All Categories

History

For clean rooms: Tempclean/air cooling ceiling cassette type/wall embedded type-EPI-GP28K1
For clean rooms: Tempclean/air cooling ceiling cassette type/wall embedded type-Kyushu Kiden Co., Ltd.

For clean rooms: Tempclean/air cooling ceiling cassette type/wall embedded type
Kyushu Kiden Co., Ltd.

Kyushu Kiden Co., Ltd.'s Response Status

Response Rate

100.0%

Response Time

40.0hours


About This Product

■Summary

Achieves a clean indoor environment and a comfortable space at the same time. Suitable for places that require high air cleanliness, such as hospitals and precision industries.

■Compatible with cleanliness ISO class 7

The HEPA filter has a collection efficiency (counting method) of 99.97% (0.3μm) or higher, and is compliant with cleanliness ISO class 7 (equivalent to former U.S. federal standard Fed.Std.209D class 10,000), so high cleanliness is required. Suitable for hospitals, food processing, precision equipment, and electronic equipment fields. (Ceiling cassette type, wall-embedded type, and direct outlet type HEPA filters are sold separately; wall-embedded type and duct outlet type are items prepared locally.)

■Improved performance of standard HEPA filter

Scan test products and SEK (red mark) antibacterial specifications are available for standard optional HEPA filters. A protective net has also been added to the secondary side of the filter to prevent scratches on the filter media. [Ceiling cassette type]

■Easy to adjust the height of the main body

A hanging bolt mounting structure (inside hanging method) is used inside the main unit, allowing height adjustment from inside the main unit without removing the decorative panel. [Ceiling cassette type direct suction/duct suction type]

■Improved maintainability

Comes with a replacement indicator lamp to notify you when the filter is clogged. [Ceiling cassette type/wall-mounted type (direct outlet type)] Floor-standing type with service side facing forward for easy maintenance. [Wall-embedded type]

■[Ceiling cassette type] Selectable installation types

The air conditioner body type is ``direct suction type'' and ``duct suction type''. Please select and use the optional "decorative panel". [Ceiling cassette type]

■Suitable for special specifications (products made to order)

It complies with the "GMP specifications" using the counting method (dust leakage test) based on the "Manufacturing Control and Quality Control Standards for Pharmaceuticals." [Ceiling cassette type]. We also accept orders for air conditioning for hospital operating rooms by combining a wall-embedded type (duct outlet type) with a connected fan filter unit.

■450mm thin

The height of the air conditioner body has been reduced to 450mm to save space. [Ceiling cassette type] Also, the wall-embedded type does not require a special machine room.

■Suitable for a wide range of installation conditions

Can be combined with outdoor units for stores, offices, or buildings. Compatible with a wide range of installation conditions.

  • Product

    For clean rooms: Tempclean/air cooling ceiling cassette type/wall embedded type

Share this product


820+ people viewing

Last viewed: 14 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

5 Models of For clean rooms: Tempclean/air cooling ceiling cassette type/wall embedded type

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Sound power level (dB (A) ) Piping size Liquid (mm) Piping size gas (mm) Blower motor output (kW) Mass (including HEPA filter) (kg) Power consumption Heating (kW) Power consumption Cooling (kW) External static pressure (Pa) Heating capacity standard (kW) Heating capacity Low temperature (kW) Capacity/model name (equivalent horsepower) Indoor air flow (H sudden-sudden-strong-weak) (m3/min) External dimensions (mm) Suction square duct flange Decorative panel mass (kg) Decorative panel external dimensions (mm) Decorative panel model Cooling capacity (kW) Main power supply Pre-filter HEPA filter collection efficiency HEPA filter model
For clean rooms: Tempclean/air cooling ceiling cassette type/wall embedded type-Part Number-EPI-GP28K1

EPI-GP28K1

Available upon quote

61-59-57.5-56

Φ6.35

Φ12.7

0.157

83

0.11

0.11

30

3.2

For low-temperature heating capacity, see the capacity of the combined outdoor unit.

28 type (1.0)

18-16.5-15-13

W850×D1,690×H450

PDF-28E

17

W910×D1,750×H30

P-GP28EPS

2.8

Single phase 200V

It is not included with the optional decorative panel, so please be sure to install it according to the local construction method.

Counting method 99.99% (0.3μm)

F-28HE1

For clean rooms: Tempclean/air cooling ceiling cassette type/wall embedded type-Part Number-EPI-GP45K1

EPI-GP45K1

Available upon quote

62-60-59-58

Φ6.35

Φ12.7

0.157

91

0.14

0.14

30

5

For low-temperature heating capacity, see the capacity of the combined outdoor unit.

45 type (1.8)

20-18.5-17-15

W1,000×D1,690×H450

PDF-56E

20

W1,060×D1,750×H30

P-GP56EPS

4.5

Single phase 200V

It is not included with the optional decorative panel, so please be sure to install it according to the local construction method.

Counting method 99.99% (0.3μm)

F-56HE1

For clean rooms: Tempclean/air cooling ceiling cassette type/wall embedded type-Part Number-EPI-GP56K1

EPI-GP56K1

Available upon quote

64-62-60-59

Φ6.35

Φ12.7

0.157

91

0.17

0.17

30

6.3

For low-temperature heating capacity, see the capacity of the combined outdoor unit.

56 type (2.3)

23.5-21.5-19-17

W1,000×D1,690×H450

PDF-56E

20

W1,060×D1,750×H30

P-GP56EPS

5.6

Single phase 200V

It is not included with the optional decorative panel, so please be sure to install it according to the local construction method.

Counting method 99.99% (0.3μm)

F-56HE1

For clean rooms: Tempclean/air cooling ceiling cassette type/wall embedded type-Part Number-EPI-GP80K1

EPI-GP80K1

Available upon quote

62-61-59-58

Φ9.52

Φ15.88

0.157

106

0.16

0.16

30

9

For low-temperature heating capacity, see the capacity of the combined outdoor unit.

80 type (3.0)

23.5-21.5-19-17

W1,300×D1,690×H450

PDF-112E

Twenty three

W1,360×D1,750×H30

P-GP112EPS

8

Single phase 200V

It is not included with the optional decorative panel, so please be sure to install it according to the local construction method.

Counting method 99.99% (0.3μm)

F-112HE1

For clean rooms: Tempclean/air cooling ceiling cassette type/wall embedded type-Part Number-EPI-GP112K1

EPI-GP112K1

Available upon quote

63.5-62-61-59

Φ9.52

Φ15.88

0.19

111

0.19

0.19

30

12.5

For low-temperature heating capacity, see the capacity of the combined outdoor unit.

112 type (4.0)

30-27.5-24-21

W1,300×D1,690×H450

PDF-112E

Twenty three

W1,360×D1,750×H30

P-GP112EPS

11.2

Single phase 200V

It is not included with the optional decorative panel, so please be sure to install it according to the local construction method.

Counting method 99.99% (0.3μm)

F-112HE1

Click on the part number for more information about each product

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Air Conditioners Products

Other products of Kyushu Kiden Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Kyushu Kiden Co., Ltd.

About Company Handling This Product

Response Rate

100.0%


Response Time

40.0hrs


Company Review

5.0
  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree