All Categories
History
Product
DC-AC inverter SR series SR1000Handling Company
Denryo Co., Ltd.Categories
Click on the part number for more information about each product
Image | Part Number | Price (excluding tax) | Weight | Uninterrupted switching time | No load current | Maximum efficiency | Maximum output power (3 minutes) | Dimensions (L×W×H) | Rated output power | Rated input voltage | Safety standards | Frequency (switchable) | Operating temperature range | Output voltage (switchable) | Output waveform | Cooling | Protection circuit | Storage temperature | Surge power | EMC standard | DC input voltage range | AC input breaker |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
SR1000T-124 |
Available upon quote |
5.8kg |
AC bypass mode: 20ms or less, DC-AC inverter mode: 8msec or less |
1.4A |
87% |
1,100VA |
345×483×44mm |
1,000VA |
24Vdc |
- |
Initial value 50/60Hz±0.5%, 47~63Hz setting possible |
0~+50℃ (rated load) |
Initial value 100±5%, 97~123Vac setting possible |
Sine wave (distortion rate 2% or less) |
Temperature load linked fan |
Input undervoltage, input overvoltage, input reverse polarity connection (fuse), output overload, output short circuit, overtemperature |
-30~+70℃ |
2,000VA |
- |
18~34Vdc |
12A |
|
SR1000T-148 |
Available upon quote |
5.8kg |
AC bypass mode: 20ms or less, DC-AC inverter mode: 8msec or less |
0.75A |
88% |
1,100VA |
345×483×44mm |
1,000VA |
48Vdc |
- |
Initial value 50/60Hz±0.5%, 47~63Hz setting possible |
0~+50℃ (rated load) |
Initial value 100±5%, 97~123Vac setting possible |
Sine wave (distortion rate 2% or less) |
Temperature load linked fan |
Input undervoltage, input overvoltage, input reverse polarity connection (fuse), output overload, output short circuit, overtemperature |
-30~+70℃ |
2,000VA |
- |
36~60Vdc |
12A |
|
SR1000T-224 |
Available upon quote |
5.8kg |
AC bypass mode: 20ms or less, DC-AC inverter mode: 8msec or less |
1.3A |
90% |
1,100VA |
345×483×44mm |
1,000VA |
24Vdc |
EN62368-1 |
Initial value 50/60Hz±0.5%, 47~63Hz setting possible |
0~+50℃ (rated load) |
Initial value 200±3%, 194~246Vac setting possible |
Sine wave (distortion rate 2% or less) |
Temperature load linked fan |
Input undervoltage, input overvoltage, input reverse polarity connection (fuse), output overload, output short circuit, overtemperature |
-30~+70℃ |
2,000VA |
EN55022; EN55024; EN61000-3-2,-3-3; IEC61000-4-2, 3, 4, 5, 6, 8, 11 |
18~34Vdc |
6A |
|
SR1000T-248 |
Available upon quote |
5.8kg |
AC bypass mode: 20ms or less, DC-AC inverter mode: 8msec or less |
0.7A |
91% |
1,100VA |
345×483×44mm |
1,000VA |
48Vdc |
EN62368-1 |
Initial value 50/60Hz±0.5%, 47~63Hz setting possible |
0~+50℃ (rated load) |
Initial value 200±3%, 194~246Vac setting possible |
Sine wave (distortion rate 2% or less) |
Temperature load linked fan |
Input undervoltage, input overvoltage, input reverse polarity connection (fuse), output overload, output short circuit, overtemperature |
-30~+70℃ |
2,000VA |
EN55022; EN55024; EN61000-3-2,-3-3; IEC61000-4-2, 3, 4, 5, 6, 8, 11 |
36~60Vdc |
6A |
Click on the part number for more information about each product
Reviews shown here are reviews of companies.
Reviews shown here are reviews of companies.