About This Product

■Features

The Dräger Polytron®8700IR is a high-performance explosion-proof detector and alarm for detecting flammable gases at the Lower Explosive Limit (LEL). It is equipped with a high-performance infrared Dräger PIR7000 sensor for quick detection of the most common hydrocarbon gases. In addition to the 3-wire 4-20mA analog output with relay, HART®, Modbus and various fieldbuses are also available, allowing for integration into any control system.

■Dräger PIR7000 - highly efficient, stable and robust

Dräger PIR7000 Featuring an efficient and stable 316L stainless steel housing and a drift-free optical measurement system, the Dräger PIR7000 is designed to adapt to the harshest industrial environments such as offshore installations. Masu. Featuring a unique double-compensated four-beam measurement system, the sensor is resistant to dust and dirt buildup on the optical element surface, environmental and aging effects, and long-term drift. When combined with Polytron8700, up to 100 gases can be registered in the gas library, providing flexibility for a variety of applications. Gases registered in the library list can be selected from the menu and automatically cross-calibrated using standard calibration gases such as methane and propane. There is no need to contact the factory even if the application changes.

■Easy device management using digital communication

The digital interface on the Dräger Polytron 8700 allows for quick and easy remote assessment of the status of detector alarms. You can also integrate with existing asset management systems such as PACTware via DTM. In addition to the standard HART® communication system, it also supports PROFIBUS PA, FOUNDATION Fieldbus H1, and Modbus RTU fieldbus interfaces.

  • Product

    Flammable gas and vapor detection alarm Polytron®8700IR

Share this product


50+ people viewing

Last viewed: 1 hour ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

1 Models of Flammable gas and vapor detection alarm Polytron®8700IR

Image Part Number Price (excluding tax) Electrical data Analog signal output Certification Classification Certification Performance Certification Certification UL Certification SIL 2 certification by TUEV Sued Certification MED approval Certification CSA Certification CE mark Display Environmental conditions Measuring range Performance characteristics Accuracy Repeatability Performance characteristics Response time Power supply Relay specification options Housing Case protection type Housing Indicator and alarm unit housing Housing cable connection Digital signal output Type Sensor housing Gas
Flammable gas and vapor detection alarm Polytron®8700IR-Part Number-Polytron®8700IR

Polytron®8700IR

Available upon quote

・Normal operation 4~20mA, 3 or 4 wire, sink or source connection
・Maintenance Constant current 3.4mA or 4mA±1mA 1Hz modulation (adjustable)
・Failure <1.2mA

・DNV GL
・ABS
・LR
・CCS
・RMRS

Certification number BVS 13 ATEX G 001 X

・Class I, Division 1, Groups A, B, C, D
・Class II, Division 1, Groups E, F, G
・Class I, Division 1, Groups E, F, G
・Temperature class T6/T4

Certificate number Z10 17 05 53474 023

Certification number MEDB0000411

・Class I, Division 1, Groups A, B, C, D
・Class II, Division 1, Groups E, F, G
・Temperature class T6/T4
・CSA C22.2 No.152

・ATEX (Directive 2014/34/EU)
・Electromagnetic compatibility (Directive 2014/30/EU)
・Low voltage (Directive 2014/35/EU)

Backlit graphic LCD 3 status LEDs (green/yellow/red)

・Temperature -40~65℃ (without relay), -40~65℃ without relay
・Pressure 700~1,300mbar
・Humidity 0%~100%R.H.No condensation

・Methane, propane, ethylene 0~20...100%LEL
・Methane 0~100Vol.%

・Sensitivity ≤±1%LEL
・Long-term drift ≤±1%LEL (after 12 months)

T90 4 seconds (without splash guard)

10~30V DC

・2 alarm relays
・1 point failure relay
・Single pole double throw contact 5A@230VAC, 5A@30VDC
・Contact resistance

・NEMA 4X&7
・IP65/66/67

・Copper-free aluminum coated with epoxy resin
・Or SS316 L stainless steel

・3/4”NPT screw
・Or M20 cable gland

・HART® (3 or 4 wire)
・PROFIBUS® PA
・FOUNDATION fieldbus™H1 and Modbus RTU (4-wire)

・Flameproof explosion-proof type "d" model
・Or "d/e" model combined with increased safety explosion-proof type

SS316 L Stainless Steel

Flammable gases and vapors

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Gas Sensors Products

Other products of Dräger

Reviews shown here are reviews of companies.


View more products of Dräger

About Company Handling This Product

Response Rate

100.0%


Response Time

2.8hrs

Company Overview

Dräger, established in 1889, and headquartered in Lübeck, Germany, is a manufacturer and supplier of advanced ...

See More

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree