Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-RCID-GP40RGHJ6
Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Kyushu Kiden Co., Ltd.

Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions
Kyushu Kiden Co., Ltd.

Kyushu Kiden Co., Ltd.'s Response Status

Response Rate

100.0%

Response Time

29.5hours

Relatively Fast Response


About This Product

■Simple panel design that fits the ceiling

The design of the decorative panel is simple and stylish and compatible with the flat grill. When stopped, the louver acts as a shutter.

■Suitable for high ceiling installations

Even if installed on a high ceiling, you can simply change settings from the remote control. We provide comfortable air conditioning that suits each store or office.

■Control airflow with individual louver settings

Equipped with an individual louver setting function that allows you to adjust the angle of the two louvers separately. For example, you can set the settings to suit your needs, such as setting it to sideways if you want to reduce wind blowing, or swinging if you want to send the wind.

■Smart air conditioning with human sensor kit (optional)

It senses a person's activity level and automatically saves abilities according to the situation. (Corrects the set temperature, air volume, and wind direction.)

■Antibacterial processed high-performance filter (particle collection rate 0.7μm or more 90%) Option

The power of silver ions suppresses bacteria and viruses that adhere to the filter.

■Enzyme filter (optional)

What are the enzymes used in filters? Natural enzymes immobilized on filter fibers suppress the growth of attached microorganisms and reduce secondary contamination. Because it uses natural enzymes, it is extremely safe, and because the enzyme itself is not consumed, its effects can be maintained for a long time.

■In addition to the conventional anti-mold effect, the power of silver ions suppresses bacteria and viruses that adhere to the filter.

Long-life filters have no effect on capturing viruses. Also, viruses in the air that pass through the filter are not suppressed. This is the effect of the virus attached to the filter in the test space after 2 hours, and is not the test result in the actual space. In addition, viruses attached to the collected dust are suppressed only when they come into contact with the long-life filter.

■Comfortable performance

Blow-out air thermistor Prevents the blow-out air from becoming too cold during cooling.

■Construction response ability

・Equipped with high head DC drain up mechanism ・Simplified body height adjustment with corner pockets

■Maintainability

Antibacterial treatment of drain pan There are other model numbers as well.

  • Product

    Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions

Share this product


980+ people viewing

Last viewed: 19 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

10 Models of Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Power (V) Motor compressor output (kW) Operating noise (dB (A)) Outdoor cooling/heating Operating noise (dB (A)) Indoor Operating current (A) Max. Operating current (A) Rating standard Year-round energy consumption efficiency Blower output (kW) Mass (kg) Capacity (kW) Maximum heating low temperature Capacity (kW) Rated heating standard Capacity (kW) Rated cooling standard Power consumption (kW) Maximum heating low temperature Power consumption (kW) Rated heating standard Power consumption (kW) Rated cooling standard External wiring Minimum wire thickness (mm^2) External wiring Indoor/outdoor wiring (pcs) External wiring breaker capacity (A) Indoor air flow (m^3/min) (H-sudden-strong-weak) Sensible heat ratio during rated cooling Outer diameter dimensions (mm) (width x depth x height) Power factor (%) Rating standard Refrigerant piping Liquid pipe/Gas pipe φ (mm) Refrigerant piping maximum height difference (m) Refrigerant piping maximum length (m) The refrigerant type ( ) is the filling amount (kg) Drain piping Type
Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Part Number-RCID-GP40RGHJ6

RCID-GP40RGHJ6

Available upon quote

Single phase 200
50Hz/60Hz

0.55

65/67

51-49-47-46

12.8

Cooling: 4.2
Heating: 5.1

6.2

Indoor unit: 0.057×1
Outdoor unit: 0.05×1

Indoor unit: 25 (+7.5)
Outdoor unit: 41

4.4

4.0 (1.0~5.4)

3.6 (1.1~4.0)

1.43

0.91

0.787

Indoor: 2.0
Outdoor: 3.5

2+2

Indoor: -
Outdoor: 15

15-13-11.5-10

0.73

Indoor unit: 1,100×710×375 (345)
Outdoor unit: 799 (+99) ×300×629

Cooling: 94
Heating: 89

6.35/12.7 (indoor unit/outdoor unit)

30

50

R32 (1.3)

