All Categories
History
Response Rate
100.0%
Response Time
32.5hours
Relatively Fast Response
Product
LCP Rack Industrial Liquid Cooling SystemHandling Company
Rittal GmbH & Co. KGCategories
Click on the part number for more information about each product
Image | Part Number | Price (excluding tax) | Height (mm) | Noise level | Power connection | Applicable fuse | Water temperature | Mass/pack (kg) | Maximum permissible pressure (p max) | Setting range | Temperature control | Note | Water pipe connection | Width (mm) | Rated current maximum | Rated voltage | Rated output Pel | Depth (mm) | Paint color | Included items | Operating temperature range | Cooling capacity | Coolant | Protection class according to EN 60 529 | Specification | Duty cycle (%) | 1 pack (pieces) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
SK 3378.300 |
Available upon quote |
2,000 |
60dB(A) |
Terminal block wiring method |
Circuit breaker/blow type fuse: 4 A |
7℃...30℃ |
106 |
1 - 6 bar |
20℃...55℃ |
E-Comfort controller (factory setting +35 °C) |
Can be connected by tightening screws from the side |
G ¾ inch female thread |
300 |
For 50 Hz: 2.65 A, for 60 Hz: 2.62 A |
230 V, single phase, 50 Hz/60 Hz |
For 50 Hz: 350 W, for 60 Hz: 350 W |
600 |
RAL 7035 |
Cooling unit ready for connection, wired to terminal block, front door with display, rear panel, documentation translated into multiple languages |
5℃...70℃ |
L 35 W 10 (at 2,000 l/h): 9.5 kW |
Water |
IP55 |
Water piping parts are made of copper/brass (Cu/CuZn) |
100 |
1 |
|
SK 3378.380 |
Available upon quote |
2,000 |
60dB(A) |
Terminal block wiring method |
Circuit breaker/blow type fuse: 4 A |
7℃...30℃ |
115 |
1 - 6 bar |
20℃...55℃ |
E-Comfort controller (factory setting +35 °C) |
Can be connected by tightening screws from the side |
G ¾ inch female thread |
300 |
For 50 Hz: 2.65 A, for 60 Hz: 2.62 A |
230 V, single phase, 50 Hz/60 Hz |
For 50 Hz: 350 W, for 60 Hz: 350 W |
800 |
RAL 7035 |
Cooling unit ready for connection, wired to terminal block, front door with display, rear panel, documentation translated into multiple languages |
5℃...70℃ |
L 35 W 10 (at 2,000 l/h): 9.5 kW |
Water |
IP55 |
Water piping parts are made of copper/brass (Cu/CuZn) |
100 |
1 |