All Categories
History
Response Rate
100.0%
Response Time
32.5hours
Relatively Fast Response
Product
Liquid Cooler LCP Inline CW/CWGHandling Company
Rittal GmbH & Co. KGCategories
Click on the part number for more information about each product
Image | Part Number | Price (excluding tax) | Height (mm) | Air volume (unobstructed flow) | Power connection | Applicable enclosure type | Installed in applicable enclosure | Water temperature (℃) | Mass/pack (kg) | Maximum permissible pressure (p max) | Total cooling capacity / number of fan modules | Fans can be replaced even during operation | Temperature control | Water pipe connection | Material | Maximum cooling capacity | Width (mm) | Rated voltage | Depth (mm) | Paint color | Coolant | Protection class according to EN 60 529 | Specification | Duty cycle (%) | Number of fans | EC fan | 1 pack (pieces) | About the product number |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
SK 3314.530 |
Available upon quote |
2,000 |
For 50 Hz: 4,800 m^3/h |
Connection connector |
VX IT |
Drawer forward |
15 |
230 |
10 bar |
10 kW/1, 20 kW/2, 30 kW/3 |
Yes |
Stepless fan control, 2-way control ball valve |
DN 40 (G 1½ inch male thread) |
Enclosure: Steel plate, Front door: Aluminum, anodized/painted |
30kW |
300 |
200 V~240 V, single phase, 50 Hz/60 Hz, 346 V – 415 V, 3~, 50 Hz/60 Hz |
1,200 |
Enclosure: RAL 7035, front door: vertical profile (frame) silver, horizontal profile (frame) RAL 9005 |
Water resistance |
IP10B |
Row-wise cooling, CW |
100 |
1 |
Yes |
1 |
The optimized condensed water treatment function is effective even when the outbound water temperature is low. |
|
SK 3314.540 |
Available upon quote |
2,000 |
For 50 Hz: 5,000 m^3/h |
Connection connector |
VX IT |
One side |
15 |
220 |
10 bar |
18 kW/2, 27 kW/3, 30 kW/4 |
Yes |
Stepless fan control, 2-way control ball valve |
DN 40 (G 1½ inch male thread) |
Enclosure: Steel plate, Front door: Aluminum, anodized/painted |
30kW |
300 |
200 V~240 V, single phase, 50 Hz/60 Hz, 346 V – 415 V, 3~, 50 Hz/60 Hz |
1,200 |
Enclosure: RAL 7035, front door: vertical profile (frame) silver, horizontal profile (frame) RAL 9005 |
Water resistance |
IP10B |
Row-wise cooling, CW |
100 |
2 |
Yes |
1 |
The optimized condensed water treatment function is effective even when the outbound water temperature is low. |
|
SK 3314.542 |
Available upon quote |
2,200 |
For 50 Hz: 5,000 m^3/h |
Connection connector |
VX IT |
One side |
15 |
240 |
10 bar |
18 kW/2, 27 kW/3, 30 kW/4 |
Yes |
Stepless fan control, 2-way control ball valve |
DN 40 (G 1½ inch male thread) |
Enclosure: Steel plate, Front door: Aluminum, anodized/painted |
30kW |
300 |
200 V~240 V, single phase, 50 Hz/60 Hz, 346 V – 415 V, 3~, 50 Hz/60 Hz |
1,200 |
Enclosure: RAL 7035, front door: vertical profile (frame) silver, horizontal profile (frame) RAL 9005 |
Water resistance |
IP10B |
Row-wise cooling, CW |
100 |
2 |
Yes |
1 |
The optimized condensed water treatment function is effective even when the outbound water temperature is low. |
|
SK3314.550 |
Available upon quote |
2,000 |
For 50 Hz: 5,000 m^3/h |
Connection connector |
VX IT |
One side |
15 |
280 |
10 bar |
20 kW/2, 31 kW/3, 35 kW/4 |
Yes |
Stepless fan control, 2-way control ball valve |
DN 40 (G 1½ inch male thread) |
Enclosure: Steel plate, Front door: Aluminum, anodized/painted |
28kW |
300 |
200 V~240 V, single phase, 50 Hz/60 Hz, 346 V – 415 V, 3~, 50 Hz/60 Hz |
1,200 |
Enclosure: RAL 7035, front door: vertical profile (frame) silver, horizontal profile (frame) RAL 9005 |
Water-glycol |
IP10B |
Row-wise cooling, CWG |
100 |
2 |
Yes |
1 |
- | |
SK 3314.560 |
Available upon quote |
2,000 |
For 50 Hz: 8,000 m^3/h |
Connection connector |
VX IT |
Drawer forward |
15 |
260 |
10 bar |
48 kW/4, 51 kW/5, 53 kW/6 |
Yes |
Stepless fan control, 2-way control ball valve |
DN 40 (G 1½ inch male thread) |
Enclosure: Steel plate, Front door: Aluminum, anodized/painted |
53kW |
300 |
200 V~240 V, single phase, 50 Hz/60 Hz, 346 V – 415 V, 3~, 50 Hz/60 Hz |
1,200 |
Enclosure: RAL 7035, front door: vertical profile (frame) silver, horizontal profile (frame) RAL 9005 |
Water resistance |
IP10B |
Row-wise cooling, CW |
100 |
4 |
Yes |
1 |
The optimized condensed water treatment function is effective even when the outbound water temperature is low. |
|
SK 3314.570 |
Available upon quote |
2,000 |
For 50 Hz: 6,800 m^3/h |
Connection connector |
VX IT |
Drawer forward |
15 |
280 |
10 bar |
38 kW/4, 40 kW/5, 44 kW/6 |
Yes |
Stepless fan control, 2-way control ball valve |
DN 40 (G 1½ inch male thread) |
Enclosure: Steel plate, Front door: Aluminum, anodized/painted |
35kW |
300 |
200 V~240 V, single phase, 50 Hz/60 Hz, 346 V – 415 V, 3~, 50 Hz/60 Hz |
1,200 |
Enclosure: RAL 7035, front door: vertical profile (frame) silver, horizontal profile (frame) RAL 9005 |
Water-glycol |
IP10B |
Row-wise cooling, CWG |
100 |
4 |
Yes |
1 |
- |
Click on the part number for more information about each product
Reviews shown here are reviews of companies.
Reviews shown here are reviews of companies.