Product
OIL COOLING UNIT Oil conditioner AKJ 9W series (immersion type/water cooling type)Handling Company
Nippon Mekuman Co., Ltd.Categories
Items marked with have different values depending on the model number.
Click on the part number for more information about each product
Product Image | Part Number | Price (excluding tax) | Capacity control range | Circuit voltage (operating circuit) | Compressor (totally hermetic DC swing type) | Condenser | Cooling capacity 50/60Hz (kW) | Evaporator | Exterior color | External dimensions H×W×D (mm) | Fan 50/60Hz (electric motor) | Heater (kW) | Maximum power consumption/maximum current consumption (when cooling) | Maximum power consumption/maximum current consumption (when heating) | Oil conditioner equivalent horsepower (HP) | Oil temperature controller resolution | Protection device | Protection function | Refrigerant charge amount (kg) | Refrigerant control | Stirrer (electric motor) | Supply power circuit voltage (main circuit) | Temperature control Fixed type Controlled object | Temperature control Synchronized type Controlled object | Temperature control Tuning type Tuning range (K) | Temperature control fixed type range (℃) | Temperature control synchronized type standard | Timer function | Type | Usage range Oil viscosity (mm2/s) | Usage range Primary cooling water temperature (℃) | Usage range Room temperature (℃) | Usage range Tank liquid temperature (℃) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AKJ569W |
Available upon quote | 0~100% | DC12/24V | Equivalent to 1.5kW | Double tube type | 5.0/5.6 | Open coil type | Ivory white | 1,440×470×500 | 20/19W | - |
・200V 50Hz: 2.25kW/7.7A ・200V 60Hz: 2.25kW/7.4A ・220V 60Hz: 2.24kW/6.9A |
- | 2 | ±0.1℃ | Stirrer inner thermostat, discharge pipe temperature thermostat, condenser temperature thermostat, reverse phase protection device, high liquid temperature protection thermostat, low liquid temperature protection thermostat, inverter protection device set | Restart prevention timer/refrigerant leak detection | 0.78 | Compressor rotation speed + electronic expansion valve opening by inverter | 3 phase AC, 60W, 4P | 3 phase AC200/200/220V 50/60Hz | Tank liquid temperature | Tank liquid temperature | -9.9~+9.9 relative to standard temperature (0.0 at factory shipment) | 5~50 | Room temperature or aircraft temperature (Factory setting is room temperature: Mode 4) | ON timer: 1~999 hours (set in 1 hour increments) | - | 0.5~200 | 5~40 | 5~45 | 5~50 | |
AKJ569W-B |
Available upon quote | 0~100% | DC12/24V | Equivalent to 1.5kW | Double tube type | 5.0/5.6 | Open coil type | Ivory white | 1,440×470×500 | 20/19W | - |
・200V 50Hz: 2.25kW/7.7A ・200V 60Hz: 2.25kW/7.4A ・220V 60Hz: 2.24kW/6.9A |
- | 2 | ±0.1℃ | Stirrer inner thermostat, discharge pipe temperature thermostat, condenser temperature thermostat, reverse phase protection device, high liquid temperature protection thermostat, low liquid temperature protection thermostat, inverter protection device set, circuit breaker | Restart prevention timer/refrigerant leak detection | 0.78 | Compressor rotation speed + electronic expansion valve opening by inverter | 3 phase AC, 60W, 4P | 3 phase AC200/200/220V 50/60Hz | Tank liquid temperature | Tank liquid temperature | -9.9~+9.9 relative to standard temperature (0.0 at factory shipment) | 5~50 | Room temperature or aircraft temperature (Factory setting is room temperature: Mode 4) | ON timer: 1~999 hours (set in 1 hour increments) | With breaker | 0.5~200 | 5~40 | 5~45 | 5~50 | |
