All Categories
History
Relatively Fast Response
Product
Inverter chiller Reduces the global environment and user burden Non-fluorocarbon inverter chiller with small water tank (air cooling) RKE-C-VRA seriesHandling Company
Meishin Koki Co., Ltd.Categories
Image | Part Number | Price (excluding tax) | Power capacity kVA | Power supply V (Hz) | Current A | Operation control method | Product mass (water tank empty) kg | Power consumption kW | Legal frozen tons | Water tank actual capacity L | External dimensions (height x depth x width) mm | Pressure pump | Compressor kW | Heating capacity kW | Control accuracy ℃ | Condenser | Cold water working pressure MPa | Refrigerant charge kg | Refrigerant | Cooling capacity kW | Cooler | Working liquid temperature range ℃ | Usable flow rate range L/min | Operating ambient temperature range ℃ | Fan motor output W | Breaker capacity A |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
![]() |
RKE750C-VRA |
Available upon quote |
2.2 |
Three-phase 200±10% (50/60) 220±10% (50/60) |
5.3 |
Compressor rotation speed control |
82 |
1.6 |
0.42 |
About 17 |
813 (853) ×690 (695) ×375 (398) |
Structure: multi-stage spiral horizontal type |
Structure: Fully enclosed rotary type (inverter driven) |
0.7 |
±0.1 (±2.0 when energy saving mode is set) |
Corrugated fin & tube type parallel flow type |
0.05~0.3 |
0.65 |
R1234yf |
3.3 |
Structure: plate heat exchanger |
5~40 |
10~30 |
-5~45 |
90 (inverter drive) |
10 |