All Categories

History

Insulation resistance monitoring device IRS (9 units monitoring/high-performance version)-IRS-9500
Insulation resistance monitoring device IRS (9 units monitoring/high-performance version)-IRS-9250
Insulation resistance monitoring device IRS (9 units monitoring/high-performance version)-Takenaka Electric Co., Ltd.

Insulation resistance monitoring device IRS (9 units monitoring/high-performance version)
Takenaka Electric Co., Ltd.

Takenaka Electric Co., Ltd.'s Response Status

Response Rate

100.0%

Response Time

14.0hours

Relatively Fast Response


About This Product

Achieves automation of insulation resistance monitoring using a highly accurate megger method. This contributes to preventive maintenance by preventing sudden equipment stoppages and fire accidents due to insulation deterioration. Once installed, measurements are taken automatically, reducing inspection man-hours and preventing electric shock accidents during manual work.

■Product overview

Monitors insulation resistance with the same high accuracy as the Megger method. Automatically monitors the insulation status of various motors mainly installed in machine tools. You can reduce maintenance costs and maintenance inventory costs, and prevent sudden line stoppages in advance. ・Automatic measurement with trigger input ・Because it is a megger method, it is possible to measure values ​​with higher accuracy than the I0r method. - Delay timer allows measurement after the motor has completely stopped ・Detect insulation resistance drop using any judgment value - Compatible with a wide range of devices regardless of device, capacity, or manufacturer ・There is no need to worry about electric shock, and safe measurements are possible. ・Suitable for equipment requiring safety circuits ・Can also be used as a general-purpose inspection device in production factories Introduction effect

■Preventing accidents, fires, and breakdowns due to electrical leakage

It prevents electrical leakage due to deterioration of insulation resistance and protects valuable employees, equipment, and business partners from various troubles.

■Reduction of inspection man-hours

Monitoring is performed automatically, so there is no need for human intervention. It also protects equipment from ``tampering'' during inspections.

■Promotion of DX through data conversion (trend monitoring)

Continuously monitor and record measurements. By categorizing measured values, it is possible to understand trends for each piece of equipment, allowing for early response.

■Application examples

・Insulation measurement of various motors in production equipment ・Insulation measurement of heaters in production equipment, molds, etc. ・Insulation measurement of power generation equipment, etc. ・Simple in-process measurement of parts (products) that require insulation, etc.

  • Product

    Insulation resistance monitoring device IRS (9 units monitoring/high-performance version)

Share this product


100+ people viewing


Free
Get started with our free quotation service - no cost, no obligation.

No Phone Required
We respect your privacy. You can receive quotes without sharing your phone number.

2 Models of Insulation resistance monitoring device IRS (9 units monitoring/high-performance version)

Click on the part number for more information about each product

Image Part Number Price (excluding tax) Power supply voltage Weight Vibration resistance (malfunction) Monitoring equipment power supply voltage Number of monitors Measurement mode Power consumption Safety category External dimensions Control relay mainstay Ambient temperature Operating ambient temperature Overview Others
Insulation resistance monitoring device IRS (9 units monitoring/high-performance version)-Part Number-IRS-9500

IRS-9500

Available upon quote

DC24V (range 20.4V~26.4V)

820g

10~55Hz Single amplitude 0.5mm each direction of XYZ

Upper limit 440V

Up to 9 units

DC500V/0.1~99MΩ

4.8W or less

Class2 (JIS B 9705-1)

W213XH200XD94.2mm

Measuring output/insulation resistance drop output/mechanical failure output
Rated load AC125V0.5A/DC24V1A

-

0~55℃ (No freezing or condensation)

Highly functional version

Modbus (RS-485) compatible
Settings tool (settings, history management) *Free

Insulation resistance monitoring device IRS (9 units monitoring/high-performance version)-Part Number-IRS-9250

IRS-9250

Available upon quote

DC24V (range 20.4V~26.4V)

820g

10~55Hz Single amplitude 0.5mm in each XYZ direction

Upper limit 440V

Up to 9 units

DC250V/0.1~99MΩ

4.8W or less

Class2(JIS B9705-1)

W213XH200XD94.2mm

Measuring output/insulation resistance drop output/mechanical failure output Rated load AC125V0.5A/DC24V1A

0~55℃ (no freezing or condensation)

-

Highly functional version

Modbus (RS-485) compatible configuration tool (settings, history management) *Free

Click on the part number for more information about each product

Other products of Takenaka Electric Co., Ltd.

Reviews shown here are reviews of companies.


View more products of Takenaka Electric Co., Ltd.

About Company Handling This Product

Response Rate

100.0%


Response Time

14.0hrs

  • Japan

This is the version of our website addressed to speakers of English in the United States. If you are a resident of another country, please select the appropriate version of Metoree for your country in the drop-down menu.

Copyright © 2024 Metoree