AKJ569W-C |
Available upon quote | 0~100% | DC12/24V | Equivalent to 1.5kW | Double tube type | 5.0/5.6 | Open coil type | Ivory white | 1,440×470×500 | 20/19W | - |
・200V 50Hz: 2.25kW/7.7A ・200V 60Hz: 2.25kW/7.4A ・220V 60Hz: 2.24kW/6.9A |
- | 2 | ±0.1℃ | Stirrer inner thermostat, discharge pipe temperature thermostat, condenser temperature thermostat, reverse phase protection device, high liquid temperature protection thermostat, low liquid temperature protection thermostat, inverter protection device set, high pressure switch, compressor protection thermostat | Restart prevention timer/refrigerant leak detection | 0.78 | Compressor rotation speed + electronic expansion valve opening by inverter | 3 phase AC, 60W, 4P | 3 phase AC200/200/220V 50/60Hz | Tank liquid temperature | Tank liquid temperature | -9.9~+9.9 relative to standard temperature (0.0 at factory shipment) | 5~50 | Room temperature or aircraft temperature (Factory setting is room temperature: Mode 4) | ON timer: 1~999 hours (set in 1 hour increments) | CE compatible | 0.5~200 | 5~40 | 5~45 | 5~50 | |
AKJ569W-H |
Available upon quote | 0~100% | DC12/24V | Equivalent to 1.5kW | Double tube type | 5.0/5.6 | Open coil type | Ivory white | 1,440×470×500 | 20/19W | 2 |
・200V 50Hz: 2.25kW/7.7A ・200V 60Hz: 2.25kW/7.4A ・220V 60Hz: 2.24kW/6.9A |
・200V 50Hz: 2.32kW/7.1A ・200V 60Hz: 2.33kW/7.1A ・220V 60Hz: 2.79kW/7.8A |
2 | ±0.1℃ | Stirrer inner thermostat, discharge pipe temperature thermostat, condenser temperature thermostat, reverse phase protection device, high liquid temperature protection thermostat, low liquid temperature protection thermostat, inverter protection device set, heating prevention temperature switch, temperature fuse | Restart prevention timer/refrigerant leak detection | 0.78 | Compressor rotation speed + electronic expansion valve opening by inverter | 3 phase AC, 60W, 4P | 3 phase AC200/200/220V 50/60Hz | Tank liquid temperature | Tank liquid temperature | -9.9~+9.9 relative to standard temperature (0.0 at factory shipment) | 5~50 | Room temperature or aircraft temperature (Factory setting is room temperature: Mode 4) | ON timer: 1~999 hours (set in 1 hour increments) | With heater | 0.5~200 | 5~40 | 5~45 | 5~50 | |
AKJ909W |
Available upon quote | 0~100% | DC12/24V | Equivalent to 2.2kW | Double tube type | 8.0/9.0 | Open coil type | Ivory white | 1,615×560×620 | 20/19W | - |
・200V 50Hz: 4.13kW/13.5A ・200V 60Hz: 4.14kW/13.3A ・220V 60Hz: 4.13kW/12.1A |
- | 3 | ±0.1℃ | Stirrer inner thermostat, discharge pipe temperature thermostat, condenser temperature thermostat, reverse phase protection device, high liquid temperature protection thermostat, low liquid temperature protection thermostat, inverter protection device set | Restart prevention timer/refrigerant leak detection | 1.07 | Compressor rotation speed + electronic expansion valve opening by inverter | 3 phase AC, 60W, 4P | 3 phase AC200/200/220V 50/60Hz | Tank liquid temperature | Tank liquid temperature | -9.9~+9.9 relative to standard temperature (0.0 at factory shipment) | 5~50 | Room temperature or aircraft temperature (Factory setting is room temperature: Mode 4) | ON timer: 1~999 hours (set in 1 hour increments) | - | 0.5~200 | 5~40 | 5~45 | 5~50 | |
AKJ909W-B |
Available upon quote | 0~100% | DC12/24V | Equivalent to 2.2kW | Double tube type | 8.0/9.0 | Open coil type | Ivory white | 1,615×560×620 | 20/19W | - |
・200V 50Hz: 4.13kW/13.5A ・200V 60Hz: 4.14kW/13.3A ・220V 60Hz: 4.13kW/12.1A |
- | 3 | ±0.1℃ | Stirrer inner thermostat, discharge pipe temperature thermostat, condenser temperature thermostat, reverse phase protection device, high liquid temperature protection thermostat, low liquid temperature protection thermostat, inverter protection device set, circuit breaker | Restart prevention timer/refrigerant leak detection | 1.07 | Compressor rotation speed + electronic expansion valve opening by inverter | 3 phase AC, 60W, 4P | 3 phase AC200/200/220V 50/60Hz | Tank liquid temperature | Tank liquid temperature | -9.9~+9.9 relative to standard temperature (0.0 at factory shipment) | 5~50 | Room temperature or aircraft temperature (Factory setting is room temperature: Mode 4) | ON timer: 1~999 hours (set in 1 hour increments) | With breaker | 0.5~200 | 5~40 | 5~45 | 5~50 | |
AKJ909W-C |
Available upon quote | 0~100% | DC12/24V | Equivalent to 2.2kW | Double tube type | 8.0/9.0 | Open coil type | Ivory white | 1,615×560×620 | 20/19W | - |
・200V 50Hz: 4.13kW/13.5A ・200V 60Hz: 4.14kW/13.3A ・220V 60Hz: 4.13kW/12.1A |
- | 3 | ±0.1℃ | Stirrer inner thermostat, discharge pipe temperature thermostat, condenser temperature thermostat, reverse phase protection device, high liquid temperature protection thermostat, low liquid temperature protection thermostat, inverter protection device set, high pressure switch, compressor protection thermostat | Restart prevention timer/refrigerant leak detection | 1.07 | Compressor rotation speed + electronic expansion valve opening by inverter | 3 phase AC, 60W, 4P | 3 phase AC200/200/220V 50/60Hz | Tank liquid temperature | Tank liquid temperature | -9.9~+9.9 relative to standard temperature (0.0 at factory shipment) | 5~50 | Room temperature or aircraft temperature (Factory setting is room temperature: Mode 4) | ON timer: 1~999 hours (set in 1 hour increments) | CE compatible | 0.5~200 | 5~40 | 5~45 | 5~50 | |
AKJ909W-H |
Available upon quote | 0~100% | DC12/24V | Equivalent to 2.2kW | Double tube type | 8.0/9.0 | Open coil type | Ivory white | 1,615×560×620 | 20/19W | 4 |
・200V 50Hz: 4.13kW/13.5A ・200V 60Hz: 4.14kW/13.3A ・220V 60Hz: 4.13kW/12.1A |
・200V 50Hz: 4.42kW/13.1A ・200V 60Hz: 4.45kW/13.1A ・220V 60Hz: 5.33kW/14.1A |
3 | ±0.1℃ | Stirrer inner thermostat, discharge pipe temperature thermostat, condenser temperature thermostat, reverse phase protection device, high liquid temperature protection thermostat, low liquid temperature protection thermostat, inverter protection device set, heating prevention temperature switch, temperature fuse | Restart prevention timer/refrigerant leak detection | 1.07 | Compressor rotation speed + electronic expansion valve opening by inverter | 3 phase AC, 60W, 4P | 3 phase AC200/200/220V 50/60Hz | Tank liquid temperature | Tank liquid temperature | -9.9~+9.9 relative to standard temperature (0.0 at factory shipment) | 5~50 | Room temperature or aircraft temperature (Factory setting is room temperature: Mode 4) | ON timer: 1~999 hours (set in 1 hour increments) | With heater | 0.5~200 | 5~40 | 5~45 | 5~50 |
Click on the part number for more information about each product