Liquid Cooling Package 1-6 kW Toptherm ChillerHandling Company
Rittal GmbH & Co. KGCategories
Click on the part number for more information about each product
Image | Part Number | Price (excluding tax) | Height (mm) | Air volume (unobstructed flow) | Mass/pack (kg) | Total cooling capacity Tw18 / Tu32 | Total cooling capacity Tw10 / Tu32 | Temperature control | Temperature hysteresis | Water pipe connection | Water circulation path | Width (mm) | Rated current maximum | Rated voltage | Rated output Pel | Depth (mm) | Paint color | Operating temperature range | Number of cooling circuits | Protection class according to EN 60 529 | Operating temperature range (cooling medium) | Specification | Tank | 1 pack (pieces) | Flow rate (cooling medium) | Pump pressure |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
SK 3318.610 |
Available upon quote |
400 |
For 50 Hz: 900 m^3/h, for 60 Hz: 900 m^3/h |
48 |
Cooling capacity Tw18 Tu32 / 50 Hz: 1 kW, cooling capacity Tw18 Tu32 / 60 Hz: 1.1 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 0.8 kW, cooling capacity Tw10 Tu32 / 60 Hz: 0.9 kW |
Microcontroller control (factory setting +20 ℃) |
± 2K |
G ½ inch female thread |
No airtightness |
600 |
For 50 Hz: 5.1 A, for 60 Hz: 5.6 A |
230 V, single phase, 50 Hz/60 Hz |
For 50 Hz: 0.69 kW, for 60 Hz: 1.07 kW |
455 |
RAL 7035 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...30℃ |
Space-saving and modular cooling components, liquid pumps |
Material: plastic PP, quantity: 2.5 l |
1 |
At 50 Hz: 4 l/min, at 60 Hz: 6 l/min |
For 50 Hz: 2.5 bar |
|
SK 3319.610 |
Available upon quote |
400 |
For 50 Hz: 900 m^3/h, for 60 Hz: 900 m^3/h |
51 |
Cooling capacity Tw18 Tu32 / 50 Hz: 1.5 kW, cooling capacity Tw18 Tu32 / 60 Hz: 1.7 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 1.2 kW, cooling capacity Tw10 Tu32 / 60 Hz: 1.3 kW |
Microcontroller control (factory setting +20 ℃) |
± 2K |
G ½ inch female thread |
No airtightness |
600 |
For 50 Hz: 5.7 A, for 60 Hz: 5.6 A |
230 V, single phase, 50 Hz/60 Hz |
For 50 Hz: 0.86 kW, for 60 Hz: 0.99 kW |
455 |
RAL 7035 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...30℃ |
Space-saving and modular cooling components, liquid pumps |
Material: plastic PP, quantity: 2.5 l |
1 |
At 50 Hz: 4 l/min, at 60 Hz: 6 l/min |
For 50 Hz: 2.5 bar |
|
SK 3320.600 |
Available upon quote |
676 |
For 50 Hz: 1,785 m^3/h, for 60 Hz: 1,785 m^3/h |
88 |
Cooling capacity Tw18 Tu32 / 50 Hz: 3 kW, cooling capacity Tw18 Tu32 / 60 Hz: 3.4 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 2.7 kW, cooling capacity Tw10 Tu32 / 60 Hz: 3 kW |
Microcontroller control (factory setting +20 ℃) |
± 2K |
G ½ inch female thread |
Open type |
602 |
For 50 Hz: 4.05 A, for 60 Hz: 4.35 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 2.03 kW, for 60 Hz: 2.67 kW |
645 |
RAL 7035 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...30℃ |
Space-saving and modular cooling components, liquid pumps |
Material: plastic PP, quantity: 30 l |
1 |
- | - | |
SK 3334.600 |
Available upon quote |
676 |
For 50 Hz: 1,785 m^3/h, for 60 Hz: 1,785 m^3/h |
94 |
Cooling capacity Tw18 Tu32 / 50 Hz: 4.5 kW, cooling capacity Tw18 Tu32 / 60 Hz: 5.4 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 3.9 kW, cooling capacity Tw10 Tu32 / 60 Hz: 4.7 kW |
Microcontroller control (factory setting +20 ℃) |
± 2K |
G ½ inch female thread |
Open type |
602 |
For 50 Hz: 5.6 A, for 60 Hz: 6.15 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 2.88 kW, for 60 Hz: 3.24 kW |
645 |
RAL 7035 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...30℃ |
Space-saving and modular cooling components, liquid pumps |
Material: plastic PP, quantity: 30 l |
1 |
- | - |
Click on the part number for more information about each product