All Categories
History
Response Rate
100.0%
Response Time
32.5hours
Relatively Fast Response
Product
Liquid Cooling Package 8-48 kW Blue e ChillerHandling Company
Rittal GmbH & Co. KGCategories
Click on the part number for more information about each product
Image | Part Number | Price (excluding tax) | Height (mm) | Noise level | Air volume (unobstructed flow) | Mass/pack (kg) | Total cooling capacity Tw18 / Tu32 | Total cooling capacity Tw10 / Tu32 | Temperature hysteresis | Flow rate (cooling medium) | Water pipe connection | Width (mm) | Rated current maximum | Rated voltage | Rated output Pel | Depth (mm) | Paint color | Included items | Operating mass (kg) | Operating temperature range | Number of cooling circuits | Protection class according to EN 60 529 | Operating temperature range (cooling medium) | Specification | Tank | 1 pack (pieces) | Precision control | Performance enhanced pump | Control voltage 24V DC | Pump pressure |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
SK 3336.390 |
Available upon quote |
1,185 |
64.9dB(A) |
For 50 Hz: 1,600 m^3/h, for 60 Hz: 2,000 m^3/h |
180 |
Cooling capacity Tw18 Tu32 / 50 Hz: 7.81 kW, cooling capacity Tw18 Tu32 / 60 Hz: 9.34 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 6.02 kW, cooling capacity Tw10 Tu32 / 60 Hz: 7.09 kW |
± 2K |
At 50 Hz: 25 l/min, at 60 Hz: 30 l/min |
R ¾ inch female thread |
655 |
For 50 Hz: 7.6 A, for 60 Hz: 8.16 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 4.18 kW, for 60 Hz: 5.26 kW |
890 |
Enclosure: RAL 7035, Base: RAL 7016 |
Chiller, pre-wired/multilingual documentation including functional diagrams and wiring diagrams |
210 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
Robust according to industrial standards, potential-free contacts for alarm output |
Material: INOX 1.4305, quantity: 30 l |
1 |
- | - | - |
For 50 Hz: 3 bar, for 60 Hz: 4 bar |
|
SK 3336.400 |
Available upon quote |
1,265 |
68 dB(A) |
For 50 Hz: 6,000 m^3/h, for 60 Hz: 7,200 m^3/h |
247 |
Cooling capacity Tw18 Tu32 / 50 Hz: 11.8 kW, cooling capacity Tw18 Tu32 / 60 Hz: 13.2 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 10.2 kW, cooling capacity Tw10 Tu32 / 60 Hz: 11.7 kW |
± 2K |
At 50 Hz: 30 l/min, at 60 Hz: 55 l/min |
R 1" inch female thread |
660 |
For 50 Hz: 10.2 A, for 60 Hz: 11.3 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 6.3 kW, for 60 Hz: 8.8 kW |
1,315 |
Enclosure: RAL 7035, Base: RAL 7016 |
Chiller, pre-wired/multilingual documentation including functional diagrams and wiring diagrams |
316 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
Robust according to industrial standards, potential-free contacts for alarm output |
Material: plastic PE, quantity: 49 l |
1 |
- | - | - |
For 50 Hz: 2 bar, for 60 Hz: 2 bar |
|
SK 3336.405 |
Available upon quote |
1,265 |
68 dB(A) |
For 50 Hz: 6,000 m^3/h, for 60 Hz: 7,200 m^3/h |
247 |
Cooling capacity Tw18 Tu32 / 50 Hz: 11.8 kW, cooling capacity Tw18 Tu32 / 60 Hz: 13.2 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 10.2 kW, cooling capacity Tw10 Tu32 / 60 Hz: 11.7 kW |
± 0.25K |
At 50 Hz: 30 l/min, at 60 Hz: 55 l/min |
R 1" inch female thread |
660 |
At 50 Hz: 11.1 A, at 60 Hz: 13.1 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 6.3 kW, for 60 Hz: 8.8 kW |
1,315 |
Enclosure: RAL 7035, Base: RAL 7016 |
