All Categories
History
Response Rate
100.0%
Response Time
32.5hours
Relatively Fast Response
Product
Liquid cooling equipment LCP rack DX, LCP rack DX/FCHandling Company
Rittal GmbH & Co. KGCategories
Click on the part number for more information about each product
Image | Part Number | Price (excluding tax) | Height (mm) | Noise level | Air volume (unobstructed flow) | Power connection | Applicable fuse | Applicable enclosure type | Installed in applicable enclosure | Mass/pack (kg) | Adjustment range (kW) | Total cooling capacity according to DIN EN 14511 | Total cooling capacity / number of fan modules | Fans can be replaced even during operation | Purpose | Temperature control | Material | Maximum cooling capacity | Width (mm) | Rated current maximum | Rated voltage | Depth (mm) | Operating temperature range | Protection class according to EN 60 529 | Storage temperature range | Specification | Monitoring | Duty cycle (%) | SNMP card | EC fan | 1 pack (pieces) | Starting current (LRA) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
![]() |
SK 3313.290 |
Available upon quote |
2,000 |
At 50 Hz: 68 dB (A) |
For 50 Hz: 4,800 m^3/h |
Terminal block wiring method |
- |
VX IT |
One side |
201 |
5-20 |
Effective cooling capacity L22 L35: 20 kW |
20kW/4 |
Yes |
Ideal for cooling small and medium-sized server rooms. One or two racks can be cooled separately. |
Stepless fan control, inverter controlled compressor |
Steel plate, painted |
20kW |
300 |
At 50 Hz: 12.4 A |
380 V~480 V, three phase, 50 Hz/60 Hz |
1,200 |
5℃...35℃ |
IP20 |
- |
DX |
Direct connection of SNMP equipment via Ethernet. Integration into RiZone |
100 |
Yes |
Yes |
1 |
32A |
![]() |
SK 3313.410 |
Available upon quote |
2,000 |
At 50 Hz: 68 dB (A) |
For 50 Hz: 4,800 m^3/h |
Terminal block wiring method |
Circuit breaker/blow type fuse: 20 A |
VX IT |
One side |
181 |
3-12 |
Useful cooling output L22 L35: 12 kW, Useful cooling output L22 L45: 10 kW |
12kW/4 |
Yes |
Ideal for cooling small and medium-sized server rooms. One or two racks can be cooled separately. |
Stepless fan control, inverter controlled compressor |
- |
12kW |
300 |
At 50Hz: 7.5A |
380 V~480 V, three phase, 50 Hz/60 Hz |
1,000 |
5℃...35℃ |
IP20 |
-20℃...50℃ |
DX |
Direct connection of SNMP equipment via Ethernet. Integration into RiZone |
100 |
Yes |
Yes |
1 |
- |
![]() |
SK 3313.420 |
Available upon quote |
2,000 |
At 50 Hz: 68 dB (A) |
For 50 Hz: 4,800 m^3/h |
Terminal block wiring method |
Circuit breaker/blow type fuse: 20 A |
VX IT |
One side |
201 |
3-12 |
Useful cooling output L22 L35: 12 kW, Useful cooling output L22 L45: 10 kW |
12kW/4 |
Yes |
Ideal for cooling small and medium-sized server rooms. One or two racks can be cooled separately. |
Stepless fan control, inverter controlled compressor |
Steel plate, painted |
12kW |
300 |
At 50Hz: 7.5A |
380 V~480 V, three phase, 50 Hz/60 Hz |
1,200 |
5℃...35℃ |
IP40 |
-20℃...50℃ |
DX |
Direct connection of SNMP equipment via Ethernet. Integration into RiZone |
100 |
Yes |
Yes |
1 |
- |
Click on the part number for more information about each product
Reviews shown here are reviews of companies.
Reviews shown here are reviews of companies.