All Categories

History

Liquid cooling equipment LCP rack DX, LCP rack DX/FC-SK 3313.290
Liquid cooling equipment LCP rack DX, LCP rack DX/FC-SK 3313.410
Liquid cooling equipment LCP rack DX, LCP rack DX/FC-SK 3313.420
Liquid cooling equipment LCP rack DX, LCP rack DX/FC-Rittal GmbH & Co. KG

Liquid cooling equipment LCP rack DX, LCP rack DX/FC
Rittal GmbH & Co. KG

Rittal GmbH & Co. KG's Response Status

Response Rate

100.0%

Response Time

32.5hours

Relatively Fast Response


About This Product

■Summary

Rack-based cooling for one or two IT racks. The cooling capacity is continuously adapted by a variable power compressor in the LCP rack DX (evaporator). An external condenser is required to operate the unit.

■Advantages

・Maximum energy efficiency thanks to EC fan technology and IT-oriented control technology - Low pressure loss on the air side, which minimizes fan energy consumption ・Control of server inlet air temperature - Inverter-controlled compressors match cooling capacity to demand. ・Equipped with a redundant temperature sensor on the air side as standard - When performing LCP DX-specific maintenance, separate the server enclosure and cooling device.

■Function method

・LCP (Liquid Cooling Package) sucks air from the rear side of the server rack, cools it through a high-performance compact register (heat exchanger), and blows the cooled air from the side to the front of the server rack. -The absorbed thermal energy is released around the condenser outside, so there is no temperature rise in the installation room.

■Options

・Humidification device ・Dehumidification and additional heating equipment ・Condensed water pump ・Low temperature condenser / high temperature condenser (-40 ℃ / +53 ℃)

  • Product

    Liquid cooling equipment LCP rack DX, LCP rack DX/FC

Share this product


190+ people viewing

Last viewed: 12 hours ago


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

3 Models of Liquid cooling equipment LCP rack DX, LCP rack DX/FC

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Height (mm) Noise level Air volume (unobstructed flow) Power connection Applicable fuse Applicable enclosure type Installed in applicable enclosure Mass/pack (kg) Adjustment range (kW) Total cooling capacity according to DIN EN 14511 Total cooling capacity / number of fan modules Fans can be replaced even during operation Purpose Temperature control Material Maximum cooling capacity Width (mm) Rated current maximum Rated voltage Depth (mm) Operating temperature range Protection class according to EN 60 529 Storage temperature range Specification Monitoring Duty cycle (%) SNMP card EC fan 1 pack (pieces) Starting current (LRA)
Liquid cooling equipment LCP rack DX, LCP rack DX/FC-Part Number-SK 3313.290

SK 3313.290

Available upon quote

2,000

At 50 Hz: 68 dB (A)

For 50 Hz: 4,800 m^3/h

Terminal block wiring method

-

VX IT

One side

201

5-20

Effective cooling capacity L22 L35: 20 kW

20kW/4

Yes

Ideal for cooling small and medium-sized server rooms. One or two racks can be cooled separately.

Stepless fan control, inverter controlled compressor

Steel plate, painted

20kW

300

At 50 Hz: 12.4 A

380 V~480 V, three phase, 50 Hz/60 Hz

1,200

5℃...35℃

IP20

-

DX

Direct connection of SNMP equipment via Ethernet. Integration into RiZone

100

Yes

Yes

1

32A

Liquid cooling equipment LCP rack DX, LCP rack DX/FC-Part Number-SK 3313.410

SK 3313.410

Available upon quote

2,000

At 50 Hz: 68 dB (A)

For 50 Hz: 4,800 m^3/h

Terminal block wiring method

Circuit breaker/blow type fuse: 20 A

VX IT

One side

181

3-12

Useful cooling output L22 L35: 12 kW, Useful cooling output L22 L45: 10 kW

12kW/4

Yes

Ideal for cooling small and medium-sized server rooms. One or two racks can be cooled separately.

Stepless fan control, inverter controlled compressor

-

12kW

300

At 50Hz: 7.5A

380 V~480 V, three phase, 50 Hz/60 Hz

1,000

5℃...35℃

IP20

-20℃...50℃

DX

Direct connection of SNMP equipment via Ethernet. Integration into RiZone

100

Yes

Yes

1

-
Liquid cooling equipment LCP rack DX, LCP rack DX/FC-Part Number-SK 3313.420

SK 3313.420

Available upon quote

2,000

At 50 Hz: 68 dB (A)

For 50 Hz: 4,800 m^3/h

Terminal block wiring method

Circuit breaker/blow type fuse: 20 A

VX IT

One side

201

3-12

Useful cooling output L22 L35: 12 kW, Useful cooling output L22 L45: 10 kW

12kW/4

Yes

Ideal for cooling small and medium-sized server rooms. One or two racks can be cooled separately.

Stepless fan control, inverter controlled compressor

Steel plate, painted

12kW

300

At 50Hz: 7.5A

380 V~480 V, three phase, 50 Hz/60 Hz

1,200

5℃...35℃

IP40

-20℃...50℃

DX

Direct connection of SNMP equipment via Ethernet. Integration into RiZone

100

Yes

Yes

1

-

Click on the part number for more information about each product

Customers who viewed this product also viewed

Reviews shown here are reviews of companies.

See More Server Racks Products

Other products of Rittal GmbH & Co. KG

Reviews shown here are reviews of companies.


View more products of Rittal GmbH & Co. KG

About Company Handling This Product

Response Rate

100.0%


Response Time

32.5hrs

Company Overview

Rittal is a German manufacturer of electrical enclosures and related products that was established in Herborn,...

See More

  • Germany

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2025 Metoree