Liquid Cooling Package 8 - 20 kW VX25 Toptherm ChillerHandling Company
Rittal GmbH & Co. KGCategories
Click on the part number for more information about each product
Image | Part Number | Price (excluding tax) | Height (mm) | Noise level | Air volume (unobstructed flow) | Starting current (max) | Mass/pack (kg) | Total cooling capacity Tw18 / Tu32 | Total cooling capacity Tw10 / Tu32 | Temperature control | Temperature hysteresis | Power consumption, coolant pump 50/60 Hz | Flow rate (cooling medium) | Note | Water pipe connection | Material | Width (mm) | Rated current maximum | Rated voltage | Rated output Pel | Depth (mm) | Paint color | Included items | Operating mass (kg) | Operating temperature range | Number of cooling circuits | Protection class according to EN 60 529 | Operating temperature range (cooling medium) | Pump pressure | Tank | 1 pack (pieces) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
SK 3335.930 |
Available upon quote |
2,238 |
75.6 dB(A) |
For 50 Hz: 6,000 m^3/h, for 60 Hz: 7,200 m^3/h |
For 50 Hz: 44 A, for 60 Hz: 39.8 A |
248 |
Cooling capacity Tw18 Tu32 / 50 Hz: 8 kW, cooling capacity Tw18 Tu32 / 60 Hz: 8.6 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 6.5 kW, cooling capacity Tw10 Tu32 / 60 Hz: 7.5 kW |
E controller (factory setting +18 ℃) |
± 1K |
0.67/1.06kW |
At 50 Hz: 30 l/min, at 60 Hz: 47 l/min |
Regular airtightness tests are not required by law. |
R 1" inch female thread |
Made of steel plate |
808 |
At 50 Hz: 9.4 A, at 60 Hz: 8.8 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 4.91 kW, for 60 Hz: 5.92 kW |
608 |
RAL 7035 |
Complete pre-wired unit with side panel and door |
323 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
For 50 Hz: 2.5 bar, for 60 Hz: 2.5 bar |
Material: plastic PP, quantity: 75 l |
1 |
|
SK 3335.940 |
Available upon quote |
2,238 |
75.6 dB(A) |
For 50 Hz: 6,000 m^3/h, for 60 Hz: 7,200 m^3/h |
For 50 Hz: 48.8 A, for 60 Hz: 53.5 A |
282 |
Cooling capacity Tw18 Tu32 / 50 Hz: 12 kW, cooling capacity Tw18 Tu32 / 60 Hz: 13.1 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 10.3 kW, cooling capacity Tw10 Tu32 / 60 Hz: 11.3 kW |
E controller (factory setting +18 ℃) |
± 1K |
0.67/1.06kW |
At 50 Hz: 30 l/min, at 60 Hz: 55 l/min |
Regular airtightness tests are not required by law. |
R 1" inch female thread |
Made of steel plate |
808 |
At 50 Hz: 10.2 A, at 60 Hz: 11.1 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 6.41 kW, for 60 Hz: 7.42 kW |
608 |
RAL 7035 |
Complete pre-wired unit with side panel and door |
357 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
For 50 Hz: 2.5 bar, for 60 Hz: 2.5 bar |
Material: plastic PP, quantity: 75 l |
1 |
|
SK 3335.950 |
Available upon quote |
2,238 |
75.6 dB(A) |
For 50 Hz: 6,000 m^3/h, for 60 Hz: 7,200 m^3/h |
At 50 Hz: 65 A, at 60 Hz: 62.8 A |
282 |
Cooling capacity Tw18 Tu32 / 50 Hz: 16 kW, cooling capacity Tw18 Tu32 / 60 Hz: 17.6 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 13.8 kW, cooling capacity Tw10 Tu32 / 60 Hz: 15.2 kW |
E controller (factory setting +18 ℃) |
± 1K |
0.67/1.06kW |
At 50 Hz: 35 l/min, at 60 Hz: 63 l/min |
Regular airtightness tests are not required by law. |
R 1" inch female thread |
Made of steel plate |
808 |
For 50 Hz: 12.9 A, for 60 Hz: 12.6 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 7.11 kW, for 60 Hz: 8.82 kW |
608 |
RAL 7035 |
Complete pre-wired unit with side panel and door |
357 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
For 50 Hz: 2.5 bar, for 60 Hz: 2.5 bar |
Material: plastic PP, quantity: 75 l |
1 |
|
SK 3335.960 |
Available upon quote |
2,238 |
75.6 dB(A) |
For 50 Hz: 6,000 m^3/h, for 60 Hz: 7,200 m^3/h |
For 50 Hz: 102.5 A, for 60 Hz: 102.4 A |
295 |
Cooling capacity Tw18 Tu32 / 50 Hz: 20 kW, cooling capacity Tw18 Tu32 / 60 Hz: 21.8 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 16.6 kW, cooling capacity Tw10 Tu32 / 60 Hz: 18.7 kW |
E controller (factory setting +18 ℃) |
± 1K |
1.35/1.93kW |
At 50 Hz: 43 l/min, at 60 Hz: 76 l/min |
Regular airtightness tests are not required by law. |
R 1" inch female thread |
Made of steel plate |
808 |
For 50 Hz: 20.4 A, for 60 Hz: 20.9 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 10.89 kW, for 60 Hz: 13.49 kW |
608 |
RAL 7035 |
Complete pre-wired unit with side panel and door |
370 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
For 50 Hz: 2.2 bar, for 60 Hz: 3.2 bar |
Material: plastic PP, quantity: 75 l |
1 |