■Product overview

Analog signal converters convert analog signals (temperature to voltage, etc.) to connect control equipment (sequencers) and devices (sensors, etc.). Various sensor information can be easily visualized (small-scale IoT).

■Features 1.

Thick wires such as compensation conductors can be connected directly.

■Features 2.

Various output modules can be mixed together due to channel isolation.

■Feature 3.

There is no loosening caused by vibration, and there is no need to retighten during periodic inspections.

■Feature 4.

Push-in connection is possible by using ferrule terminals.

■Connection device series

・MELSEC iQ-R ・MELSEC-Q ・MELSEC-L ・MELSEC iQ-F ・MELSEC-F ・CC-Link IE TSN ・CC-Link IE Field ・CC-Link ・Other company's PLC - Computers from various companies are environments where electrical conduction can occur.

■Notes

・*1: Do not use or store in an environment pressurized above atmospheric pressure at an altitude of 0m. If used, it may malfunction. If you wish to use it under pressure, please contact our branch office or agent. ・※2: This product is an open type product. Install it in a panel with a protection structure of UL50 Type 1 IP20 or higher, and use it in the environment listed in the "General specifications." ・*3: Indicates which power distribution section, from the public power distribution network to on-premises machinery, the device is expected to be connected to. Category II applies to equipment that is powered from fixed equipment. The surge voltage for equipment rated up to 300V is 2500V. ・*4: An index that indicates the degree of occurrence of conductive substances in the environment in which the device is used. Pollution degree 2 produces only non-conductive pollution. However, it is an environment where temporary conductivity can occur due to accidental condensation.

  • Product

    Spring clamp terminal type Output type Module mounting base unit FA1-AT1B4Y1TE

Share this product


10+ people viewing


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

1 Models of Spring clamp terminal type Output type Module mounting base unit FA1-AT1B4Y1TE

Image Part Number Price (excluding tax) Overvoltage category *3 Number of slots Unit installation: DIN rail Unit installation: screw installation Operating ambient temperature Ambient humidity Usage altitude *1 Usage atmosphere Storage ambient temperature Storage ambient humidity External power supply Connected equipment Pollution degree *4 Current consumption (DC24V) Purpose Terminal block type Terminal block: Applicable wire When using ferrule terminal Terminal block: Applicable wire When ferrule terminal is not used Terminal block: Wire strip length Deadline Dielectric strength voltage, insulation resistance Vibration resistance (if there is intermittent vibration) 5-8.4Hz Vibration resistance (if there is intermittent vibration) 8.4~150Hz Vibration resistance (if there is intermittent vibration) Number of sweeps Vibration resistance (when there is continuous vibration) 5-8.4Hz Vibration resistance (when there is continuous vibration) 8.4~150Hz Shockproof Product classification Installation location *2 Mass
Spring clamp terminal type Output type Module mounting base unit FA1-AT1B4Y1TE-Part Number-FA1-AT1B4Y1TE

FA1-AT1B4Y1TE

$ 97.50〜

II or below

4

Compatible DIN rail: TH35-7.5Fe, TH35-7.5Al (conforms to JIS C 2812)

M4×0.7mm×27mm or more Tightening torque range: 78~118N・cm (8~12kgf・cm)

0~55℃

5-95%RH (non-condensing)

2,000m or less

No corrosive gas

-25~75℃

5-95%RH (non-condensing)

DC24V+-10%

Sequencer

2 or less

6mA or less (excluding module current consumption)

Wiring-saving/man-hour saving equipment

Spring clamp terminal type

Stranded wire: 0.25~1.5mm^2 (AWG24-16)

Stranded wire, solid wire: 0.2~1.5mm^2 (AWG24-16)

10mm

〇 (prepared product)

Between input, output, and power supply: AC500V for 1 minute, 10MΩ or more

Single amplitude 3.5mm

Acceleration 9.8m/s^2

10 times each in X, Y, and Z directions

Single amplitude 1.75mm

Acceleration 4.9m/s^2

147m/s^2, 3 times each in X, Y, and Z directions (JIS B 3502, IEC61131-2 compliant)

Analog signal converter

Inside the control panel (indoor use)

Approximately 160g

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Signal Converters Products

Other products of Mitsubishi Electric Engineering Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Mitsubishi Electric Engineering Co., Ltd.

About Company Handling This Product

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2025 Metoree