About This Product

The SD series is a next-generation DC-AC sine wave inverter with N+1 redundancy and commercial power selector switch. In the N+1 method, up to 5 units can output in parallel with an output capacity of up to 17.5kVA. In the unlikely event that the inverter fails, the system can continue to operate without stopping, improving system reliability. It also has a built-in bypass relay that synchronizes with the commercial power supply, allowing you to set the priority source for the commercial power supply and inverter. Suitable as an emergency power source during disasters, a backup power system for power outages, and an auxiliary power source for independent solar systems. There is less vibration and noise than a generator, and there is no need to carry exhaust gas or fuel. With the SD series, you can also build a three-phase AC or single-phase three-wire system by combining multiple units of the same model. Three of the same model can output three-phase AC. Can be used in industrial applications such as power motors. You can build a single-phase three-wire system with two of the same model and operate a 100V load and a 200V load in one system. ■Parallel function Up to 5 units can be connected in parallel to expand output capacity. In addition, N+1 redundancy allows you to prepare an extra number in addition to the number required for operation to prevent system stoppage due to failure. ■Single-phase three-wire AC output You can build a single-phase three-wire system by combining two units of the same model. One system can operate 100V and 200V loads. ■Three-phase AC power supply (Y connection) You can output three-phase AC by combining three units of the same model. It can also be used in industrial applications such as power motors. It also supports Δ connection loads. ■Built-in automatic switching relay that allows priority source selection The switching relay instantly (4msec or 6msec) prevents the load from shutting down. You can set the priority source for commercial power and inverter, so it can be used as a countermeasure against power outages or as an auxiliary power source for standalone solar systems. *To configure, you need to connect to a PC with the optional controller CR-10 or serial communication conversion cable CC-1.

  • Product

    DC-AC inverter SD series SD3500

Share this product


440+ people viewing

Last viewed: 3 hours ago


Free
Since our quotes are free, feel free to use our service.

No Phone Number Required
You won’t have to worry about receiving unnecessary calls.

6 Models of DC-AC inverter SD series SD3500

Items marked with have different values depending on the model number.

Click on the part number for more information about each product

Product Image Part Number Price (excluding tax) AC input selection frequency AC input synchronous frequency AC input voltage range Breaker Cooling Current consumption (power save mode) DC input voltage range Dimensions (L×W×H) E mark EMC standard Frequency (switchable) Input protection circuit Insulation resistance Maximum efficiency Maximum output power (3 seconds) No load current Operating temperature range Output power (3 minutes) Output protection circuit Output voltage (switchable) Output waveform Pressure resistance Rated input voltage Rated output power Safety standards Storage temperature/humidity range Surge power (0.2 seconds or less) Uninterrupted switching time Vibration resistance Weight
DC-AC inverter SD series SD3500-Part Number-SD3500-112

SD3500-112

Available upon quote 50/60Hz 47~57/53~63Hz 100/110/115/120Vac±12.5% 35A Temperature load linked fan 1.4A 10.0~16.0Vdc 496×283×128mm - - 50/60 (initial value) Hz±0.1% Undervoltage, overvoltage, reverse polarity connection (fuse), AC input overcurrent (breaker) 100MΩ/500Vdc 90% 4,500~6.4000VA <2.9A -20~+60℃ 3,500~4,500VA Overload, short circuit, overtemperature, overvoltage 100 (initial value) /110/115/120Vac±3% Sine wave (distortion rate 3% or less) Battery Input – AC Output: 2,121Vdc Battery Input – Chassis Ground: 500Vdc AC Output – Chassis Ground: 1,414Vdc 12Vdc 3,500VA - -40~+70℃/0~90%RH (no condensation) >6,000VA Less than 4msec when used alone, less than 6msec when operated in parallel 10~500Hz, 2G 10min./1cycle, 60 minutes in each direction of XYZ 10kg

SD3500-124

Available upon quote 50/60Hz 47~57/53~63Hz 100/110/115/120Vac±12.5% 35A Temperature load linked fan 0.5A 20.0~32.0Vdc 496×283×128mm - - 50/60 (initial value) Hz±0.1% Undervoltage, overvoltage, reverse polarity connection (fuse), AC input overcurrent (breaker) 100MΩ/500Vdc 90% 4,500~6.4000VA <1.4A -20~+60℃ 3,500~4,500VA Overload, short circuit, overtemperature, overvoltage 100 (initial value) /110/115/120Vac±3% Sine wave (distortion rate 3% or less) Battery Input – AC Output: 2,121Vdc Battery Input – Chassis Ground: 500Vdc AC Output – Chassis Ground: 1,414Vdc 24Vdc 3,500VA - -40~+70℃/0~90%RH (no condensation) >6,000VA Less than 4msec when used alone, less than 6msec when operated in parallel 10~500Hz, 2G 10min./1cycle, 60 minutes in each direction of XYZ 10kg

