■Features

- 14 digital input points, 2 pulse input points, 2 analog input points, 14 digital output points, 2 pulse output points, 2 analog output points, and I/O input and output ratio is 1:1. Therefore, a small telemeter/telecontroller can be easily constructed by simply installing this unit at the master station and slave stations. - By connecting an external modem, it can also be used as a conventional analog line telemeter/telecon. ・We will publish the standard upper-level communication protocol for the LAN interface, so customers can freely create upper-level application software. ・This machine supports software customization for each customer, so it can flexibly respond to system construction with special communication rules.

  • Product

    IP compatible telemeter IPT602A

Share this product


20+ people viewing

Last viewed: 1 minute ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

1 Models of IP compatible telemeter IPT602A

Image Part Number Price (excluding tax) Insulation voltage Insulation resistance Leakage current Power consumption Minimum detection width Surrounding environment Applied voltage/current Number of output points Output format Output rating Output pulse conditions Input power Number of input quantities Number of input points Input conditions Input method Input pulse conditions Storage humidity Storage temperature Operating humidity Operating temperature Pulse output (PO) number of output points Pulse output (PO) output format Pulse output (PO) output rating Pulse input (PI) applied voltage/current Pulse input (PI) number of input points Pulse input (PI) input conditions Pulse input (PI) input method Digital output (DO) output rating Analog input (AI) input type
IP compatible telemeter IPT602A-Part Number-IPT602A

IPT602A

Available upon quote

Input power supply ~FG AC2,000V for 1 minute
DI/DO signal batch ~FG AC2,000V 1 minute
AI signal batch ~ FG DC500V 1 minute

Input power supply ~FG 10MΩ or more with DC500V megger
DI/DO signal batch ~ FG 10MΩ or more with DC500V megger
AI signal batch ~ FG 10MΩ or more with DC500V megger

1mA or less

25 VA or less

50ms

No corrosive gases
Dust: 0.1mg/m3 or less, no conductive dust
Not exposed to wind and rain

DC12V, 5mA/1 point

14 points (common)

Isolated non-voltage A contact output using semiconductor relay

DC50V, 100mA or less

Output pulse width 50ms±10ms
Output pulse interval 50ms or more

AC100V±15% 50/60Hz

2 quantities (common independent)

14 points (common)

Voltage-free contact or open collector

Isolated input by photocoupler

Input pulse width 50ms or more
Input pulse interval 50ms or more

20~90%RH (no condensation)

-20~+55℃

30~90%RH (no condensation)

-10~+55℃

2 points (common)

Isolated non-voltage A contact output using semiconductor relay

DC50V, 100mA or less

DC12V, 5mA/1 point

2 points (common)

Voltage-free contact or open collector

Isolated input by photocoupler

DC50V, 100mA or less

0~±5V, 1~5V, 4~20mA (voltage/current switching depending on settings)