All Categories

History

Liquid cooling equipment LCP Rack CW, LCP Rack CWG-SK 3313.238
Liquid cooling equipment LCP Rack CW, LCP Rack CWG-Rittal GmbH & Co. KG

Liquid cooling equipment LCP Rack CW, LCP Rack CWG
Rittal GmbH & Co. KG

Rittal GmbH & Co. KG's Response Status

Response Rate

100.0%

Response Time

32.5hours

Relatively Fast Response


About This Product

■Summary

Cooling with high performance compact resistors. The LCP (Liquid Cooling Package) exhausts air from the rear side of the server enclosure and injects cooled air into the front side of the server rack. *This is a made-to-order product (special order available). This product is not listed in the latest general catalog.

■Advantages

・Maximum energy efficiency thanks to EC fan technology and IT-oriented control technology - Low pressure loss on the air side, which minimizes fan energy consumption ・Control of server inlet air temperature ・Equipped with a redundant temperature sensor on the air side as standard ・Demonstrates the best adaptability through dynamic continuous control of chilled water flow rate. ・Since the water supply temperature is set high, the proportion of indirect natural cooling increases, thereby reducing operating costs. - Modular fan units provide cooling capacity that adapts to your needs. -Fan modules can be configured in n+1 redundant configuration ・Since the cooling system and enclosure are separated, there is no possibility of water entering the server enclosure. ・Supports all cooling capacities with floor space (installation area) of up to 0.36 m^2 When using the L/CP CW glycol type, the return water temperature will be higher, improving the heat recovery rate. For example, when used in conjunction with a heat pump. ・Good accessibility from front and rear makes maintenance and after-sales service easier. ・No tools required to replace fan module

■Function method

The LCP (Liquid Cooling Package) draws air from the rear side of the server rack, cools it through a high-performance compact register (heat exchanger), and blows the cooled air from the side to the front of the server rack.

■Options

・Fully integrated fire detection and extinguishing system ・Server rack automatic door ・CMC III sensors can be added by direct connection ・Rack height 2,200 mm

■Monitoring

Monitoring of system-related parameters such as server intake and exhaust temperatures, water supply and return water temperatures, once-through water, cooling output, fan speed and leaks ・Direct connection of SNMP devices via Ethernet ・Integration into RiZone

  • Product

    Liquid cooling equipment LCP Rack CW, LCP Rack CWG

Share this product


60+ people viewing

Last viewed: 14 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

2 Models of Liquid cooling equipment LCP Rack CW, LCP Rack CWG

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Height (mm) Air volume (unobstructed flow) Power connection Applicable enclosure type Installed in applicable enclosure Water temperature (℃) Mass/pack (kg) Maximum permissible pressure (p max) Surface Total cooling capacity / number of fan modules Temperature control Water pipe connection Material Maximum cooling capacity Width (mm) Rated voltage Depth (mm) Paint color Coolant Protection class according to EN 60 529 Specification Duty cycle (%) Number of fans 1 pack (pieces)
Liquid cooling equipment LCP Rack CW, LCP Rack CWG-Part Number-SK 3313.238

SK 3313.238

Available upon quote

2,000

For 60 Hz: 6,500 m^3/h

Connection connector

VX IT, TS IT PRO

One side

15

230

10 bar

RAL 9005, fine texture (matte finish)

10 kW/1, 20 kW/2, 30 kW/3

Stepless fan control, 2-way control ball valve

DN 40 (G 1½ inch male thread)

Steel plate, painted

30kW

300

200 V~240 V, single phase, 50 Hz/60 Hz, 200~240 V AC

1,200

RAL 9005

Water resistance

IP20

C.W.

100

4

1

Liquid cooling equipment LCP Rack CW, LCP Rack CWG-Part Number-SK 3313.268

SK 3313.268

Available upon quote

2,000

For 60 Hz: 8,000 m^3/h

Connection connector

VX IT, TS IT PRO

One side

15

260

10 bar

RAL 9005, fine texture (matte finish)

48 kW/4, 51 kW/5, 53 kW/6

Stepless fan control, 2-way control ball valve

DN 40 (G 1½ inch male thread)

Steel plate, painted

53kW

300

200 V~240 V, single phase, 50 Hz/60 Hz, 200~240 V AC

1,200

RAL 9005

Water resistance

IP20

C.W.

100

6

1

Click on the part number for more information about each product

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Server Racks Products

Other products of Rittal GmbH & Co. KG

Reviews shown here are reviews of companies.


View more products of Rittal GmbH & Co. KG

About Company Handling This Product

Response Rate

100.0%


Response Time

32.5hrs

Company Overview

Rittal is a German manufacturer of electrical enclosures and related products that was established in Herborn,...