SD3500-148

Available upon quote 50/60Hz 47~57/53~63Hz 100/110/115/120Vac±12.5% 35A Temperature load linked fan 0.5A 40.0~64.0Vdc 496×283×128mm - - 50/60 (initial value) Hz±0.1% Undervoltage, overvoltage, reverse polarity connection (fuse), AC input overcurrent (breaker) 100MΩ/500Vdc 91% 4,500~6.4000VA <0.8A -20~+60℃ 3,500~4,500VA Overload, short circuit, overtemperature, overvoltage 100 (initial value) /110/115/120Vac±3% Sine wave (distortion rate 3% or less) Battery Input – AC Output: 2,121Vdc Battery Input – Chassis Ground: 500Vdc AC Output – Chassis Ground: 1,414Vdc 48Vdc 3,500VA - -40~+70℃/0~90%RH (no condensation) >6,000VA Less than 4msec when used alone, less than 6msec when operated in parallel 10~500Hz, 2G 10min./1cycle, 60 minutes in each direction of XYZ 10kg

SD3500-212

Available upon quote 50/60Hz 47~57/53~63Hz 200/220/230/240Vac±12.5% 20A Temperature load linked fan 1.4A 10.0~16.0Vdc 496×283×128mm CISPR 25; ISO 7637-2 EN55014-1, EN55014-2; EN61000-3-2, -3-3; EN61204-3; EN61000-6-1, -6-2, -6-3, -6-4 50 (initial value) /60Hz±0.1% Undervoltage, overvoltage, reverse polarity connection (fuse), AC input overcurrent (breaker) 100MΩ/500Vdc 90% 4,500~6.4000VA <3.6A -20~+60℃ 3,500~4,500VA Overload, short circuit, overtemperature, overvoltage 200 (initial value) /220/230/240Vac±3% Sine wave (distortion rate 3% or less) Battery Input – AC Output: 4,242Vdc Battery Input – Chassis Ground: 500Vdc AC Output – Chassis Ground: 2,121Vdc 12Vdc 3,500VA EN62368-1 -40~+70℃/0~90%RH (no condensation) >6,000VA Less than 4msec when used alone, less than 6msec when operated in parallel 10~500Hz, 2G 10min./1cycle, 60 minutes in each direction of XYZ 10kg

SD3500-224

Available upon quote 50/60Hz 47~57/53~63Hz 200/220/230/240Vac±12.5% 20A Temperature load linked fan 0.5A 20.0~32.0Vdc 496×283×128mm CISPR 25; ISO 7637-2 EN55014-1, EN55014-2; EN61000-3-2, -3-3; EN61204-3; EN61000-6-1, -6-2, -6-3, -6-4 50 (initial value) /60Hz±0.1% Undervoltage, overvoltage, reverse polarity connection (fuse), AC input overcurrent (breaker) 100MΩ/500Vdc 91% 4,500~6.4000VA <1.8A -20~+60℃ 3,500~4,500VA Overload, short circuit, overtemperature, overvoltage 200 (initial value) /220/230/240Vac±3% Sine wave (distortion rate 3% or less) Battery Input – AC Output: 4,242Vdc Battery Input – Chassis Ground: 500Vdc AC Output – Chassis Ground: 2,121Vdc 24Vdc 3,500VA EN62368-1 -40~+70℃/0~90%RH (no condensation) >6,000VA Less than 4msec when used alone, less than 6msec when operated in parallel 10~500Hz, 2G 10min./1cycle, 60 minutes in each direction of XYZ 10kg

SD3500-248

Available upon quote 50/60Hz 47~57/53~63Hz 200/220/230/240Vac±12.5% 20A Temperature load linked fan 0.5A 40.0~64.0Vdc 496×283×128mm CISPR 25; ISO 7637-2 EN55014-1, EN55014-2; EN61000-3-2, -3-3; EN61204-3; EN61000-6-1, -6-2, -6-3, -6-4 50 (initial value) /60Hz±0.1% Undervoltage, overvoltage, reverse polarity connection (fuse), AC input overcurrent (breaker) 100MΩ/500Vdc 91% 4,500~6.4000VA <1A -20~+60℃ 3,500~4,500VA Overload, short circuit, overtemperature, overvoltage 200 (initial value) /220/230/240Vac±3% Sine wave (distortion rate 3% or less) Battery Input – AC Output: 4,242Vdc Battery Input – Chassis Ground: 500Vdc AC Output – Chassis Ground: 2,121Vdc 48Vdc 3,500VA EN62368-1 -40~+70℃/0~90%RH (no condensation) >6,000VA Less than 4msec when used alone, less than 6msec when operated in parallel 10~500Hz, 2G 10min./1cycle, 60 minutes in each direction of XYZ 10kg

Click on the part number for more information about each product

Customers who viewed this product also viewed

Other products of Denryo Co., Ltd.


View more products of Denryo Co., Ltd.

About Company Handling This Product

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree