Absorption chiller/heater Direct-fired dual-effect pack type (integrated cooling tower) SIGMA MIDY MP type MP-60 (Standard/Gas-fired)Handling Company
Kawaju Refrigeration Industry Co., Ltd.Categories
Image | Part Number | Price (excluding tax) | High head power supply current (50Hz/60Hz) A | High head power supply capacity (50Hz/60Hz) kVA | High head Wiring thickness mm2 | High head Total motor output during heating (50Hz/60Hz) | High head Total motor output during cooling (50Hz/60Hz) | Electricity power supply | Capacity Heating kW (Mcal/h) | Capacity Cooling kW (USRT) | Fuel consumption Gas (cooling/heating) m3N/h (kW) | Hot water inlet temperature - outlet temperature °C | Total motor output during standard head heating (50Hz/60Hz) | Total motor output during standard head cooling (50Hz/60Hz) | Standard head Power supply current (50Hz/60Hz) A | Standard lift power capacity (50Hz/60Hz) kVA | Standard lift Wire thickness mm2 | Connection size Absorption chiller/heater fuel inlet A | Connection size Absorption chiller/heater cold/hot water inlet/outlet A | Connection size Cooling tower automatic water supply A | Connection size Cooling tower manual water supply A | Connection size Cooling tower drain A | Connection size Cooling tower overflow A | Required supply pressure kPa | Cold and hot water flow m3/h | Cold and hot water pressure loss kPa | Amount of cold and hot water held m3 | Chilled water inlet temperature - outlet temperature °C | Pump high head Motor output kW | Pump high head External head (50Hz/60Hz) | Pump standard head Motor output kW | Pump standard head External lift (50Hz/60Hz) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
MP-60 (Standard/Gas fired) |
Available upon quote |
62.1/58.9 |
20.9/19.8 |
Twenty two |
7.30/7.30kW |
13.35/13.35kW |
200V, 3Φ |
171 (147) |
211 (60) |
13A gas |
55.5 → 60.0 |
5.50/5.50kW |
11.55/11.55kW |
55.7/52.5 |
18.7/17.6 |
Twenty two |
32 |
80 |
15 |
15 |
15 |
50 |
1.96 |
33 |
32.4 |
0.091 |
12.5 → 7.0 |
5.5 |
318.3/325.3 |
3.7 |
231.8/228.8kPa |