heat exchanger model
Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)-Part Number-RCUP90L2

RCUP90L2

Available upon quote

No notification required

Single phase 200V 50/60Hz

Three phase 200V 50/60Hz

8.4/8.4

2.1/2.5

71/64

72/86

Rc1

Rc1

Push-button switch/remote-hand switch included (remote control contacts to be prepared on-site/remote control optional)

Segment display

3

0.83/1.00

100・Stop

Natural gray (1.0Y 8.5/0.5) (excluding electrical box)

900

550

550

2.2 (2)

Oil heater (40W)

Scroll G303AH

Plate type

Not included (with connection port and segment display function)

External pressure equalization temperature type automatic expansion valve

R407C

0.7

4.1/4.8

1.95/1.92

High pressure cutoff device, low pressure cutoff device, power fuse (for compressor), discharge gas overheating prevention control function, antifreeze control function, operating circuit fuse, fusible plug (not included for RCUP90L2 and RCUP150L2)

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)-Part Number-RCUP150L2

RCUP150L2

Available upon quote

No notification required

Single phase 200V 50/60Hz

Three phase 200V 50/60Hz

14.4/14.4

3.6/4.3

144/130

72/86

Rc1

Rc1

Push-button switch/remote-hand switch included (remote control contacts to be prepared on-site/remote control optional)

Segment display

5

1.41/1.70

100・Stop

Natural gray (1.0Y 8.5/0.5) (excluding electrical box)

900

550

550

3.75 (2)

Oil heater (40W)

Scroll G500DH

Plate type

Not included (with connection port and segment display function)

External pressure equalization temperature type automatic expansion valve

R407C

1

7.6/8.7

2.11/2.02

High pressure cutoff device, low pressure cutoff device, power fuse (for compressor), discharge gas overheating prevention control function, antifreeze control function, operating circuit fuse, fusible plug (not included for RCUP90L2 and RCUP150L2)

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)-Part Number-RCUP224L2

RCUP224L2

Available upon quote

No notification required

Single phase 200V 50/60Hz

Three phase 200V 50/60Hz

21.7/21.5

5.4/6.4

229/208

72/86

Rc1 1/2

Rc1 1/2

Push-button switch/remote-hand switch included (remote control contacts to be prepared on-site/remote control optional)

Segment display

7.5

2.26/2.72

100・Stop

Natural gray (1.0Y 8.5/0.5) (excluding electrical box)

900

790

550

5.5 (2)

Oil heater (60W)

Scroll G750EH

Plate type

Not included (with connection port and segment display function)

External pressure equalization temperature type automatic expansion valve

R407C

2.2

11.8/13.7

2.19/2.14

High pressure cutoff device, low pressure cutoff device, power fuse (for compressor), discharge gas overheating prevention control function, antifreeze control function, operating circuit fuse, fusible plug (not included for RCUP90L2 and RCUP150L2)

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)-Part Number-RCUP300L2

RCUP300L2

Available upon quote

No notification required

Single phase 200V 50/60Hz

Three phase 200V 50/60Hz

26.9/26.5

6.7/7.9

252/227

72/86

Rc1 1/2

Rc1 1/2

Push-button switch/remote-hand switch included (remote control contacts to be prepared on-site/remote control optional)

Segment display

10

2.82/3.40

100・Stop

Natural gray (1.0Y 8.5/0.5) (excluding electrical box)

900

790

550

7.5 (2)

Oil heater (60W)

Scroll G1000EH

Plate type

Not included (with connection port and segment display function)

External pressure equalization temperature type automatic expansion valve

R407C

2.2

15.0/17.2

2.24/2.18

High pressure cutoff device, low pressure cutoff device, power fuse (for compressor), discharge gas overheating prevention control function, antifreeze control function, operating circuit fuse, fusible plug (not included for RCUP90L2 and RCUP150L2)

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)-Part Number-RCUP450L2

RCUP450L2

Available upon quote

No notification required

Single phase 200V 50/60Hz

Three phase 200V 50/60Hz

43.4/43.0

10.8/12.8

251/230

72/86

Rc2

Rc2

Push-button switch/remote-hand switch included (remote control contacts to be prepared on-site/remote control optional)

Segment display

15

4.52/5.44

100・50・Stop

Natural gray (1.0Y 8.5/0.5) (excluding electrical box)

900

1,070

950

5.5 (2) ×2

Oil heater (60W) ×2

Scroll G750EH

Plate type

Not included (with connection port and segment display function)

External pressure equalization temperature type automatic expansion valve

R407C

2.2×2

23.6/27.4

2.19/2.14

High pressure cutoff device, low pressure cutoff device, power fuse (for compressor), discharge gas overheating prevention control function, antifreeze control function, operating circuit fuse, fusible plug (not included for RCUP90L2 and RCUP150L2)

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)-Part Number-RCUP600L2

RCUP600L2

Available upon quote

No notification required

Single phase 200V 50/60Hz

Three phase 200V 50/60Hz

53.8/53.0

13.4/15.8

279/254

72/86

Rc2

Rc2

Push-button switch/remote-hand switch included (remote control contacts to be prepared on-site/remote control optional)

Segment display

20

5.64/6.80

100・50・Stop

Natural gray (1.0Y 8.5/0.5) (excluding electrical box)

900

1,070

950

7.5 (2) ×2

Oil heater (60W) ×2

Scroll G1000EH

Plate type

Not included (with connection port and segment display function)

External pressure equalization temperature type automatic expansion valve

R407C

2.2×2

30.0/34.4

2.24/2.18

High pressure cutoff device, low pressure cutoff device, power fuse (for compressor), discharge gas overheating prevention control function, antifreeze control function, operating circuit fuse, fusible plug (not included for RCUP90L2 and RCUP150L2)

Plate type

Chiller unit brine specification (water cooling) Water cooling only (for low temperature/constant speed)-Part Number-RCUP900L2

RCUP900L2

Available upon quote

No notification required

Single phase 200V 50/60Hz

Three phase 200V 50/60Hz

80.7/79.5

20.1/23.7

306/280

72/86

Rc2 1/2

Rc2 1/2

Push-button switch/remote-hand switch included (remote control contacts to be prepared on-site/remote control optional)

Segment display

30

8.46/10.20

100・66・33・Stop

Natural gray (1.0Y 8.5/0.5) (excluding electrical box)

900

1,070

1,500

7.5 (2) ×3

Oil case heater (60W) ×3

Scroll G1000EH

Plate type

Not included (with connection port and segment display function)

External pressure equalization temperature type automatic expansion valve

R407C

2.2×3

45.0/51.6

2.24/2.18

High pressure cutoff device, low pressure cutoff device, power fuse (for compressor), discharge gas overheating prevention control function, antifreeze control function, operating circuit fuse, fusible plug (not included for RCUP90L2 and RCUP150L2)

Plate type

Click on the part number for more information about each product

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Chiller Units Products

Other products of Kyushu Kiden Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Kyushu Kiden Co., Ltd.

About Company Handling This Product

Response Rate

100.0%


Response Time

38.9hrs


Company Review

5.0
  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree