Product
Automatic reset type breaker device with built-in high-performance lightning protection unit Automatic power supply lightning protection device (for areas with severe lightning, stainless steel casing)Handling Company
Morinaga Electronics Co., Ltd.Categories
Product Image | Part Number | Price (excluding tax) | Appearance/Structure | Appearance/Structure Dimensions | Appearance/Structure Material | Appearance/Structure Paint color | Automatic reset breaker section Automatic reset time | Automatic reset breaker section power consumption | Automatic reset breaker section rated voltage | Automatic return breaker section Lightning resistance of control circuit | Automatic return breaker section Permanent cutoff judgment conditions | Automatic return breaker section operation count | Automatic return breaker section rated current | Dielectric strength | Environment | Insulation resistance | Lightning arrester unit for power supply Surge energy attenuation amount | Lightning protection unit for power supply Applicable line | Lightning protection unit for power supply method | Power supply lightning protection unit maximum discharge current (Imax) | Power supply lightning protection unit operation speed | Power supply lightning protection unit residual surge energy | Power supply lightning protection unit test class | Rated voltage/current | Voltage drop in lightning protection unit for power supply | Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ALPS-ACB-N15 |
Available upon quote | Outdoor wall-mounted type | W300×H430×D200 (mm) | SUS304t1.5 | Munsell 5Y7/1 | After tripping, 5 seconds ± 1 second |
Standby: AC100V, 20mA or less During recovery operation: AC100V, instantaneous maximum 2.5A |
1φ2W, AC100V±10% (50/60Hz) |
Residual surge energy: 5mJ or less (at nominal discharge current) Surge attenuation: -56dB or more Maximum discharge current: 5KA (at 8/20μs) Operating speed: 3nsec. or less |
Permanent shutdown at one time 3 seconds ± 1 second Permanent shutdown for 3 times 10 seconds ± 2 seconds |
Counts and displays the number of operations | 15A (30AF) |
AC2000V, 1 minute (However, excluding the lightning protection unit part) |
Temperature -10℃~50℃ Humidity 85% or less |
50MΩ or more at DC500V (However, excluding the lightning protection unit part) |
-58dB or more (at nominal discharge current) | 1φ2W, AC100V, 20A | Surge energy attenuation method | 20kA (at 8/20μs) | 3nsec. or less | 3mJ or less (at nominal discharge current) | Class II and Class III | 1Φ2W, AC100V, 15A | 0.5V or less | Approximately 13kg |