Chiller, pre-wired/multilingual documentation including functional diagrams and wiring diagrams |
316 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
Robust according to industrial standards, potential-free contacts for alarm output |
Material: plastic PE, quantity: 49 l |
1 |
Yes |
Yes |
Yes |
For 50 Hz: 5 bar, for 60 Hz: 7 bar |
|
SK 3336.410 |
Available upon quote |
1,265 |
68 dB(A) |
For 50 Hz: 6,000 m^3/h, for 60 Hz: 7,200 m^3/h |
253 |
Cooling capacity Tw18 Tu32 / 50 Hz: 14.3 kW, cooling capacity Tw18 Tu32 / 60 Hz: 14.8 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 12.2 kW, cooling capacity Tw10 Tu32 / 60 Hz: 12.3 kW |
± 2K |
At 50 Hz: 35 l/min, at 60 Hz: 55 l/min |
R 1" inch female thread |
660 |
For 50 Hz: 12.9 A, for 60 Hz: 12.9 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 7.02 kW, for 60 Hz: 8.75 kW |
1,315 |
Enclosure: RAL 7035, Base: RAL 7016 |
Chiller, pre-wired/multilingual documentation including functional diagrams and wiring diagrams |
322 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
Robust according to industrial standards, potential-free contacts for alarm output |
Material: plastic PE, quantity: 49 l |
1 |
- | - | - |
For 50 Hz: 2 bar, for 60 Hz: 2 bar |
|
SK 3336.415 |
Available upon quote |
1,265 |
68 dB(A) |
For 50 Hz: 6,000 m^3/h, for 60 Hz: 7,200 m^3/h |
253 |
Cooling capacity Tw18 Tu32 / 50 Hz: 14.3 kW, cooling capacity Tw18 Tu32 / 60 Hz: 14.8 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 12.2 kW, cooling capacity Tw10 Tu32 / 60 Hz: 12.3 kW |
± 0.25K |
At 50 Hz: 35 l/min, at 60 Hz: 55 l/min |
R 1" inch female thread |
660 |
For 50 Hz: 13.8 A, for 60 Hz: 14.65 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 7.7 kW, for 60 Hz: 9.9 kW |
1,315 |
Enclosure: RAL 7035, Base: RAL 7016 |
Chiller, pre-wired/multilingual documentation including functional diagrams and wiring diagrams |
302 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
Robust according to industrial standards, potential-free contacts for alarm output |
Material: plastic PE, quantity: 49 l |
1 |
Yes |
Yes |
Yes |
For 50 Hz: 5 bar, for 60 Hz: 7 bar |
|
SK 3336.430 |
Available upon quote |
1,265 |
79 dB(A) |
For 50 Hz: 12,000 m^3/h, for 60 Hz: 14,500 m^3/h |
310 |
Cooling capacity Tw18 Tu32 / 50 Hz: 19.3 kW, cooling capacity Tw18 Tu32 / 60 Hz: 22 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 16.3 kW, cooling capacity Tw10 Tu32 / 60 Hz: 19.2 kW |
± 2K |
At 50 Hz: 45 l/min, at 60 Hz: 75 l/min |
R 1¼" inch female thread |
760 |
At 50 Hz: 19 A, at 60 Hz: 15.9 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 8.5 kW, for 60 Hz: 10.9 kW |
1,515 |
Enclosure: RAL 7035, Base: RAL 7016 |
Chiller, pre-wired/multilingual documentation including functional diagrams and wiring diagrams |
388 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
Robust according to industrial standards, potential-free contacts for alarm output |
Material: plastic PE, quantity: 78 l |
1 |
- | - | - |
For 50 Hz: 2 bar, for 60 Hz: 2 bar |
|
SK 3336.435 |
Available upon quote |
1,265 |
79 dB(A) |
For 50 Hz: 12,000 m^3/h, for 60 Hz: 14,500 m^3/h |
310 |
Cooling capacity Tw18 Tu32 / 50 Hz: 19.3 kW, cooling capacity Tw18 Tu32 / 60 Hz: 22 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 16.3 kW, cooling capacity Tw10 Tu32 / 60 Hz: 19.2 kW |
± 0.25K |
At 50 Hz: 45 l/min, at 60 Hz: 75 l/min |
R 1¼" inch female thread |
760 |
At 50 Hz: 19.9 A, at 60 Hz: 17.2 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 8.5 kW, for 60 Hz: 10.9 kW |
1,515 |
Enclosure: RAL 7035, Base: RAL 7016 |
Chiller, pre-wired/multilingual documentation including functional diagrams and wiring diagrams |
388 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
Robust according to industrial standards, potential-free contacts for alarm output |
Material: plastic PE, quantity: 78 l |
1 |
Yes |
Yes |
Yes |
For 50 Hz: 4.75 bar, for 60 Hz: 6.75 bar |
|
SK 3336.450 |
Available upon quote |
1,265 |
79 dB(A) |
For 50 Hz: 12,000 m^3/h, for 60 Hz: 14,500 m^3/h |
326 |
Cooling capacity Tw18 Tu32 / 50 Hz: 24.4 kW, cooling capacity Tw18 Tu32 / 60 Hz: 26.3 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 19.9 kW, cooling capacity Tw10 Tu32 / 60 Hz: 22.9 kW |
± 2K |
At 50 Hz: 55 l/min, at 60 Hz: 75 l/min |
R 1¼" inch female thread |
760 |
For 50 Hz: 21.7 A, for 60 Hz: 22.4 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 10.6 kW, for 60 Hz: 13.3 kW |
1,515 |
Enclosure: RAL 7035, Base: RAL 7016 |
Chiller, pre-wired/multilingual documentation including functional diagrams and wiring diagrams |
404 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
Robust according to industrial standards, potential-free contacts for alarm output |
Material: plastic PE, quantity: 78 l |
1 |
- | - | - |
For 50 Hz: 2 bar, for 60 Hz: 2 bar |
|
SK 3336.455 |
Available upon quote |
1,265 |
79 dB(A) |
For 50 Hz: 12,000 m^3/h, for 60 Hz: 14,500 m^3/h |
326 |
Cooling capacity Tw18 Tu32 / 50 Hz: 24.4 kW, cooling capacity Tw18 Tu32 / 60 Hz: 26.3 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 19.9 kW, cooling capacity Tw10 Tu32 / 60 Hz: 22.9 kW |
± 0.25K |
At 50 Hz: 55 l/min, at 60 Hz: 75 l/min |
R 1¼" inch female thread |
760 |
At 50 Hz: 22.6 A, at 60 Hz: 24.1 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 11.3 kW, for 60 Hz: 14.4 kW |
1,515 |
Enclosure: RAL 7035, Base: RAL 7016 |
Chiller, pre-wired/multilingual documentation including functional diagrams and wiring diagrams |
404 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
Robust according to industrial standards, potential-free contacts for alarm output |
Material: plastic PE, quantity: 78 l |
1 |
Yes |
Yes |
Yes |
For 50 Hz: 4.5 bar, for 60 Hz: 6.7 bar |
|
SK 3336.460 |
Available upon quote |
1,733 |
78 dB(A) |
For 50 Hz: 12,000 m^3/h, for 60 Hz: 14,500 m^3/h |
470 |
Cooling capacity Tw18 Tu32 / 50 Hz: 32.4 kW, cooling capacity Tw18 Tu32 / 60 Hz: 37.3 kW |
Cooling capacity Tw10 Tu32 / 50 Hz: 28.1 kW, cooling capacity Tw10 Tu32 / 60 Hz: 33.2 kW |
± 2K |
At 50 Hz: 85 l/min, at 60 Hz: 105 l/min |
R 1½ inch female thread |
900 |
For 50 Hz: 22.98 A, for 60 Hz: 24.43 A |
400 V, three phase, 50 Hz, 460 V, three phase, 60 Hz |
For 50 Hz: 12.69 kW, for 60 Hz: 16.15 kW |
1,800 |
Enclosure: RAL 7035, Base: RAL 7016 |
Chiller, pre-wired/multilingual documentation including functional diagrams and wiring diagrams |
660 |
10℃...43℃ |
1 |
IP 44 (electrical system) |
10℃...25℃ |
Robust according to industrial standards, potential-free contacts for alarm output |
Material: stainless steel AISI304 - 1.4301 (V2A), quantity: 185 l |
1 |
- | - | - | - |
Click on the part number for more information about each product
Reviews shown here are reviews of companies.
Reviews shown here are reviews of companies.