All Categories
History
Product
River management products Water intake automatic control deviceHandling Company
Densei Comtech Co., Ltd.Categories
Image | Part Number | Price (excluding tax) | Earthquake resistance | Insulation resistance (between electric circuit and ground) | Environmental conditions Relative humidity | Environmental conditions Surrounding environment | Environmental conditions Ambient temperature | Scalability | Commercial frequency withstand voltage (between electrical circuits and ground) | Reliability Equipment and component configuration | Reliability Signal error control | Reliability Fail-safe/Fool-proof | Reliability System diagnosis | Reliability Surge protection |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Water intake automatic control device |
Available upon quote |
Device that can withstand static acceleration of 1.5G in installed state |
Equipment rated voltage 30V or less: 5MΩ or more with DC100V megger |
Indoor: 30%~80% |
Indoor: General switchboard room level |
Indoor:+5℃~+40℃ |
Devices are decentralized by function and designed to make it easy to expand devices, add functions, and make changes. |
Equipment rated voltage 30V or less: AC500V 1 minute |
Minimum number of parts required |
Countermeasures against erroneous control output using parity, constant mark verification, etc. |
Functional design to shift to the safe side in the event of equipment abnormality or operator error |
Implements a diagnostic function to detect abnormal conditions in the device |
Insulation measures against external surge using photocouplers etc. |