VP25

Cooling/heating single

Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Part Number-RCID-GP40RGH6

RCID-GP40RGH6

Available upon quote

Three phase 200
50Hz/60Hz

0.55

65/67

51-49-47-46

9.3

Cooling: 2.6
Heating: 3.0

6.2

Indoor unit: 0.057×1
Outdoor unit: 0.05×1

Indoor unit: 25 (+7.5)
Outdoor unit: 39

4.4

4.0 (1.0~5.4)

3.6 (1.1~4.0)

1.43

0.91

0.787

Indoor: 2.0
Outdoor: 2.0

2+2

Indoor: -
Outdoor: 15

15-13-11.5-10

0.73

Indoor unit: 1,100×710×375 (345)
Outdoor unit: 799 (+99) ×300×629

Cooling: 87
Heating: 88

6.35/12.7 (indoor unit/outdoor unit)

30

50

R32 (1.3)

VP25

Cooling/heating single

Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Part Number-RCID-GP45RGHJ6

RCID-GP45RGHJ6

Available upon quote

Single phase 200
50Hz/60Hz

0.65

65/67

51-49-47-46

12.8

Cooling: 4.8
Heating: 5.5

6.1

Indoor unit: 0.057×1
Outdoor unit: 0.05×1

Indoor unit: 25 (+7.5)
Outdoor unit: 41

4.5

4.5 (1.2~5.9)

4.0 (1.1~4.5)

1.54

1.05

0.896

Indoor: 2.0
Outdoor: 3.5

2+2

Indoor: -
Outdoor: 15

15-13-11.5-10

0.71

Indoor unit: 1,100×710×375 (345)
Outdoor unit: 799 (+99) ×300×629

Cooling: 93
Heating: 95

6.35/12.7 (indoor unit/outdoor unit)

30

50

R32 (1.3)

VP25

Cooling/heating single

Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Part Number-RCID-GP45RGH6

RCID-GP45RGH6

Available upon quote

Three phase 200
50Hz/60Hz

0.65

65/67

51-49-47-46

9.3

Cooling: 2.9
Heating: 3.4

6.1

Indoor unit: 0.057×1
Outdoor unit: 0.05×1

Indoor unit: 25 (+7.5)
Outdoor unit: 39

4.5

4.5 (1.2~5.9)

4.0 (1.1~4.5)

1.54

1.05

0.896

Indoor: 2.0
Outdoor: 2.0

2+2

Indoor: -
Outdoor: 15

15-13-11.5-10

0.71

Indoor unit: 1,100×710×375 (345)
Outdoor unit: 799 (+99) ×300×629

Cooling: 89
Heating: 89

6.35/12.7 (indoor unit/outdoor unit)

30

50

R32 (1.3)

VP25

Cooling/heating single

Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Part Number-RCID-GP50RGHJ6

RCID-GP50RGHJ6

Available upon quote

Single phase 200
50Hz/60Hz

0.75

65/67

52-51-49-47

12.9

Cooling: 5.7
Heating: 6.4

5.9

Indoor unit: 0.057×1
Outdoor unit: 0.05×1

Indoor unit: 25 (+7.5)
Outdoor unit: 41

4.8

5.0 (1.3~6.3)

4.5 (1.4~5.0)

1.83

1.23

1.08

Indoor: 2.0
Outdoor: 3.5

2+2

Indoor: -
Outdoor: 15

16.5-14.5-12.5-10.5

0.73

Indoor unit: 1,100×710×375 (345)
Outdoor unit: 799 (+99) ×300×629

Cooling: 95
Heating: 96

6.35/12.7 (indoor unit/outdoor unit)

30

50

R32 (1.3)

VP25

Cooling/heating single

Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Part Number-RCID-GP50RGH6

RCID-GP50RGH6

Available upon quote

Three phase 200
50Hz/60Hz

0.75

65/67

52-51-49-47

9.4

Cooling: 3.3
Heating: 3.7

5.9

Indoor unit: 0.057×1
Outdoor unit: 0.05×1

Indoor unit: 25 (+7.5)
Outdoor unit: 39

4.8

5.0 (1.3~6.3)

4.5 (1.4~5.0)

