SPD for power supply For PV (for DC power supply) ADN series-ADN-406DA
SPD for power supply For PV (for DC power supply) ADN series-Showden Co., Ltd.

SPD for power supply For PV (for DC power supply) ADN series
Showden Co., Ltd.

Showden Co., Ltd.'s Response Status

Response Rate

100.0%

Response Time

117.8hours


About This Product

■High-end model with Imax40kA of PV SPD compatible with JIS C 5381-31

The ADN series is a PV SPD that uses safety shutoff technologies "SIT" and "SITS®" and supports a nominal discharge current of 8/20μs 20kA and a maximum discharge current of 8/20μs 40kA. Protects the DC power system equipment of solar power generation systems from lightning damage. Even in the unlikely event of an SPD short-circuit failure, all current up to 2.5kA can be safely cut off by connecting the specified SPD separator. In addition, in the event of an SPD short-circuit failure, the SPD alone can cut off up to 100A, so if it is used in a PV system with a short-circuit current of 100A or less, it can be used without an SPD separator.

■SPD (surge arrester) with built-in isolation mechanism for DC high voltage and short circuit current

Adopts safety cut-off technologies SIT and SITS®, which can cut off short-circuit current of up to 150A when an SPD fails, and by connecting a dedicated SPD separator, short-circuit current can be cut off in the entire range up to the maximum short-circuit current of the circuit. can be safely shut off. It can also handle short-circuit currents between grounds that vary depending on the equipment (in Japan's TT system, short-circuit currents between grounds differ depending on class B and class D grounding resistance values), further improving safety in the event of an SPD failure. I did.

■Plug-in type, failure display, and alarm output terminal (*) are standard equipment.

When this product malfunctions due to a lightning surge current that exceeds the current withstand capacity, the malfunction display window changes from white to red to indicate a malfunction. The risk of failure can be minimized. *ADN-406DA/ADN-410DA only

■Features

・Can interrupt short circuit current up to DC1000 V100A with a single SPD ・Lineup compatible with DC600V system and DC1000V system ・Long life with In20kA (Imax40kA) ・Plug-in type, failure display, and alarm output terminal* are standard equipment. *ADN-406DA/ADN-410DA only

  • Product

    SPD for power supply For PV (for DC power supply) ADN series

Share this product


410+ people viewing

Last viewed: 6 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

4 Models of SPD for power supply For PV (for DC power supply) ADN series

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Voltage protection level up Protection mode Applicable wire Applicable circuit DC1000V 2W Alarm contact Test standards Exam class Temperature/humidity Structure Maximum continuous working voltage Ucpv Maximum discharge current Imax Failure display Recommended wire Connection terminal Specified SPD separator Short circuit current 850A or less Specified SPD separator Short circuit current 2.5kA or less Specified SPD separator Required quantity Rated short circuit current Iscpv External dimensions (mm) Installation location Installation method Nominal discharge current In Impulse discharge current Iimp Applicable circuit DC600V 2W
SPD for power supply For PV (for DC power supply) ADN series-Part Number-ADN-406DA

ADN-406DA

Available upon quote

2.5kV

'Between + and E, between - and E, between + and -

5.5mm2~14mm2

-

Mechanical

JIS C 5381-31

Class I Class II

Operating temperature and storage temperature: -40℃~+70℃ Relative humidity: 95% or less

Plugin

DC750V

8/20μs 40kA

Normal: Green When faulty: Red or black

Line side 5.5mm2 Ground side 8mm2

M5 screw terminal (connected using M5 crimp terminal)

KLD2 20A (Lightning surge) / HK1551 (Holder) HC-15 (Cover) PFP-S (Spacer)

PV-20A14F or PV-25A14F (gPV fuse) /CH141B-PV

2 sets

100A*Can be applied to short circuit currents up to 850A or 2.5kA by connecting the specified SPD separator.

54×97×93.5

Indoors or inside the panel

Direct mounting with rail mounting (35mm width) or mounting bracket (optional)

8/20μs 20kA

10/350μs 4kA

SPD for power supply For PV (for DC power supply) ADN series-Part Number-ADN-406D

ADN-406D

Available upon quote

2.5kV

'Between + and E, between - and E, between + and -

5.5mm2~14mm2

-

Mechanical

JIS C 5381-31

Class I Class II

Operating temperature and storage temperature: -40℃~+70℃ Relative humidity: 95% or less

Plugin

DC750V

8/20μs 40kA

Normal: Green When faulty: Red or black

Line side 5.5mm2 Ground side 8mm2

M5 screw terminal (connected using M5 crimp terminal)

KLD2 20A (Lightning surge) / HK1551 (Holder) HC-15 (Cover) PFP-S (Spacer)

PV-20A14F or PV-25A14F (gPV fuse) /CH141B-PV

2 sets

100A*Can be applied to short circuit currents up to 850A or 2.5kA by connecting the specified SPD separator.

54×97×93.5

Indoors or inside the panel

Direct mounting with rail mounting (35mm width) or mounting bracket (optional)

8/20μs 20kA

10/350μs 4kA

SPD for power supply For PV (for DC power supply) ADN series-Part Number-ADN-410DA

ADN-410DA

Available upon quote

4kV

'Between + and E, between - and E, between + and -

5.5mm2~14mm2

Mechanical

JIS C 5381-31

Class I Class II

Operating temperature and storage temperature: -40℃~+70℃ Relative humidity: 95% or less

Plugin

DC1,200V

8/20μs 40kA

Normal: Green When faulty: Red or black

Line side 5.5mm2 Ground side 8mm2

M5 screw terminal (connected using M5 crimp terminal)

PV-20A14F or PV-25A14F (gPV fuse) / CH141B-PV

PV-20A14F or PV-25A14F (gPV fuse) /CH141B-PV

2 sets

100A*Can be applied to short circuit currents up to 850A or 2.5kA by connecting the specified SPD separator.

54×97×93.5

Indoors or inside the panel

Direct mounting with rail mounting (35mm width) or mounting bracket (optional)

8/20μs 20kA

10/350μs 2.5kA

-
SPD for power supply For PV (for DC power supply) ADN series-Part Number-ADN-410D

ADN-410D

Available upon quote

4kV

'Between + and E, between - and E, between + and -

5.5mm2~14mm2

Mechanical

JIS C 5381-31

Class I Class II

Operating temperature and storage temperature: -40℃~+70℃ Relative humidity: 95% or less

Plugin

DC1,200V

8/20μs 40kA

Normal: Green When faulty: Red or black

Line side 5.5mm2 Ground side 8mm2

M5 screw terminal (connected using M5 crimp terminal)

PV-20A14F or PV-25A14F (gPV fuse) / CH141B-PV

PV-20A14F or PV-25A14F (gPV fuse) /CH141B-PV

2 sets

100A*Can be applied to short circuit currents up to 850A or 2.5kA by connecting the specified SPD separator.

54×97×93.5

Indoors or inside the panel

Direct mounting with rail mounting (35mm width) or mounting bracket (optional)

8/20μs 20kA

10/350μs 2.5kA

-

Click on the part number for more information about each product

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Lightning Arresters Products

Other products of Showden Co., Ltd.