Communication SPD (for communication/signal) Z seriesHandling Company
Showden Co., Ltd.Categories
Click on the part number for more information about each product
Image | Part Number | Price (excluding tax) | Voltage protection level (Up) between earth | Voltage protection level (Up) between lines | Voltage pulse Sensin pulse AC100V 200V | Protection mode between lines | Protection mode between ground | Protection mode Shield-to-ground | Anti-ground noise countermeasures | DC resistance | DC operating voltage V1mA line to line | DC operating voltage V1mA between ground | Purpose | Maximum continuous working voltage Uc | Failure display | Insertion loss | Rated current | Rated voltage | Number of protection hearts | Transmission frequency band (110Ω) | Relay contact control power supply AC100V 200V | Speaker line AC100V 200V | Impulse durability category D1 between ground | Impulse durability category C2 between lines | Impulse durability category C2 between ground | Impulse limit voltage between lines | Impulse limit voltage between ground | Relay contact control power supply (2A or less) DC110V | Thermocouple/side temperature resistance potentiometer DC24V | Relay contact control power supply DC48V, AC24V | Relay contact control power supply (2A or less) DC24V | Relay contact control power supply (2A or less) DC12V |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ASG-Z12S |
Available upon quote |
110V or less Noise-resistant connection: 500V or less |
150V or less |
- |
Normal connection: between terminals 1, 2, 3, 4, noise-resistant connection: between terminals 1, 2, 3, 4 and terminal 6 (common) |
Normal connection: between terminals 1, 2, 3, 4 to terminal 6 (ground), noise-resistant connection: between terminals 1, 2, 3, 4 and terminal 6 (common) to terminal 5 (ground) |
Normal connection: between terminal 5 (shield) and terminal 6, noise-resistant connection: only supports grounding at both ends of the shield and connects to terminal 5 (ground) |
Compatible with noise-resistant connections |
0.1Ω or less |
DC19V+10%-14% |
DC19V+10%-14% Noise-resistant connection: DC230V±20% |
DC12V or less Contact/control line |
DC14V |
Normal: LED (red) goes off Deterioration/failure: LED (red) lights up |
1.0dB or less |
DC/AC 2A |
DC12V |
4 cores + shield |
DC~5MHz |
- | - |
10/350μs 0.5kA |
8/20μs 4kA |
8/20μs 4kA |
100V or less |
90V or less |
- | - | - | - |
◎ |
|
ASG-Z24S |
Available upon quote |
180V or less Noise-resistant connection: 500V or less |
220V or less |
- |
Normal connection: between terminals 1, 2, 3, 4, noise-resistant connection: between terminals 1, 2, 3, 4 and terminal 6 (common) |
Normal connection: between terminals 1, 2, 3, 4 to terminal 6 (ground), noise-resistant connection: between terminals 1, 2, 3, 4 and terminal 6 (common) to terminal 5 (ground) |
Normal connection: between terminal 5 (shield) and terminal 6, noise-resistant connection: only supports grounding at both ends of the shield and connects to terminal 5 (ground) |
Compatible with noise-resistant connections |
0.1Ω or less |
DC40V+10%-14% |
DC40V+10%-14% Noise resistant connection: DC230V±20% |
DC24V or less Contact/control line |
DC31V |
Normal: LED (red) goes off Deterioration/failure: LED (red) lights up |
1.0dB or less |
DC/AC 2A |
DC24V |
4 cores + shield |
DC~5MHz |
- | - |
10/350μs 0.5kA |
8/20μs 4kA |
8/20μs 4kA |
160V or less |
150V or less |
- | - | - |
◎ |
- | |
ASG-Z48S |
Available upon quote |
300V or less Noise-resistant connection: 500V or less |
240V or less |
- |
Normal connection: between terminals 1, 2, 3, 4, noise-resistant connection: between terminals 1, 2, 3, 4 and terminal 6 (common) |
Normal connection: between terminals 1, 2, 3, 4 to terminal 6 (ground), noise-resistant connection: between terminals 1, 2, 3, 4 and terminal 6 (common) to terminal 5 (ground) |
Normal connection: between terminal 5 (shield) and terminal 6, noise-resistant connection: only supports grounding at both ends of the shield and connects to terminal 5 (ground) |
Compatible with noise-resistant connections |
0.1Ω or less |
DC82V+10%-14% |
DC82V+10%-14% Noise resistant connection: DC230V±20% |
DC48V, AC24V contacts/control wires, thermocouples, resistance temperature detectors for DC voltage signals, potentiometers |
DC60V |
Normal: LED (red) goes off Deterioration/failure: LED (red) lights up |
1.0dB or less |
DC/AC 2A |
DC48V |
4 cores + shield |
DC~5MHz |
- | - |
10/350μs 1kA |
8/20μs 4kA |
8/20μs 10kA |
200V or less |
200V or less |
- |
◎ |
◎ |
- | - | |
ASG-Z100S |
Available upon quote |
450V or less Noise-resistant connection: 500V or less |
360V or less |
- |
Normal connection: between terminals 1, 2, 3, 4, noise-resistant connection: between terminals 1, 2, 3, 4 and terminal 6 (common) |
Normal connection: between terminals 1, 2, 3, 4 to terminal 6 (ground), noise-resistant connection: between terminals 1, 2, 3, 4 and terminal 6 (common) to terminal 5 (ground) |
Normal connection: between terminal 5 (shield) and terminal 6, noise-resistant connection: only supports grounding at both ends of the shield and connects to terminal 5 (ground) |
Compatible with noise-resistant connections |
0.1Ω or less |
DC150V+10%-14% |
DC150V+10%-14% Noise resistant connection: DC230V±20% |
DC110V contact/control line |
DC125V |
Normal: LED (red) goes off Deterioration/failure: LED (red) lights up |
1.0dB or less |
DC/AC 2A |
DC110V |
4 cores + shield |
DC~5MHz |
- | - |
10/350μs 1kA |
8/20μs 4kA |
8/20μs 10kA |
300V or less |
300V or less |
◎ |
- | - | - | - | |
ASG-Z350S |
Available upon quote |
1,200V or less Noise-resistant connection: 500V or less |
1,000V or less |
◎ |
Normal connection: between terminals 1, 2, 3, 4, noise-resistant connection: between terminals 1, 2, 3, 4 and terminal 6 (common) |
Normal connection: between terminals 1, 2, 3, 4 to terminal 6 (ground), noise-resistant connection: between terminals 1, 2, 3, 4 and terminal 6 (common) to terminal 5 (ground) |
Normal connection: between terminal 5 (shield) and terminal 6, noise-resistant connection: only supports grounding at both ends of the shield and connects to terminal 5 (ground) |
Compatible with noise-resistant connections |
0.1Ω or less |
DC470V+10%-14% |
DC470V+10%-14% Noise resistant connection: DC230V±20% |
AC100V/200V contacts/control wires for broadcasting (for speakers) |
AC275V DC350V *When making noise-resistant connections with ASG-Z350S, Uc should be AC140V/DC170V. (Noise-resistant connection is not possible when used at AC200V) |
Normal: LED (red) goes off Deterioration/failure: LED (red) lights up |
1.0dB or less |
DC/AC 2A |
AC100V AC200V *When making noise-resistant connections with ASG-Z350S, Uc should be AC140V/DC170V. (Noise-resistant connection is not possible when used at AC200V) |
4 cores + shield |
DC~5MHz |
◎ |
◎ |
10/350μs 0.5kA |
8/20μs 4kA |
8/20μs 10kA |
900V or less |
900V or less |
- | - | - | - | - |