Product
High-speed line lightning protection unit For power supply, compatible with 2A to 50A of AC power supply and DC power supply ALPK-VNJ (for power supply/DC power supply)Handling Company
Morinaga Electronics Co., Ltd.Categories
Usage Scenarios
Architecture & Construction Use / Electronics & Electrical Use / Energy Industry UseProduct Image | Part Number | Price (excluding tax) | Applicable line | Deterioration display output | Dielectric strength | Exam class | External dimensions | Insertion loss | Insulation resistance | Maximum continuous working voltage (Uc) | Maximum discharge current (Imax/Itotal) | Method | Nominal discharge current (In) | Open circuit voltage (Uoc) | Operating speed | Protection mode | Rated load current (IL) | Residual surge energy | Separator | Surge energy attenuation | Usage environment | Voltage drop | Voltage protection level (Up) | Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ALPK-VNJ2P (PWD0212) |
Available upon quote | DC12V, 2A power line |
Display...When normal: status lamp lights up, when deteriorated: status lamp goes off Output... Normal: ON, Degraded: OFF, Output rating: AC250V, 2A or less |
AC2,200V, 1 minute (between all input/output terminals and frame) | Class II and Class III | W95×H80×D139 (mm) | 1VA or less | DC500V, 50MΩ or more (between all input/output terminals and frame) | DC18V | 20kA/40kA (8/20μs) | Surge energy attenuation method | 10kA (8/20μs) | 10kV (1.2/50μs) | 3nsec. or less | L-L (Line-Line) L-E (Line-Earth) L-N (Line-Neutral) | 2A |
Full protection mode: 1mJ or less *At nominal discharge current (In) and open circuit voltage (Uoc) |
Built-in |
Full protection mode: -63dB or more *At nominal discharge current (In) and open circuit voltage (Uoc) |
Temperature -40~+70℃, humidity 95% or less (no condensation) | 0.5V or less |
Full protection mode: 500V or less *At nominal discharge current (In) and open circuit voltage (Uoc) |
Approximately 1.2kg |