1.83

1.23

1.08

Indoor: 2.0
Outdoor: 2.0

2+2

Indoor: -
Outdoor: 15

16.5-14.5-12.5-10.5

0.73

Indoor unit: 1,100×710×375 (345)
Outdoor unit: 799 (+99) ×300×629

Cooling: 94
Heating: 96

6.35/12.7 (indoor unit/outdoor unit)

30

50

R32 (1.3)

VP25

Cooling/heating single

Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Part Number-RCID-GP56RGHJ6

RCID-GP56RGHJ6

Available upon quote

Single phase 200
50Hz/60Hz

0.9

65/67

52-51-49-47

12.9

Cooling: 6.2
Heating: 7.1

6.2

Indoor unit: 0.057×1
Outdoor unit: 0.05×1

Indoor unit: 25 (+7.5)
Outdoor unit: 41

5.7

5.6 (1.4~7.1)

5.0 (1.5~5.6)

2.36

1.36

1.2

Indoor: 2.0
Outdoor: 3.5

2+2

Indoor: -
Outdoor: 15

16.5-14.5-12.5-10.5

0.72

Indoor unit: 1,100×710×375 (345)
Outdoor unit: 799 (+99) ×300×629

Cooling: 97
Heating: 96

6.35/12.7 (indoor unit/outdoor unit)

30

50

R32 (1.3)

VP25

Cooling/heating single

Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Part Number-RCID-GP56RGH6

RCID-GP56RGH6

Available upon quote

Three phase 200
50Hz/60Hz

0.9

65/67

52-51-49-47

9.4

Cooling: 3.7
Heating: 4.1

6.2

Indoor unit: 0.057×1
Outdoor unit: 0.05×1

Indoor unit: 25 (+7.5)
Outdoor unit: 39

5.7

5.6 (1.4~7.1)

5.0 (1.5~5.6)

2.36

1.36

1.2

Indoor: 2.0
Outdoor: 2.0

2+2

Indoor: -
Outdoor: 15

16.5-14.5-12.5-10.5

0.72

Indoor unit: 1,100×710×375 (345)
Outdoor unit: 799 (+99) ×300×629

Cooling: 94
Heating: 96

6.35/12.7 (indoor unit/outdoor unit)

30

50

R32 (1.3)

VP25

Cooling/heating single

Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Part Number-RCID-GP63RGHJ6

RCID-GP63RGHJ6

Available upon quote

Single phase 200
50Hz/60Hz

1

65/67

53-51-49-47

12.9

Cooling: 7.6
Heating: 8.8

6

Indoor unit: 0.057×1
Outdoor unit: 0.05×1

Indoor unit: 25 (+7.5)
Outdoor unit: 41

6

6.3 (1.6~8.0)

5.6 (1.5~6.3)

2.84

1.68

1.47

Indoor: 2.0
Outdoor: 3.5

2+2

Indoor: -
Outdoor: 15

17-15-13-11

0.73

Indoor unit: 1,100×710×375 (345)
Outdoor unit: 799 (+99) ×300×629

Cooling: 97
Heating: 96

6.35/12.7 (indoor unit/outdoor unit)

30

50

R32 (1.3)

VP25

Cooling/heating single

Air conditioner for stores and offices Indoor unit Equipped with individual louver setting function 2 directions-Part Number-RCID-GP63RGH6

RCID-GP63RGH6

Available upon quote

Three phase 200
50Hz/60Hz

1

65/67

53-51-49-47

9.4

Cooling: 4.4
Heating: 5.2

6

Indoor unit: 0.057×1
Outdoor unit: 0.05×1

Indoor unit: 25 (+7.5)
Outdoor unit: 39

6

6.3 (1.6~8.0)

5.6 (1.5~6.3)

2.84

1.68

1.47

Indoor: 2.0
Outdoor: 2.0

2+2

Indoor: -
Outdoor: 15

17-15-13-11

0.73

Indoor unit: 1,100×710×375 (345)
Outdoor unit: 799 (+99) ×300×629

Cooling: 94
Heating: 96

6.35/12.7 (indoor unit/outdoor unit)

30

50

R32 (1.3)

VP25

Cooling/heating single

Click on the part number for more information about each product

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Cooling Devices Products

Other products of Kyushu Kiden Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Kyushu Kiden Co., Ltd.

About Company Handling This Product

Response Rate

100.0%


Response Time

29.5hrs


Company Review

5.0
  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2025 Metoree