Power supply SPD GN-2 series-GN-222A
Power supply SPD GN-2 series-Showden Co., Ltd.

Power supply SPD GN-2 series
Showden Co., Ltd.

Showden Co., Ltd.'s Response Status

Response Rate

100.0%

Response Time

117.8hours


About This Product

■Electrical failure display and electrical alarm contact

Fault indicators and alarm contacts are electrical. The LED (green) lights up when the failure is normal and turns off when the SPD fails or there is a power outage. For electrical failure indicators, the LED will also turn off when the specified SPD separator is activated (fuse blown) or when the SPD separator (fuse) is not installed. The alarm contact is output from the alarm contact terminal (ALM), and between c and a is a contact output (normal: OPEN, abnormal: CLOSE), and between b and c is a b contact output (normal: CLOSE, abnormal: OPEN). The advantage of electrical alarm contacts is that they not only issue an alarm when an SPD fails, but also operate the SPD separator and output the alarm contact even when the SPD separator (fuse) is not installed. Therefore, in the unlikely event that the SPD separator operates or the fuse is not installed, it is possible to avoid situations where the SPD's overvoltage limiting function cannot be fully utilized.

■Features

Compatible with low voltage SPD class II of public construction standard specifications (2019 edition)

■Can also be connected to the primary side of an earth leakage breaker

Annex K of IS C 5381-12:2014 stipulates that in TT systems (including Japanese power distribution systems), when connecting an SPD to the primary side of an earth leakage breaker, a voltage switching element such as a spark gap or GDT must be It is described that it is implemented. The GN-2 series can be connected to the primary side of an earth leakage breaker without any problems by installing a GDT (gas-filled discharge tube) between N and E.

■Model names that include specified SPD separators as a set have also been added.

The old standard JIS C 5381-1 did not require safety in the event of an SPD short-circuit failure, so 50AF/50AT MCCBs have been mainly used for SPD separators. On the other hand, the new standard JIS C 5381-11 requires testing for safety in the event of SPD failure in combination with the SPD separator specified by the manufacturer. Therefore, when using an SPD that complies with JIS C 5381-11, it is necessary to connect the specified SPD separator. This time, we have added a model name that includes a specified SPD separator as a set. This set model name with the SPD separator eliminates mistakes in SPD separator selection and allows safer use.

  • Product

    Power supply SPD GN-2 series

Share this product


570+ people viewing

Last viewed: 7 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

8 Models of Power supply SPD GN-2 series

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Protection mode Test standards Exam class Structure Maximum continuous working voltage Uc Voltage switching device to ground (GDT) Single phase 3 wire neutral wire grounding 100V/200V TOV on low pressure side Three-phase 4-wire Y connection, neutral point grounding 100V/173V Three-phase three-wire delta connection one-wire grounding 200V Type SPD separator Single phase 2 wire neutral point grounding 200V Single phase 2 wire 1 wire grounding 200V Single phase 2 wire 1 wire grounding 100V
Power supply SPD GN-2 series-Part Number-GN-222A

GN-222A

Available upon quote

L-L, L-E

JIS C 5381-11

Class II

One piece

AC280V

Yes

-

Endure

- -

Single SPD, with alarm contact

External

Power supply SPD GN-2 series-Part Number-GN-223A

GN-223A

Available upon quote

L-L, L-E

JIS C 5381-11

Class II

One piece

AC280V

Yes

Endure

Single SPD, with alarm contact

External

- - -
Power supply SPD GN-2 series-Part Number-GN-222

GN-222

Available upon quote

L-L, L-E

JIS C 5381-11

Class II

One piece

AC280V

Yes

-

Endure

- -

Single SPD, no alarm contact

External

Power supply SPD GN-2 series-Part Number-GN-223

GN-223

Available upon quote

L-L, L-E

JIS C 5381-11

Class II

One piece

AC280V

Yes

Endure

Single SPD, no alarm contact

External

- - -
Power supply SPD GN-2 series-Part Number-GN-222A-F

GN-222A-F

Available upon quote

L-L, L-E

JIS C 5381-11

Class II

One piece

AC280V

Yes

-

Endure

- -

Set format of SPD and SPD separator, with alarm contact

External

Power supply SPD GN-2 series-Part Number-GN-223A-F

GN-223A-F

Available upon quote

L-L, L-E

JIS C 5381-11

Class II

One piece

AC280V

Yes

Endure

Set format of SPD and SPD separator, with alarm contact

External

- - -
Power supply SPD GN-2 series-Part Number-GN-222-F

GN-222-F

Available upon quote

L-L, L-E

JIS C 5381-11

Class II

One piece

AC280V

Yes

-

Endure

- -

Set format of SPD and SPD separator, no alarm contact

External

Power supply SPD GN-2 series-Part Number-GN-223-F

GN-223-F

Available upon quote

L-L, L-E

JIS C 5381-11

Class II

One piece

AC280V

Yes

Endure

Set format of SPD and SPD separator, no alarm contact

External

- - -

Click on the part number for more information about each product

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Lightning Arresters Products

Other products of Showden Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Showden Co., Ltd.

About Company Handling This Product

Response Rate

100.0%


Response Time

117.8hrs

  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2025 Metoree